Loss of the FMGC 2 Bus for the ELAC 1
TASK 27-93-00-810-890-A
Loss of the FMGC 2 Bus for the ELAC 1
1. Possible Causes
A. Referenced Information
3. Fault Confirmation
Subtask 27-93-00-740-122-A 4. Fault Isolation
Subtask 27-93-00-810-135-A
[Rev.8 from Aug 2018]
2026.04.04 04:28:02 UTC
Loss of the FMGC 2 Bus for the ELAC 1
1. Possible Causes
- ELAC-1 [2CE1]
wiring of the DGI 05 signal from the ELAC 1 (2CE1) to the first terminal block
A. Referenced Information
| REFERENCE | DESIGNATION |
|---|---|
| ASM 279250 | |
| AMM 27-93-34-000-001 | Removal of the ELAC |
| AMM 27-93-34-400-001 | Installation of the ELAC |
| AMM 27-96-00-740-001 | BITE Test of the EFCS (Ground Scanning) |
Subtask 27-93-00-740-122-A 4. Fault Isolation
Subtask 27-93-00-810-135-A
A. If the BITE test gives the maintenance message:
ELAC1 COM OR BUS FROM FMGC2
or
ELAC1 MON OR BUS FROM FMGC2
Subtask 27-93-00-740-123-A ELAC1 COM OR BUS FROM FMGC2
or
ELAC1 MON OR BUS FROM FMGC2
- replace the ELAC-1 [2CE1] AMM 27-93-34-000-001 and AMM 27-93-34-400-001.
- do a check and repair the
wiring of the DGI 05 signal from the ELAC 1 (2CE1) to the first terminal block , COM or MON part as shown in the maintenance message ASM 279250.
B. Do the test given in Para. 3.