Failure of the Right Spoiler 5 Position Transducer


TASK 27-60-00-810-845-A
Failure of the Right Spoiler 5 Position Transducer


1. Possible Causes
  • SERVO CTL-SPLR5, R G [31CE10]
  • wiring of the POS XDCR SPLY signal from the servo control (31CE10) to the first terminal block
  • wiring of the POS XDCR V1, V2 signals from the servo control (31CE10) to the first terminal block
2. Job Set-up Information
 A. Referenced Information
REFERENCE
DESIGNATION
TSM TASK 27-90-00-810-804-A
Loss of the ACS2 Signal of the SEC2 MON Side
AMM 27-64-51-000-004
Removal of the Spoiler Servo Control
AMM 27-64-51-400-004
Installation of the Spoiler Servo Control
ASM 279403
AMM 27-96-00-710-020
Operational Test of the Side Stick Assembly (Activation for the BITE Test)
AMM 27-96-00-740-001
BITE Test of the EFCS (Ground Scanning)
3. Fault Confirmation
Subtask 27-60-00-700-122-B
A. Test
   (1) Do the operational test of the side stick assembly (activation for the BITE test) AMM 27-96-00-710-020.
   (2) Do the BITE test of the EFCS (Ground Scanning) AMM 27-96-00-740-001.
     (a) If the ground scanning gives the maintenance message:
R SPLR5 POS XDCR 31CE10
  • refer to the Para. Fault Isolation.
     (b) If the ground scanning gives the maintenance messages:
R SPLR5 POS XDCR 31CE10
L SPLR5 POS XDCR 31CE9
4. Fault Isolation
Subtask 27-60-00-810-094-B
A. If the BITE test gives the maintenance message:
R SPLR5 POS XDCR 31CE10
NOTE: The resistance of primary and secondary windings must be between 30 ohms and 500 ohms.
   (1) If the fault continues:
  • do a check and repair the wiring of the POS XDCR SPLY signal from the servo control (31CE10) to the first terminal block, ASM 279403.
   (2) If the fault continues:
  • do a check and repair the wiring of the POS XDCR V1, V2 signals from the servo control (31CE10) to the first terminal block, ASM 279403.
Subtask 27-60-00-700-123-A
B. Do the tests given in Para. 3.