Ground Service Buses cannot be supplied from the External Power
TASK 24-42-00-810-803-A
Ground Service Buses cannot be supplied from the External Power
1. Possible Causes
A. Referenced Information
3. Fault Confirmation
Subtask 24-42-00-710-054-A
Subtask 24-42-00-810-052-A
[Rev.8 from Aug 2018]
2026.04.04 04:26:55 UTC
Ground Service Buses cannot be supplied from the External Power
1. Possible Causes
- RCPT-EXT PWR [20XG]
- SW-MAINT BUS/ON [5XX]
- wiring
- RELAY-GND/FLT SELECT CTL [7XX]
- CNTOR-AC SVCE BUS NORM SPLY [12XN]
- CNTOR-AC GND SVCE SPLY [12XX]
- RELAY-TR 2 OVHT [6XX]
- TR-2 [1PU2]
A. Referenced Information
| REFERENCE | DESIGNATION |
|---|---|
| AMM 24-32-51-000-001 | Removal of the Transformer Rectifier |
| AMM 24-32-51-400-001 | Installation of the Transformer Rectifier |
| AMM 24-41-51-000-001 | Removal of the External Power Receptacle |
| AMM 24-41-51-400-001 | Installation of the External Power Receptacle |
| AMM 24-42-00-861-001 | Energize the Ground Service Network from the External Power |
| ASM 244201 | |
| AMM 24-42-55-000-001 | Removal of the Contactors |
| AMM 24-42-55-400-001 | Installation of the Contactors |
| AMM 24-51-55-000-001 | Removal of the AC Service Bus Normal Supply Contactor |
| AMM 24-51-55-400-001 | Installation of the AC Service Bus Normal Supply Contactor |
Subtask 24-42-00-710-054-A
A. Energize the Ground Service Network from the External Power AMM 24-42-00-861-001.
4. Fault IsolationNOTE: Examine the external power supply-cable and the external power receptacle before you do the connection.
If you find corrosion or damage, or if the pins are not aligned correctly, replace the RCPT-EXT PWR [20XG] AMM 24-41-51-000-001 and AMM 24-41-51-400-001.
If you find corrosion or damage, or if the pins are not aligned correctly, replace the RCPT-EXT PWR [20XG] AMM 24-41-51-000-001 and AMM 24-41-51-400-001.
Subtask 24-42-00-810-052-A
A. If the above procedure confirms that the EXT PWR/NOT IN USE indicator light stays on:
Subtask 24-42-00-710-055-A - Do a check of the position of the MAINT BUS/ON switch (5XX).
- is a check for 28VDC at pin A/B2 of the GND/FLT selection control relay (7XX) ASM 244201.
- Replace the SW-MAINT BUS/ON [5XX] .
- Do a check and repair the wiring between pin 2A of the MAINT BUS/ON switch (5XX) and pin A/B2 of the GND/FLT selection control relay (7XX) ASM 244201.
- Do a check for 28VDC at pin B/12 of the AC service bus normal supply contactor (12XN).
- Replace the RELAY-GND/FLT SELECT CTL [7XX] .
- Do a check and repair the wiring between pin B/12 of the AC service bus normal supply contactor (12XN) and pin A/B3 of the GND/FLT selection control relay (7XX).
- Do a check for 28VDC at pin B/3 of the AC ground service supply contactor (12XX).
- Replace the CNTOR-AC SVCE BUS NORM SPLY [12XN] AMM 24-51-55-000-001 and AMM 24-51-55-400-001.
- Do a check and repair the wiring between pin B/3 of the AC ground service supply contactor (12XX) and pin B/10 of the AC service bus normal supply contactor (12XN).
- Replace the CNTOR-AC GND SVCE SPLY [12XX] AMM 24-42-55-000-001 and AMM 24-42-55-400-001.
- Do a check for 28VDC at pin 1A or 1B of the MAINT BUS/ON switch (5XX) ASM 244201.
- Replace the SW-MAINT BUS/ON [5XX] .
- Do a check for 28VDC between pins A/X2 and A/A2 of the TR 2 overheat relay (6XX).
- Replace the RELAY-TR 2 OVHT [6XX] .
- Do a check for 28VDC between pin A/A2 or A/X1 of the TR 2 overheat relay (6XX) and the ground.
- Do a check and repair the wiring between pin 2 of the circuit breaker (6XG) and pins A/A2 and A/X1 of the TR 2 overheat relay (6XX) ASM 244201.
- Do a check for 28VDC between pin A/X1 of the TR 2 overheat relay (6XX) and pin B/F of the TR 2 (1PU2).
- Replace the TR-2 [1PU2] AMM 24-32-51-000-001 and AMM 24-32-51-400-001.
- Do a check and repair the wiring between pin A/X2 of the TR 2 overheat relay (6XX) and pin B/F of the TR 2 (1PU2) ASM 244201.
B. Do the procedure given in Para. 3.A.