Loss of the Signal of the Right Yellow Elevator-Servocontrol Solenoid Valve by the SEC 1
TASK 27-30-00-810-844-A
Loss of the Signal of the Right Yellow Elevator-Servocontrol Solenoid Valve by the SEC 1
A. Referenced Information
3. Fault Confirmation
Subtask 27-30-00-700-120-A
Subtask 27-30-00-810-085-A
[Rev.8 from Aug 2018]
2026.04.04 04:27:34 UTC
Loss of the Signal of the Right Yellow Elevator-Servocontrol Solenoid Valve by the SEC 1
CAUTION:
DO NOT SWAP FLIGHT CONTROL COMPUTERS. IF THERE IS A SHORT CIRCUIT, YOU WILL CAUSE DAMAGE TO A SERVICEABLE COMPUTER WHEN YOU SWAP THEM.
1. Possible Causes- solenoid valve of the servocontrol 34CE2
- SERVO CTL-R ELEVATOR, INBD Y [34CE2]
- SEC-1 [1CE1]
wiring of the SOL VLV2 signal from the servocontrol (34CE2) to the SEC1 (1CE1) wiring from the SEC1 (1CE1) COM part to the SEC1 MON part - ELAC-2 [2CE2]
A. Referenced Information
| REFERENCE | DESIGNATION |
|---|---|
| AMM 27-34-51-000-001 | Removal of the Elevator Servo Control |
| AMM 27-34-51-000-005 | Removal of the Solenoid Valve of the Elevator Servo-Control Actuator |
| AMM 27-34-51-400-001 | Installation of the Elevator Servo Control |
| AMM 27-34-51-400-004 | Installation of the Solenoid Valve of the Elevator Servo-Control Actuator |
| AMM 27-93-34-000-001 | Removal of the ELAC |
| AMM 27-93-34-400-001 | Installation of the ELAC |
| ASM 279407 | |
| AMM 27-94-34-000-001 | Removal of the SEC |
| AMM 27-94-34-400-001 | Installation of the SEC |
| AMM 27-96-00-710-020 | Operational Test of the Side Stick Assembly (Activation for the BITE Test) |
| AMM 27-96-00-740-001 | BITE Test of the EFCS (Ground Scanning) |
Subtask 27-30-00-700-120-A
A. Test
(1) Do the operational test of the side stick assembly (Activation for the BITE test) AMM 27-96-00-710-020.
4. Fault Isolation(1) Do the operational test of the side stick assembly (Activation for the BITE test) AMM 27-96-00-710-020.
NOTE: Before you start the operational test procedure, release the FLT CTL/ELAC 1, FLT CTL/ELAC 2 and FLT CTL/SEC 2 pushbutton switches (on these pushbutton switches the OFF legends come on).
(2) Do the BITE test of the EFCS (ground scanning) AMM 27-96-00-740-001. Subtask 27-30-00-810-085-A
A. If the test gives the maintenance message:
SEC1 MON OR WIRING TO R Y ELEV SOL VLV 34CE2
(1) Remove the SEC1 AMM 27-94-34-000-001.
(2) At the SEC1 receptacle, do a check of the resistance between the pin AB/15D and the pin AE/15G ASM 279407.
a Replace the solenoid valve of the servocontrol 34CE2 AMM 27-34-51-000-005 and AMM 27-34-51-400-004.
b Do again a check of the resistance of the solenoid valve between the pin C/J and the pin C/U of the inboard elevator servocontrol (34CE2) (40 to 100 Ohms).
a Repair thewiring of the SOL VLV2 signal from the servocontrol (34CE2) to the SEC1 (1CE1) , from the pin C/J to the pin AB/15D and from the pin C/U to the pin AE/15G ASM 279407:
b Replace the SEC-1 [1CE1] AMM 27-94-34-000-001 and AMM 27-94-34-400-001.
(b) If the resistance is more than 100 Ohms:
a Replace the solenoid valve of the servocontrol 34CE2 AMM 27-34-51-000-005 and AMM 27-34-51-400-004.
b Do again a check of the resistance of the solenoid valve between the pin C/J and the pin C/U of the inboard elevator servocontrol (34CE2) (40 to 100 Ohms).
a Repair thewiring of the SOL VLV2 signal from the servocontrol (34CE2) to the SEC1 (1CE1) , from the pin C/J to the pin AB/15D and from the pin C/U to the pin AE/15G ASM 279407:
b Install the SEC1 AMM 27-94-34-400-001.
(c) If the resistance values are in the specified limits:
wiring from the SEC1 (1CE1) COM part to the SEC1 MON part , from the pin AB/12F to the pin AE/15E ASM 279407:
a If the wiring is correct:
a Repair the wiring of the solenoid valve signal from the SERVO CTL-R ELEVATOR, INBD Y [34CE2] to the SEC-1 [1CE1] .
b Replace the SEC-1 [1CE1] AMM 27-94-34-000-001 and AMM 27-94-34-400-001.
(4) If the fault continues:
Subtask 27-30-00-700-121-A SEC1 MON OR WIRING TO R Y ELEV SOL VLV 34CE2
(1) Remove the SEC1 AMM 27-94-34-000-001.
(2) At the SEC1 receptacle, do a check of the resistance between the pin AB/15D and the pin AE/15G ASM 279407.
NOTE: The resistance must be between 40 and 100 Ohms.
(a) If the resistance is less than 40 Ohms: - at the inboard elevator servocontrol (34CE2), do a check of the resistance of the solenoid valve between the pin C/J and the pin C/U ASM 279407.
NOTE: The resistance must be between 40 and 100 Ohms.
1 If the resistance values are out of the specified limits:a Replace the solenoid valve of the servocontrol 34CE2 AMM 27-34-51-000-005 and AMM 27-34-51-400-004.
b Do again a check of the resistance of the solenoid valve between the pin C/J and the pin C/U of the inboard elevator servocontrol (34CE2) (40 to 100 Ohms).
- If the resistance values are out of the specified limits:
. Replace the SERVO CTL-R ELEVATOR, INBD Y [34CE2] AMM 27-34-51-000-001 and AMM 27-34-51-400-001.
. Replace the SEC-1 [1CE1] AMM 27-94-34-000-001 and AMM 27-94-34-400-001. - If the resistance values are in the specified limits:
Replace the SEC-1 [1CE1] AMM 27-94-34-000-001 and AMM 27-94-34-400-001.
a Repair the
b Replace the SEC-1 [1CE1] AMM 27-94-34-000-001 and AMM 27-94-34-400-001.
(b) If the resistance is more than 100 Ohms:
- at the inboard elevator servocontrol (34CE2), do a check of the resistance of the solenoid valve between the pin C/J and the pin C/U ASM 279407.
NOTE: The resistance must be between 40 and 100 Ohms.
1 If the resistance values are out of the specified limits:a Replace the solenoid valve of the servocontrol 34CE2 AMM 27-34-51-000-005 and AMM 27-34-51-400-004.
b Do again a check of the resistance of the solenoid valve between the pin C/J and the pin C/U of the inboard elevator servocontrol (34CE2) (40 to 100 Ohms).
- If the resistance values are out of the specified limits:
. Replace the SERVO CTL-R ELEVATOR, INBD Y [34CE2] AMM 27-34-51-000-001 and AMM 27-34-51-400-001.
. Install the SEC1 AMM 27-94-34-400-001. - If the resistance values are in the specified limits:
Install the SEC1 AMM 27-94-34-400-001.
a Repair the
b Install the SEC1 AMM 27-94-34-400-001.
(c) If the resistance values are in the specified limits:
- See Para. (3).
NOTE: The resistance must be more than 100 Meghoms.
(a) If the resistance is more than 100 Megohms: - Replace the SEC-1 [1CE1] AMM 27-94-34-000-001 and AMM 27-94-34-400-001.
- Replace the solenoid valve AMM 27-34-51-000-005 and AMM 27-34-51-400-004.
- Replace the SERVO CTL-R ELEVATOR, INBD Y [34CE2] AMM 27-34-51-000-001 and AMM 27-34-51-400-001.
a If the wiring is correct:
- replace the SEC-1 [1CE1] AMM 27-94-34-000-001 and AMM 27-94-34-400-001.
- repair it
- install the SEC1 AMM 27-94-34-400-001.
- At the SERVO CTL-R ELEVATOR, INBD Y [34CE2] , do a check of the insulation between pin C/U (pin C/J) and the ground.
- Replace the solenoid valve AMM 27-34-51-000-005 and AMM 27-34-51-400-004.
- If the resistance is less than 100 Megohms:
.Replace the SERVO CTL-R ELEVATOR, INBD Y [34CE2] AMM 27-34-51-000-001 and AMM 27-34-51-400-001.
.Replace the SEC-1 [1CE1] AMM 27-94-34-000-001 and AMM 27-94-34-400-001.
a Repair the wiring of the solenoid valve signal from the SERVO CTL-R ELEVATOR, INBD Y [34CE2] to the SEC-1 [1CE1] .
b Replace the SEC-1 [1CE1] AMM 27-94-34-000-001 and AMM 27-94-34-400-001.
(4) If the fault continues:
- replace the ELAC-2 [2CE2] , (MON part relay K2), AMM 27-93-34-000-001 and AMM 27-93-34-400-001.
B. Do the tests given in Para. 3.