Failure of the RS422 Electrical Connection between the GPCU and the GCU 2
TASK 24-41-00-810-807-A
Failure of the RS422 Electrical Connection between the GPCU and the GCU 2
1. Possible Causes
2. Job Set-up Information
A. Referenced Information
3. Fault Confirmation
Subtask 24-41-00-710-061-A ** ON A/C NOT FOR ALL 4. Fault Isolation
Subtask 24-41-00-810-056-A ** ON A/C NOT FOR ALL
[Rev.8 from Aug 2018]
2026.04.04 04:26:53 UTC
Failure of the RS422 Electrical Connection between the GPCU and the GCU 2
1. Possible Causes
2. Job Set-up Information
A. Referenced Information
| REFERENCE | DESIGNATION |
|---|---|
| AMM 24-22-34-000-001 | Removal of the GCU-1(2) |
| AMM 24-22-34-400-001 | Installation of the GCU-1(2) |
| AMM 24-41-00-740-004 | Operational Check of the GPCU via the CFDS |
| ASM 244102 | |
| AMM 24-41-34-000-001 | Removal of the Ground Power Control Unit (GPCU) |
| AMM 24-41-34-400-001 | Installation of the Ground Power Control Unit (GPCU) |
Subtask 24-41-00-710-061-A ** ON A/C NOT FOR ALL 4. Fault Isolation
Subtask 24-41-00-810-056-A ** ON A/C NOT FOR ALL
A. If the test gives the maintenance message CHECK SERIAL LINK GPCU TO GCU 2:
Subtask 24-41-00-710-062-A ** ON A/C NOT FOR ALL - do a check of the wiring for short to ground or open circuit between respectively the GPCU pins A/12D, A/13D and the GCU 2 pins B/14C, B/14D ASM 244102.
- repair it.
- replace the GPCU [1XG] AMM 24-41-34-000-001 and AMM 24-41-34-400-001.
- replace the GCU-2 [1XU2] AMM 24-22-34-000-001 and AMM 24-22-34-400-001.
B. Do the test given in Para. 3.