Failure of the IDG Cables


TASK 24-21-00-810-846-A
Failure of the IDG Cables


1. Possible Causes
  • IDG harness
  • IDG cables
  • IDG harness
2. Job Set-up Information
 A. Referenced Information
REFERENCE
DESIGNATION
AMM 24-21-61-000-802
Removal of the IDG Power Feeder-Cables
AMM 24-21-61-400-802
Installation of the IDG Power Feeder-Cables
AMM 24-92-00-000-001
Removal of the IDG Feeders from the Pylon
AMM 24-92-00-400-001
Installation of the IDG Feeders on the Pylon
AMM 71-51-43-000-043
Removal of the Generator Power Harness
AMM 71-51-43-400-043
Installation of the Generator Power Harness
AMM 71-51-44-000-001
Removal of the Generator Power Harness 238W0903
AMM 71-51-44-400-001
Installation of the Generator Power Harness 238W0903
3. Fault Confirmation
Subtask 24-21-00-869-068-A
A. Test
   (1) Not applicable
4. Fault Isolation
Subtask 24-21-00-810-109-B ** ON A/C NOT FOR ALL
A. Inspection
   (1) Disconnect the IDG cables on the pylon on affected engine.
   (2) Do a check of the connector for pin burning or arcing damage or corrosion
     (a) If there is pin burning/arcing damage or corrosion:
Subtask 24-21-00-810-109-E ** ON A/C NOT FOR ALL
A. Inspection
   (1) Disconnect the IDG cables on the pylon on affected engine.
   (2) Do a check of the connector for pin burning or arcing damage or corrosion
     (a) If there is pin burning/arcing damage or corrosion:
Subtask 24-21-00-810-109-G ** ON A/C NOT FOR ALL
A. Inspection
   (1) Disconnect the IDG cables on the pylon on affected engine.
   (2) Do a check of the connector for pin burning or arcing damage or corrosion
     (a) If there is pin burning/arcing damage or corrosion: