Loss of the Reception of the FWC 1 VALID Discrete by the FMGC 2
TASK 22-83-00-810-852-A
Loss of the Reception of the FWC 1 VALID Discrete by the FMGC 2
1. Possible Causes
A. Referenced Information
3. Fault Confirmation
Subtask 22-83-00-865-079-A
Subtask 22-83-00-810-133-A
[Rev.8 from Aug 2018]
2026.04.04 04:25:32 UTC
Loss of the Reception of the FWC 1 VALID Discrete by the FMGC 2
1. Possible Causes
- FMGC-2 [1CA2]
wiring of the FWC OPP VALID discrete (from the FMGC 2 (1CA2) to the first terminal block)
A. Referenced Information
| REFERENCE | DESIGNATION |
|---|---|
| AMM 22-83-34-000-001 | Removal of the FMGC |
| AMM 22-83-34-400-001 | Installation of the FMGC |
| ASM 228504 | |
| AMM 22-91-00-710-001 | Ground Scanning of the AFS |
Subtask 22-83-00-865-079-A
A. Make sure that this(these) circuit breaker(s) is(are) closed:
Subtask 22-83-00-710-136-A 4. Fault Isolation| PANEL | DESIGNATION | FIN | LOCATION |
|---|---|---|---|
| ** ON A/C ALL | |||
| 49VU | FWS/FWC1/SPLY | 3WW | F01 |
Subtask 22-83-00-810-133-A
A. If the test gives the maintenance message AFS: CHK FWC1-FMGC2 CKT:
Subtask 22-83-00-710-137-A - replace the FMGC-2 [1CA2] AMM 22-83-34-000-001 and AMM 22-83-34-400-001.
- do a check and repair the
wiring of the FWC OPP VALID discrete (from the FMGC 2 (1CA2) to the first terminal block) ASM 228504.
B. Do the test given in Para. 3.