Loss of the Reception of the ENG STP Discretes by the FAC 2
TASK 22-66-00-810-864-A
Loss of the Reception of the ENG STP Discretes by the FAC 2
1. Possible Causes
A. Referenced Information
3. Fault Confirmation
Subtask 22-66-00-710-172-A
Subtask 22-66-00-810-133-A
[Rev.8 from Aug 2018]
2026.04.04 04:25:21 UTC
Loss of the Reception of the ENG STP Discretes by the FAC 2
1. Possible Causes
- FAC-2 [1CC2]
wiring of the ENG OWN STP and ENG OPP STP discretes (from the FAC 2 (1CC2) to the diode modules (1800VD and 1801VD) - wiring of the diode module 1800VD
- wiring of the diode module 1801VD
DIODE MODULE (1800VD) DIODE MODULE (1801VD)
A. Referenced Information
| REFERENCE | DESIGNATION |
|---|---|
| AMM 22-66-34-000-002 | Removal of the FAC |
| AMM 22-66-34-400-002 | Installation of the FAC |
| ASM 226801 | |
| AMM 22-96-00-710-001 | Operational Test of the AFS |
Subtask 22-66-00-710-172-A
A. Test
(1) Do the operational test of the AFS AMM 22-96-00-710-001 and read the result for the FAC 2.
4. Fault Isolation(1) Do the operational test of the AFS AMM 22-96-00-710-001 and read the result for the FAC 2.
Subtask 22-66-00-810-133-A
A. If the test gives the message LRU TEST NOT COMPLETED:
Subtask 22-66-00-710-173-A - replace the FAC-2 [1CC2] AMM 22-66-34-000-002 and AMM 22-66-34-400-002.
- do a check of the
wiring of the ENG OWN STP and ENG OPP STP discretes (from the FAC 2 (1CC2) to the diode modules (1800VD and 1801VD) ASM 226801.
- repair the above wiring.
- do a check of the wiring of the diode module 1800VD from pin A/2 to the first terminal block
- do a check of the wiring of the diode module 1801VD from pin A/7 to the first terminal block
ASM 226801.
- repair the above wiring.
- replace the
DIODE MODULE (1800VD) .
- replace the
DIODE MODULE (1801VD) .
B. Do the test given in Para. 3.