Failure of the Connection between the GPCU and the APU GCU


TASK 24-41-00-810-802-A
Failure of the Connection between the GPCU and the APU GCU


1. Possible Causes
  • wiring
  • GPCU [1XG]
  • GCU-APU [1XS]
2. Job Set-up Information
 A. Referenced Information
REFERENCE
DESIGNATION
AMM 24-23-34-000-001
Removal of the GCU-APU
AMM 24-23-34-400-001
Installation of the GCU-APU
AMM 24-41-00-740-004
Operational Check of the GPCU via the CFDS
ASM 244102
AMM 24-41-34-000-001
Removal of the Ground Power Control Unit (GPCU)
AMM 24-41-34-400-001
Installation of the Ground Power Control Unit (GPCU)
3. Fault Confirmation
Subtask 24-41-00-710-051-A ** ON A/C NOT FOR ALL
A. Test
Do the operational check of the GPCU with the CFDS AMM 24-41-00-740-004.
4. Fault Isolation
Subtask 24-41-00-810-051-A ** ON A/C NOT FOR ALL
A. If the test gives the maintenance message CHECK SERIAL LINK GPCU TO GCU APU:
  • do a check of the wiring for open circuit or short to ground between respectively the APU GCU pins B/14C, B/14D and the GPCU pins A/14B, A/15B ASM 244102.
   (1) If the wiring is not correct:
  • repair it.
   (2) If the wiring is correct:
   (3) If the fault continues:
Subtask 24-41-00-710-052-A ** ON A/C NOT FOR ALL
B. Do the test given in Para. 3.