CAN Bus A or CAN Bus B Failure
TASK 26-16-00-810-816-A
CAN Bus A or CAN Bus B Failure
1. Possible Causes
2. Job Set-up Information
A. Referenced Information
3. Fault Confirmation
Subtask 26-16-00-865-062-A ** ON A/C NOT FOR ALL
Subtask 26-16-00-810-076-A ** ON A/C NOT FOR ALL
Subtask 26-16-00-860-065-A ** ON A/C NOT FOR ALL
[Rev.8 from Aug 2018]
2026.04.04 04:27:19 UTC
CAN Bus A or CAN Bus B Failure
1. Possible Causes
2. Job Set-up Information
A. Referenced Information
| REFERENCE | DESIGNATION |
|---|---|
| AMM 23-73-34-000-001 | Removal of the CIDS Director |
| AMM 23-73-34-400-001 | Installation of the CIDS Director |
| AMM 26-10-00-740-802 | Ground Scanning of the Cabin Intercommunication Data-System (CIDS) - Smoke Detection Function (SDF) |
| ASM 261602 | |
| AMM 26-16-15-000-001 | Removal of the Cargo-Compartment Smoke Detectors |
| AMM 26-16-15-400-001 | Installation of the Cargo-Compartment Smoke Detectors |
Subtask 26-16-00-865-062-A ** ON A/C NOT FOR ALL
A. Table of the circuit breakers used in this procedure:
Subtask 26-16-00-710-073-A ** ON A/C NOT FOR ALL | PANEL | DESIGNATION | FIN | LOCATION |
|---|---|---|---|
| ** ON A/C NOT FOR ALL | |||
| 49VU | COM/CIDS/DIR ESS/2 | 157RH | G02 |
| ** ON A/C NOT FOR ALL | |||
| 49VU | AIR COND/CIDS/SDF/DIR2 ESS | 18WH | C06 |
| 49VU | AIR COND/CIDS/SDF/DIR1 ESS | 15WH | C05 |
| 49VU | COM/CIDS/DIR ESS/1 | 150RH | G01 |
| ** ON A/C NOT FOR ALL | |||
| 49VU | COM DIR ESS/2 | 157RH | G02 |
| ** ON A/C NOT FOR ALL | |||
| 121VU | COM NAV/CIDS/DIR NORM/2 | 156RH | M06 |
| 121VU | COM NAV/CIDS/DIR NORM/1 | 151RH | M05 |
| 121VU | COM NAV/CIDS/DIR NORM/1 | 151RH | M05 |
| ** ON A/C NOT FOR ALL | |||
| 121VU | COM/CIDS/DIR 2/BAT | 146RH | P14 |
| 121VU | COM/CIDS/DIR 1/BAT | 147RH | P13 |
| ** ON A/C NOT FOR ALL | |||
| 121VU | COM NAV/CIDS/DIR NORM/2 | 156RH | M07 |
| 121VU | COM NAV/CIDS/DIR NORM/1 | 151RH | M06 |
| 121VU | COM NAV/CIDS/DIR NORM/1 | 151RH | M06 |
| ** ON A/C NOT FOR ALL | |||
| 122VU | AIR COND/CIDS/SDF/DIR NORM/2 | 14WH | T18 |
| 122VU | AIR COND/CIDS/SDF/DIR NORM/1 | 17WH | T17 |
B. Test
(1) Deactivation of the CIDS Directors
(a) On circuit breaker panel 49VU, open circuit breakers 15WH and 18WH, then open circuit breakers 150RH and 157RH.
(b) On circuit breaker panel 121VU, open circuit breakers 17WH and 14WH, then open circuit breakers 151RH and 156RH.
(2) Reactivation of the CIDS Directors
(a) After a minimum of 5 seconds from power-down, on circuit breaker panel 121VU, close circuit breakers 151RH and 156RH.
(b) On circuit breaker panel 49VU, close circuit breakers 150RH and 157RH.
(d) On circuit breaker panel 121VU, in maximum 2 seconds after the CIDS-SDF1 and CIDS-SDF2 essential busses are energized, close circuit breakers 17WH and 14WH at the same time.
(3) After a minimum time of 30 seconds, do the Ground Scanning of the Cabin Intercommunication Data-System (CIDS) - Smoke Detection Function (SDF) AMM 26-10-00-740-802.
4. Fault Isolation(1) Deactivation of the CIDS Directors
(a) On circuit breaker panel 49VU, open circuit breakers 15WH and 18WH, then open circuit breakers 150RH and 157RH.
(b) On circuit breaker panel 121VU, open circuit breakers 17WH and 14WH, then open circuit breakers 151RH and 156RH.
(2) Reactivation of the CIDS Directors
(a) After a minimum of 5 seconds from power-down, on circuit breaker panel 121VU, close circuit breakers 151RH and 156RH.
(b) On circuit breaker panel 49VU, close circuit breakers 150RH and 157RH.
NOTE: The CIDS-SDF1 and CIDS-SDF2 must be energized in maximum 30 seconds after the CIDS is energized.
(c) On circuit breaker panel 49VU, close circuit breakers 15WH and 18WH at the same time. (d) On circuit breaker panel 121VU, in maximum 2 seconds after the CIDS-SDF1 and CIDS-SDF2 essential busses are energized, close circuit breakers 17WH and 14WH at the same time.
(3) After a minimum time of 30 seconds, do the Ground Scanning of the Cabin Intercommunication Data-System (CIDS) - Smoke Detection Function (SDF) AMM 26-10-00-740-802.
Subtask 26-16-00-810-076-A ** ON A/C NOT FOR ALL
A. If the test gives a different maintenance message:
Subtask 26-16-00-810-093-A ** ON A/C NOT FOR ALL - Do the trouble shooting procedure related to the maintenance message.
B. If the test gives the maintenance message WRG: CAN BUS X:
(a) Replace DIR-CIDS, 1 [101RH] AMM 23-73-34-000-001 and AMM 23-73-34-400-001.
(4) If the fault continues:
(a) Replace DIR-CIDS, 2 [102RH] AMM 23-73-34-000-001 and AMM 23-73-34-400-001.
(5) If the fault continues:
1 Do a check and repair the wiring of the last smoke detector on the bus between pins R and P (bridgewire) ASM 261602.
2 If the fault continues:
1 Replace all the smoke detectors on the related CAN bus one by one AMM 26-16-15-000-001 and AMM 26-16-15-400-001.
After each smoke detector replacement, examine if the measured resistance value has changed.
2 If the fault continues:
1 Do a check and repair the wiring between CAN H and GND for short circuits ASM 261602.
2 If the fault continues:
(a) Do a check and if necessary repair the shield of the wiring between DIR-CIDS, 1 [101RH] (or DIR-CIDS, 2 [102RH] ) and the LDCC smoke detectors ASM 261602.
Subtask 26-16-00-710-082-A ** ON A/C NOT FOR ALL - Do a check of the CAN BUS wiring between DIR-CIDS, 1 [101RH] and the last smoke detector on the related CAN BUS for continuity ASM 261602.
- Do a check and repair all the connectors and the wiring between DIR-CIDS, 1 [101RH] and the smoke detectors ASM 261602.
- Do a check of the CAN bus wiring between DIR-CIDS, 2 [102RH] and the last smoke detector on the related CAN BUS for continuity ASM 261602.
- Do a check and repair all the connectors and the wiring between DIR-CIDS, 2 [102RH] and the smoke detectors ASM 261602.
(a) Replace DIR-CIDS, 1 [101RH] AMM 23-73-34-000-001 and AMM 23-73-34-400-001.
(4) If the fault continues:
(a) Replace DIR-CIDS, 2 [102RH] AMM 23-73-34-000-001 and AMM 23-73-34-400-001.
(5) If the fault continues:
- Measure the resistance between CAN H and CAN L at the first smoke detector on the related CAN bus. All the equipment (the CIDS directors and the smoke detectors) other than the first smoke detector must be connected to the CAN bus.
1 Do a check and repair the wiring of the last smoke detector on the bus between pins R and P (bridgewire) ASM 261602.
2 If the fault continues:
- Replace the last smoke detector on the CAN bus AMM 26-16-15-000-001 and AMM 26-16-15-400-001.
1 Replace all the smoke detectors on the related CAN bus one by one AMM 26-16-15-000-001 and AMM 26-16-15-400-001.
After each smoke detector replacement, examine if the measured resistance value has changed.
2 If the fault continues:
- Do a check and repair the wiring between CAN H and CAN L for short circuits ASM 261602.
1 Do a check and repair the wiring between CAN H and GND for short circuits ASM 261602.
2 If the fault continues:
- Do a check and repair the wiring between CAN L and GND for short circuits ASM 261602.
(a) Do a check and if necessary repair the shield of the wiring between DIR-CIDS, 1 [101RH] (or DIR-CIDS, 2 [102RH] ) and the LDCC smoke detectors ASM 261602.
C. Do the test given in Para. 3.
5. Close-upSubtask 26-16-00-860-065-A ** ON A/C NOT FOR ALL
A. Put the aircraft back to its initial configuration.
(1) Make sure that the work area is clean and clear of tools and other items.
(1) Make sure that the work area is clean and clear of tools and other items.