Failure of the BTC 2 Status Sense-Circuit
TASK 24-20-00-810-921-A
Failure of the BTC 2 Status Sense-Circuit
1. Possible Causes
2. Job Set-up Information
A. Referenced Information
3. Fault Confirmation
Subtask 24-20-00-740-084-A ** ON A/C NOT FOR ALL
Subtask 24-20-00-810-184-A ** ON A/C NOT FOR ALL
[Rev.8 from Aug 2018]
2026.04.04 04:26:24 UTC
Failure of the BTC 2 Status Sense-Circuit
1. Possible Causes
2. Job Set-up Information
A. Referenced Information
| REFERENCE | DESIGNATION |
|---|---|
| ASM 242203 | |
| AMM 24-22-34-000-001 | Removal of the GCU-1(2) |
| AMM 24-22-34-400-001 | Installation of the GCU-1(2) |
| AMM 24-22-55-000-001 | Removal of the Contactors |
| AMM 24-22-55-400-002 | Installation of the Contactors |
| AMM 24-41-00-740-002 | Operational Check of the GAPCU via the CFDS |
Subtask 24-20-00-740-084-A ** ON A/C NOT FOR ALL
A. Test
(1) Do the BITE test of the GAPCU AMM 24-41-00-740-002.
4. Fault Isolation(1) Do the BITE test of the GAPCU AMM 24-41-00-740-002.
NOTE: If the CFDS message PB BUS TIE (10XU) / BTC2 (11XU2) / GCU2 (1XU2) comes into view when the flight crew or the maintenance personnel puts the BUS TIE pushbutton switch (10XU) in the released or OFF position the trouble shooting is not necessary. This can occur during an electrical system test or during trouble shooting.
If the flight crew or the maintenance personnel did not operate the BUS TIE pushbutton switch and this CFDS message comes into view, do the trouble shooting procedure that follows.
(a) If the BITE test gives the message TEST FAILED: If the flight crew or the maintenance personnel did not operate the BUS TIE pushbutton switch and this CFDS message comes into view, do the trouble shooting procedure that follows.
- do the trouble shooting given in Para 4.A.
- do the trouble shooting given in Para 4.B.
Subtask 24-20-00-810-184-A ** ON A/C NOT FOR ALL
A. If the BITE test gives the message TEST FAILED:
Subtask 24-20-00-810-173-A ** ON A/C NOT FOR ALL - push the line key adjacent to the TEST FAILED message.
- replace the GCU-2 [1XU2] AMM 24-22-34-000-001 and AMM 24-22-34-400-001.
B. If the BITE test gives the message TEST PASSED:
Subtask 24-20-00-740-085-A ** ON A/C NOT FOR ALL - replace the BTC-2 [11XU2] AMM 24-22-55-000-001 and AMM 24-22-55-400-002.
- do a check of the status sense wiring for an open circuit or high resistance condition between pin A/4C of the GCU 2 and pin B/29 of the BTC 2 ASM 242203.
- repair or replace as necessary.
- replace the GCU-2 [1XU2] AMM 24-22-34-000-001 and AMM 24-22-34-400-001.
C. When you replace a component or repair the wiring:
- do the subsequent flight before you do the check of the Class 3 Faults of the GAPCU from the CFDS to make sure that the system operates correctly.
If the test continues to give the fault message, continue the trouble shooting procedure.