Wrong Inhibit Sign From Cargo Door Yellow System


TASK 27-51-00-810-841-A
Wrong Inhibit Sign From Cargo Door Yellow System


1. Possible Causes
  • RELAY-SCCB PWR SPLY 3811GX
  • TIME RELAY 3816GX
2. Job Set-up Information
 A. Referenced Information
REFERENCE
DESIGNATION
ASM 292401
AMM 31-32-00-860-006
Procedure to Get Access to the SYSTEM REPORT/TEST F/CTL Page
3. Fault Confirmation
Subtask 27-51-00-710-072-A
A. Test
   (1) Get access to the SYSTEM REPORT/TEST F/CTL page AMM 31-32-00-860-006.
   (2) Get access to the SFCC-2 flap discrete i/p status page:
NOTE: The cargo door signal status is shown as follows:
  • sgoi: 0 = cargo door closed
  • sgoi: 1 = cargo door open
   (3) Make sure that the cargo doors are closed.
4. Fault Isolation
Subtask 27-51-00-810-093-A
A. Procedure
   (1) If the SFCC-2 flap dicrete i/p status page shows sgoi: 1:
     (a) Do a check for 28VDC at the RELAY-SCCB PWR SPLY 3811GX connector pin X1 ASM 292401.
     (b) If there is no 28VDC replace the RELAY-SCCB PWR SPLY 3811GX.
     (c) If there is 28VDC replace the TIME RELAY 3816GX (Ref. ASM 2924/01).
   (2) Do the test in para 3A. and make sure that the cargo door indications are correct.
   (3) Get access to the SFCC-2 system status flap, and make sure that the message 'inhibit signal from cargo yellow door system' is not shown.