Loss of the MCDU 1 FAIL Discrete
TASK 22-82-00-810-809-A
Loss of the MCDU 1 FAIL Discrete
1. Possible Causes
A. Referenced Information
3. Fault Confirmation
Subtask 22-82-00-710-066-A
Subtask 22-82-00-810-062-A
[Rev.8 from Aug 2018]
2026.04.04 04:25:27 UTC
Loss of the MCDU 1 FAIL Discrete
1. Possible Causes
- FMGC-1 [1CA1]
wiring of the MCDU OWN FAIL discrete from the FMGC 1 (1CA1) to the first terminal block - FMGC-2 [1CA2]
wiring of the MCDU OPP FAIL discrete from the FMGC 2 (1CA2) to the first terminal block - MCDU-1 [3CA1]
wiring of the MCDU FAIL discrete from the MCDU 1 (3CA1) to the first terminal block
A. Referenced Information
| REFERENCE | DESIGNATION |
|---|---|
| AMM 22-82-12-000-001 | Removal of the MCDU |
| AMM 22-82-12-400-002 | Installation of the MCDU |
| AMM 22-83-34-000-001 | Removal of the FMGC |
| AMM 22-83-34-400-001 | Installation of the FMGC |
| ASM 228504 | |
| AMM 22-96-00-710-001 | Operational Test of the AFS |
Subtask 22-82-00-710-066-A
A. Test
(1) Do the operational test of the AFS AMM 22-96-00-710-001, read the result for the FMGC 1 and the FMGC 2 and do one of these three fault isolation steps (A., B. or C.).
4. Fault Isolation(1) Do the operational test of the AFS AMM 22-96-00-710-001, read the result for the FMGC 1 and the FMGC 2 and do one of these three fault isolation steps (A., B. or C.).
Subtask 22-82-00-810-062-A
A. If the test only gives the maintenance message AFS : MCDU1 (FW DISC)/FMGC1:
Subtask 22-82-00-810-063-A - replace the FMGC-1 [1CA1] AMM 22-83-34-000-001 and AMM 22-83-34-400-001.
- do a check and repair the
wiring of the MCDU OWN FAIL discrete from the FMGC 1 (1CA1) to the first terminal block ASM 228504.
B. If the test only gives the maintenance message AFS : MCDU 1 (FW DISC)/FMGC2:
Subtask 22-82-00-810-064-A - replace the FMGC-2 [1CA2] AMM 22-83-34-000-001 and AMM 22-83-34-400-001.
- do a check and repair the
wiring of the MCDU OPP FAIL discrete from the FMGC 2 (1CA2) to the first terminal block ASM 228504.
C. If the test gives the two maintenance messages AFS : MCDU1 (FW DISC)/ FMGC1 and AFS : MCDU1 (FW DISC)/FMGC2:
Subtask 22-82-00-710-067-A - replace the MCDU-1 [3CA1] AMM 22-82-12-000-001 and AMM 22-82-12-400-002.
- do a check and repair the
wiring of the MCDU FAIL discrete from the MCDU 1 (3CA1) to the first terminal block ASM 228504.
D. Do the test given in Para. 3.