Loss of the FCU Information on the FMGC 1
TASK 22-83-00-810-864-A
Loss of the FCU Information on the FMGC 1
1. Possible Causes
A. Referenced Information
3. Fault Confirmation
Subtask 22-83-00-710-160-A 4. Fault Isolation
Subtask 22-83-00-865-092-A
[Rev.8 from Aug 2018]
2026.04.04 04:25:33 UTC
Loss of the FCU Information on the FMGC 1
1. Possible Causes
- FMGC 1
A. Referenced Information
| REFERENCE | DESIGNATION |
|---|---|
| AMM 22-96-00-710-001 | Operational Test of the AFS |
| AMM 22-97-00-710-001 | Operational Test of the LAND CAT III Capability |
Subtask 22-83-00-710-160-A 4. Fault Isolation
Subtask 22-83-00-865-092-A
A. Table of the circuit breakers used in this procedure:
Subtask 22-83-00-810-145-A | PANEL | DESIGNATION | FIN | LOCATION |
|---|---|---|---|
| ** ON A/C ALL | |||
| 49VU | AUTO FLT/FCU/1 | 9CA1 | B05 |
| 49VU | AUTO FLT/FMGC/1 | 10CA1 | B02 |
| 121VU | AUTO FLT/FCU/2 | 9CA2 | M21 |
B. If the test gives the maintenance message AFS : CHK FMGC1 (FCU INPUT):
Subtask 22-83-00-710-161-A - open the circuit breakers 9CA1, 9CA2 and 10CA1
- after 15 s, close these circuit breakers
- do the operational test of the AFS AMM 22-96-00-710-001 and read the result for the FMGC 1 .
- refer to the procedure related to this message.
C. Do the test given in Para. 3.