Abnormal Electrical Transient Time on AC 1 busbar during Switching from IDG 1 or External Power to APU Generator
TASK 24-23-00-810-828-A
Abnormal Electrical Transient Time on AC 1 busbar during Switching from IDG 1 or External Power to APU Generator
1. Possible Causes
A. Referenced Information
3. Fault Confirmation
Subtask 24-23-00-860-069-A ** ON A/C NOT FOR ALL
Subtask 24-23-00-810-081-C ** ON A/C NOT FOR ALL
[Rev.8 from Aug 2018]
2026.04.04 04:26:42 UTC
Abnormal Electrical Transient Time on AC 1 busbar during Switching from IDG 1 or External Power to APU Generator
1. Possible Causes
- MODULE DIODE UNIT [1164VD]
- wiring
- RELAY-APU AVAIL [6KD]
- GCU-APU [1XS]
- RELAY-GLC 1 AUX CTL [4XU1]
- GLC-1 [9XU1]
- BTC-1 [11XU1]
- RELAY-EPC AUX CTL [5XG]
- EPC [3XG]
- GLC-APU [3XS]
A. Referenced Information
| REFERENCE | DESIGNATION |
|---|---|
| AMM 24-22-55-000-001 | Removal of the Contactors |
| AMM 24-22-55-400-002 | Installation of the Contactors |
| ASM 242302 | |
| AWM 242304 | |
| AMM 24-23-34-000-001 | Removal of the GCU-APU |
| AMM 24-23-34-400-001 | Installation of the GCU-APU |
| AMM 24-23-55-000-001 | Removal of the APU GLC |
| AMM 24-23-55-400-001 | Installation of the APU GLC |
| AMM 24-41-00-861-002 | Energize the Aircraft Electrical Circuits from the External Power |
| AMM 24-41-55-000-001 | Removal of the External Power Contactor (EPC) |
| AMM 24-41-55-400-001 | Installation of the External Power Contactor (EPC) |
| AMM 31-60-00-860-001 | EIS Start Procedure |
| AMM 49-00-00-860-003 | APU Start by External Power |
| AMM 49-00-00-860-005 | APU Start by External Power |
| AMM 49-00-00-860-008 | APU Start by External Power |
| AMM 71-00-00-710-003 | Engine Automatic Start |
Subtask 24-23-00-860-069-A ** ON A/C NOT FOR ALL
A. Aircraft Maintenance Configuration
(1) Energize the aircraft electrical circuits from the external power AMM 24-41-00-861-002.
(2) Do the EIS start procedure (Upper ECAM DU and lower ECAM DU only)
AMM 31-60-00-860-001.
(3) Start the APU:
Subtask 24-23-00-710-061-A ** ON A/C NOT FOR ALL (1) Energize the aircraft electrical circuits from the external power AMM 24-41-00-861-002.
(2) Do the EIS start procedure (Upper ECAM DU and lower ECAM DU only)
AMM 31-60-00-860-001.
(3) Start the APU:
- GTCP 36-300 AMM 49-00-00-860-003
or - APS 3200 AMM 49-00-00-860-005
or - 131-9(A) AMM 49-00-00-860-008.
B. Test
(1) On the ELEC panel 35VU, release the BAT1 and BAT2 pushbutton switches:
(4) On the ELEC panel 35VU, push the EXT PWR pushbutton switch:
(8) If the fault continues, go to Para. 4.B.
Subtask 24-23-00-710-061-C ** ON A/C NOT FOR ALL (1) On the ELEC panel 35VU, release the BAT1 and BAT2 pushbutton switches:
- The OFF legend comes on.
- The ON legend goes off.
- The AVAIL legend comes on.
(4) On the ELEC panel 35VU, push the EXT PWR pushbutton switch:
- The ON legend comes on.
- The AVAIL legend goes off.
- The OFF legend goes off.
- The ON legend goes off.
- The AVAIL legend comes on.
(8) If the fault continues, go to Para. 4.B.
B. Test
(1) On the ECAM control panel, push the ELEC key (on the lower ECAM DU, the ELEC page comes into view).
(6) If the fault continues (long time with signifiant impacts in the cockpit), go to Para. 4.B.
4. Fault Isolation(1) On the ECAM control panel, push the ELEC key (on the lower ECAM DU, the ELEC page comes into view).
- Make sure that the APU energizes the aircraft electrical circuit correctly.
- The OFF legends are off.
- The green arrow from the DC BAT indication to the BAT 1 or the green line between the DC BAT indication and the BAT 1 is shown.
- The green arrow from the DC BAT indication to the BAT 2 or the green line between the DC BAT indication and the BAT 2 is shown.
- The ON legend goes off.
- The AVAIL legend comes on.
(6) If the fault continues (long time with signifiant impacts in the cockpit), go to Para. 4.B.
Subtask 24-23-00-810-081-C ** ON A/C NOT FOR ALL
A. If the fault stops:
(1) Replace the MODULE DIODE UNIT [1164VD] .
(2) If the fault continues:
(a) Do a check of the wiring AWM 242304 between:
Subtask 24-23-00-810-082-B ** ON A/C NOT FOR ALL (1) Replace the MODULE DIODE UNIT [1164VD] .
(2) If the fault continues:
(a) Do a check of the wiring AWM 242304 between:
- Pin D module 34 of the terminal block 1156VT and pin 44 of the diode module (1164VD) through the APU AVAIL relay (6KD)
- Pin S module 31 of the terminal block 1154VT and pin 43 of the diode module (1164VD).
- Replace the RELAY-APU AVAIL [6KD] .
- Repair it.
B. If the fault continues:
(1) Replace the RELAY-GLC 1 AUX CTL [4XU1] .
(2) If the fault continues:
Subtask 24-23-00-810-081-G ** ON A/C NOT FOR ALL (1) Replace the RELAY-GLC 1 AUX CTL [4XU1] .
(2) If the fault continues:
- Replace the GLC-1 [9XU1] AMM 24-22-55-000-001 and AMM 24-22-55-400-002.
C. If the fault stops:
(1) On ELEC panel 35VU, push the EXT PWR pushbutton switch:
(a) Release the BAT1 and BAT2 pushbutton switches:
Subtask 24-23-00-810-082-C ** ON A/C NOT FOR ALL (1) On ELEC panel 35VU, push the EXT PWR pushbutton switch:
- The ON legend comes on.
- The AVAIL legend goes off.
(a) Release the BAT1 and BAT2 pushbutton switches:
- The OFF legends come on.
- The OFF legends go off.
- The green arrow from the DC BAT indication to the BAT 1 or the green line between the DC BAT indication and the BAT 1 goes out of view.
- The green arrow from the DC BAT indication to the BAT 2 or the green line between the DC BAT indication and the BAT 2 goes out of view.
- The ON legend goes off.
- The AVAIL legend comes on.
- Replace GCU-APU [1XS] AMM 24-23-34-000-001 and AMM 24-23-34-400-001.
- Do a check and repair the wiring ASM 242302 between:
. Pin AA/12D of the APU GCU (1XS) and pin D3 of the external-power control relay (5XG)
. Pin AA/2D of the APU GCU (1XS) and the first terminal block.
- Start the engine 1 AMM 71-00-00-710-003.
- On the lower ECAM DU, on the ELEC page, make sure that there is a green line between the GEN1 indication and the AC1 busbar.
- On the lower ECAM DU, on the ELEC page, make sure that:
. The green arrow from the DC BAT indication to BAT 1 or the green line between the DC BAT indication and BAT 1 are not shown.
. The green arrow from the DC BAT indication to BAT 2 or the green line between the DC BAT indication and BAT 2 are not shown. - On the ELEC control panel 35VU:
. Release the GEN1 pushbutton switch.
. The OFF legend of the GEN1 pushbutton switch comes on.
- Replace RELAY-GLC 1 AUX CTL [4XU1] .
- Replace GLC-1 [9XU1] AMM 24-22-55-000-001 and AMM 24-22-55-400-002.
- If the fault continues:
- Replace BTC-1 [11XU1] AMM 24-22-55-000-001 and AMM 24-22-55-400-002.
D. If the fault continues:
(1) Replace the RELAY-EPC AUX CTL [5XG] .
(2) If the fault continues:
(1) Replace the RELAY-EPC AUX CTL [5XG] .
(2) If the fault continues:
- Replace the EPC [3XG] AMM 24-41-55-000-001 and AMM 24-41-55-400-001.
- Replace the GLC-APU [3XS] AMM 24-23-55-000-001 and AMM 24-23-55-400-001.