Loss of the Reception of the DMC 2 VALID Discrete by the FMGC 1


TASK 22-83-00-810-858-A
Loss of the Reception of the DMC 2 VALID Discrete by the FMGC 1


1. Possible Causes
  • FMGC-1 [1CA1]
  • DMC-2 [1WT2]
  • wiring of the PFD OPP VALID discrete (from the FMGC 1 (1CA1) to the DMC 2 (1WT2))
2. Job Set-up Information
 A. Referenced Information
REFERENCE
DESIGNATION
AMM 22-83-34-000-001
Removal of the FMGC
AMM 22-83-34-400-001
Installation of the FMGC
ASM 228504
AMM 22-91-00-710-001
Ground Scanning of the AFS
AMM 31-63-34-000-001
Removal of the DMC
AMM 31-63-34-400-001
Installation of the DMC
3. Fault Confirmation
Subtask 22-83-00-865-085-A
A. Make sure that this(these) circuit breaker(s) is(are) closed:
PANELDESIGNATIONFINLOCATION
** ON A/C ALL
121VUEIS/DMC2/SPLY10WT2Q08
121VUEIS/DMC2/SWTG21WT2R08
Subtask 22-83-00-710-148-A
B. Test
   (1) Do the Ground Scanning of the AFS AMM 22-91-00-710-001.
4. Fault Isolation
Subtask 22-83-00-810-139-A
A. If the test gives the maintenance message AFS: CHK DMC2-FMGC1 CKT:
   (1) If the fault continues:
   (2) If the fault continues:
  • do a check and repair the wiring of the PFD OPP VALID discrete (from the FMGC 1 (1CA1) to the DMC 2 (1WT2)) ASM 228504.
Subtask 22-83-00-710-149-A
B. Do the test given in Para. 3.