Loss of the SFCC 2 Data


TASK 22-66-00-810-882-A
Loss of the SFCC 2 Data


1. Possible Causes
  • SLAT/FLAP CONTR.COMP. [22CV]
2. Job Set-up Information
 A. Referenced Information
REFERENCE
DESIGNATION
AMM 22-97-00-710-001
Operational Test of the LAND CAT III Capability
AMM 27-51-34-000-001
Removal of the SFCC
AMM 27-51-34-400-001
Installation of the SFCC
3. Fault Confirmation
Subtask 22-66-00-865-085-A
A. Make sure that this(these) circuit breaker(s) is(are) closed:
PANELDESIGNATIONFINLOCATION
** ON A/C ALL
105VUELEC/HOT BUS/702PP SPLY5PB2D02
105VUELEC/HOT BUS/702PP SPLY12PB2E02
121VUFLIGHT CONTROLS/FLP/CTL AND/MONG/SYS28CVQ21
121VUFLIGHT CONTROLS/SLT/CTL/SYS27CVR21
Subtask 22-66-00-710-202-A
B. Test
   (1) Do the operational test of the LAND CAT III capability AMM 22-97-00-710-001.
4. Fault Isolation
Subtask 22-66-00-810-158-A
A. If the test gives the maintenance message AFS: CHK FMGC2-FAC 1/2 WRG:
  • open the circuit breakers 7CV, 8CV, 5PB2, 12PB2
  • after 15 s, close these circuit breakers
  • do the operational test of the LAND CAT III capability AMM 22-97-00-710-001.
   (1) If the fault continues:
Subtask 22-66-00-710-203-A
B. Do the test given in Para. 3.
[Rev.8 from Aug 2018] 2026.04.04 04:25:22 UTC