Loss of the ELAC 1 MON BUS 1 Signal for the SEC 2
TASK 27-93-00-810-906-A
Loss of the ELAC 1 MON BUS 1 Signal for the SEC 2
1. Possible Causes
A. Referenced Information
3. Fault Confirmation
Subtask 27-93-00-740-140-A 4. Fault Isolation
Subtask 27-93-00-810-144-A
[Rev.8 from Aug 2018]
2026.04.04 04:28:05 UTC
Loss of the ELAC 1 MON BUS 1 Signal for the SEC 2
1. Possible Causes
wiring of the DGO 01 signal of the ELAC 1 (2CE1) MON part
A. Referenced Information
| REFERENCE | DESIGNATION |
|---|---|
| AWM 209231 | |
| ASM 279250 | |
| AMM 27-96-00-740-001 | BITE Test of the EFCS (Ground Scanning) |
Subtask 27-93-00-740-140-A 4. Fault Isolation
Subtask 27-93-00-810-144-A
A. If the BITE test gives the maintenance message:
ELAC1 MON BUS1
Subtask 27-93-00-740-141-A ELAC1 MON BUS1
- Do a check and repair if necessary the
wiring of the DGO 01 signal of the ELAC 1 (2CE1) MON part , ASM 279250 from the terminal block 1837VT to the terminal block 1846VT AWM 209231.
B. Do the test given in Para. 3.