W DOC AIRBUS | TSM A320F

Failure of the GCU 1 Pin Programming


TASK 24-20-00-810-932-A
Failure of the GCU 1 Pin Programming


1. Possible Causes
  • GCU-1 [1XU1]
  • wiring
2. Job Set-up Information
 A. Referenced Information
REFERENCE
DESIGNATION
ASM 242202
AMM 24-22-34-000-001
Removal of the GCU-1(2)
AMM 24-22-34-400-001
Installation of the GCU-1(2)
AMM 24-41-00-740-002
Operational Check of the GAPCU via the CFDS
3. Fault Confirmation
Subtask 24-20-00-740-054-A ** ON A/C NOT FOR ALL
A. Test
   (1) Do the BITE test of the GAPCU AMM 24-41-00-740-002.
     (a) If the BITE test gives the message TEST FAILED:
  • do the trouble shooting given in Para 4.A.
     (b) If the BITE test gives the message TEST PASSED:
  • do the trouble shooting given in Para 4.B.
4. Fault Isolation
Subtask 24-20-00-810-181-A ** ON A/C NOT FOR ALL
A. If the BITE test gives the message TEST FAILED:
  • push the line key adjacent to the TEST FAILED message.
   (1) If the maintenance message GCU1 (1XU1) comes into view:
Subtask 24-20-00-810-125-B ** ON A/C NOT FOR ALL
B. If the BITE test gives the message TEST PASSED:
  • do a check of the pin programming wiring ASM 242202 of the GCU 1:
    . pin A/5A connected to ground
    . pin A/3E connected to ground
    . pin A/4G connected to ground
    . pins A/7C, A/8A, A/2E and A/5E not connected.
NOTE: The wiring diagram of the aircraft interface with the pin programming connections is necessary to do the trouble shooting procedure.
   (1) If the wiring is not correct:
  • repair or replace as necessary.
   (2) If the wiring is correct:
Subtask 24-20-00-740-055-A ** ON A/C NOT FOR ALL
C. Do the test given in Para. 3.
[Rev.8 from Aug 2018] 2026.04.04 04:26:25 UTC