Loss of APU Fire- Test LOOP A


TASK 26-13-00-810-810-A
Loss of APU Fire- Test LOOP A


1. Possible Causes
  • FDU-APU [13WG]
  • wiring
  • ENG/APU FIRE PNL [1WD]
2. Job Set-up Information
 A. Referenced Information
REFERENCE
DESIGNATION
AMM 26-12-12-000-001
Removal of the ENG/APU Fire Panel
AMM 26-12-12-400-001
Installation of the ENG/APU Fire Panel
AMM 26-13-00-710-002
BITE Test of the APU Fire and Overheat Detection System
ASM 261301
AMM 26-13-34-000-001
Removal of the APU Fire-Detection Unit (FDU)
AMM 26-13-34-400-001
Installation of the APU Fire-Detection Unit (FDU)
3. Fault Confirmation
Subtask 26-13-00-710-068-A
A. Do the BITE test of the APU fire and overheat detection system AMM 26-13-00-710-002.
4. Fault Isolation
Subtask 26-13-00-810-072-A
A. If the test gives the maintenance message CHECK FDU APU FIRE TEST PB SW/FDU APU:
   (1) If the fault continues:
  • do a check of the wiring between the ENG/APU fire panel 1WD pin F/M and the FDU APU pin A/C and repair if necessary ASM 261301.
   (2) If the fault continues:
  • do a check and repair the wiring from the ENG/APU fire panel 1WD pin F/M to the circuit breaker 1WG ASM 261301.
   (3) If the fault continues:
Subtask 26-13-00-710-069-A
B. Do the test given in Para. 3.