Failure of the Supply from the HOT BUS (702PP)


TASK 24-38-00-810-825-A
Failure of the Supply from the HOT BUS (702PP)


1. Possible Causes
  • wiring
  • P/BSW-ELEC/BAT 2 [7PB2]
  • BCL-2 [1PB2]
2. Job Set-up Information
 A. Referenced Information
REFERENCE
DESIGNATION
AMM 24-38-00-710-001
Operational Test of the Battery Charge Limiter (BCL), (with the CFDS)
ASM 243802
AMM 24-38-34-000-001
Removal of the Battery Charge Limiter (BCL)
AMM 24-38-34-400-001
Installation of the Battery Charge Limiter (BCL)
3. Fault Confirmation
Subtask 24-38-00-710-090-A
A. Test
Do the operational test of the BCL2 AMM 24-38-00-710-001.
4. Fault Isolation
Subtask 24-38-00-810-074-A
A. If the test gives the maintenance message CHECK HOT BUS 702PP/BCL2 CIRCUIT:
  • do a check of the wiring for open circuit between the circuit breaker BAT REF/BCL2 (9PB2) and the pin A/C of the BCL2 ASM 243802.
   (1) If the wiring is not correct:
  • repair it.
   (2) If the wiring is correct:
  • replace the P/BSW-ELEC/BAT 2 [7PB2] .
   (3) If the fault continues:
Subtask 24-38-00-710-091-A
B. Do the test given in Para. 3.