Failure of the Generator Control Unit 2


TASK 24-20-00-810-871-A
Failure of the Generator Control Unit 2


1. Possible Causes
  • GCU-2 [1XU2]
  • wiring
2. Job Set-up Information
 A. Referenced Information
REFERENCE
DESIGNATION
ASM 242203
AMM 24-22-34-000-001
Removal of the GCU-1(2)
AMM 24-22-34-400-001
Installation of the GCU-1(2)
AMM 24-41-00-740-002
Operational Check of the GAPCU via the CFDS
3. Fault Confirmation
Subtask 24-20-00-740-060-A ** ON A/C NOT FOR ALL
A. Test
   (1) Do the BITE test of the GAPCU AMM 24-41-00-740-002.
     (a) If the BITE test gives the message TEST FAILED:
  • do the trouble shooting given in Para 4.A.
     (b) If the BITE test gives the message TEST PASSED:
  • stop the trouble shooting.
4. Fault Isolation
Subtask 24-20-00-810-128-A ** ON A/C NOT FOR ALL
A. If the BITE test gives the message TEST FAILED:
  • push the line key adjacent to the TEST FAILED message.
   (1) If the maintenance message GCU2 (1XU2) comes into view:
   (2) If the fault continues:
  • do a check and repair the wiring between the GCU 2 and the GLC 2 auxiliary control relay (4XU2) ASM 242203 for a short to 28VDC between:
    . pin B/10J of the GCU 2 and pin A/C3 of the ELEC/GEN 2 pushbutton switch (3XU2)
    . pin A/C1 of the ELEC/GEN 2 pushbutton switch and pin A/X1 of the GLC 2 auxiliary control relay.
Subtask 24-20-00-740-061-A ** ON A/C NOT FOR ALL
B. Do the test given in Para. 3.