Loss of the Right Spoiler 5 Servo Valve Signal for the SEC 2


TASK 27-60-00-810-847-A
Loss of the Right Spoiler 5 Servo Valve Signal for the SEC 2


1. Possible Causes
  • SEC-2 [1CE2]
  • servovalve
  • wiring of the SV signal from the servo control (31CE10) to the SEC 2 (1CE2)
2. Job Set-up Information
 A. Referenced Information
REFERENCE
DESIGNATION
AMM 27-64-51-000-002
Removal of the Servo-Valve from the Spoiler Servo-Control
AMM 27-64-51-400-002
Installation of the Servo-Valve on the Spoiler Servo-Control
ASM 279403
AMM 27-94-34-000-001
Removal of the SEC
AMM 27-94-34-400-001
Installation of the SEC
AMM 27-96-00-710-020
Operational Test of the Side Stick Assembly (Activation for the BITE Test)
AMM 27-96-00-740-001
BITE Test of the EFCS (Ground Scanning)
3. Fault Confirmation
Subtask 27-60-00-700-126-A
A. Test
   (1) Do the operational test of the side stick assembly (activation for the BITE test) AMM 27-96-00-710-020.
   (2) Do the BITE test of the EFCS (Ground Scanning) AMM 27-96-00-740-001.
4. Fault Isolation
Subtask 27-60-00-810-096-B
A. If the BITE test gives the maintenance message:
R SPLR5 SERVO VLV 31CE10 OR OUTPUT FROM SEC2
   (1) If the fault continues:
NOTE: The resistance must be 500 ohms +/- 10 %.
   (2) If the fault continues:
  • Do a check and repair the wiring of the SV signal from the servo control (31CE10) to the SEC 2 (1CE2), ASM 279403.
Subtask 27-60-00-700-127-A
B. Do the tests given in Para. 3.