Loss of APU Fire- Test LOOP B
TASK 26-13-00-810-811-A
Loss of APU Fire- Test LOOP B
1. Possible Causes
2. Job Set-up Information
A. Referenced Information
3. Fault Confirmation
Subtask 26-13-00-710-070-A 4. Fault Isolation
Subtask 26-13-00-810-073-A
[Rev.8 from Aug 2018]
2026.04.04 04:27:17 UTC
Loss of APU Fire- Test LOOP B
1. Possible Causes
2. Job Set-up Information
A. Referenced Information
| REFERENCE | DESIGNATION |
|---|---|
| AMM 26-12-12-000-001 | Removal of the ENG/APU Fire Panel |
| AMM 26-12-12-400-001 | Installation of the ENG/APU Fire Panel |
| AMM 26-13-00-710-002 | BITE Test of the APU Fire and Overheat Detection System |
| ASM 261301 | |
| AMM 26-13-34-000-001 | Removal of the APU Fire-Detection Unit (FDU) |
| AMM 26-13-34-400-001 | Installation of the APU Fire-Detection Unit (FDU) |
Subtask 26-13-00-710-070-A 4. Fault Isolation
Subtask 26-13-00-810-073-A
A. If the test gives the maintenance message CHECK FDU APU FIRE TEST PB SW/FDU APU:
Subtask 26-13-00-710-071-A - replace the FDU-APU [13WG] AMM 26-13-34-000-001 and AMM 26-13-34-400-001.
- do a check of the wiring between the ENG/APU fire panel 1WD pin E/M and the FDU APU pin B/C and repair if necessary ASM 261301.
- do a check and repair the wiring from the ENG/APU fire panel 1WD pin E/M to the circuit breaker 2WG ASM 261301.
- replace the ENG/APU FIRE PNL [1WD]
AMM 26-12-12-000-001 and AMM 26-12-12-400-001.
B. Do the test given in Para. 3.