Loss of the Reception of the ELAC 2 Discretes by One FAC or One FMGC


TASK 22-66-00-810-851-A
Loss of the Reception of the ELAC 2 Discretes by One FAC or One FMGC


1. Possible Causes
  • FAC-1 [1CC1]
  • wiring of the ELAC OPP HLTY COM discrete from the FAC 1 (1CC1) to the first terminal block
  • FAC-2 [1CC2]
  • wiring of the ELAC OWN HLTY MON discrete from the FAC 2 (1CC2) to the first terminal block
  • FMGC-1 [1CA1]
  • ELAC-2 [2CE2]
  • wiring of the ELAC OPP AP DISC MON and ELAC OPP AP DISC COM discretes from the FMGC 1 (1CA1) to the ELAC 2 (2CE2)
  • FMGC-2 [1CA2]
  • wiring of the ELAC OWN AP DISC MON and ELAC OWN AP DISC COM discretes from the FMGC 2 (1CA2) to the ELAC 2 (2CE2)
2. Job Set-up Information
 A. Referenced Information
REFERENCE
DESIGNATION
AMM 22-66-34-000-002
Removal of the FAC
AMM 22-66-34-400-002
Installation of the FAC
ASM 226801
AMM 22-83-34-000-001
Removal of the FMGC
AMM 22-83-34-400-001
Installation of the FMGC
ASM 228504
AMM 22-96-00-710-001
Operational Test of the AFS
AMM 27-93-34-000-001
Removal of the ELAC
AMM 27-93-34-400-001
Installation of the ELAC
3. Fault Confirmation
Subtask 22-66-00-865-068-A
A. Make sure that this(these) circuit breaker(s) is(are) closed:
PANELDESIGNATIONFINLOCATION
** ON A/C ALL
49VUFLIGHT CONTROLS/ELAC1/NORM/SPLY15CE1B11
121VUFLIGHT CONTROLS/ELAC2/NORM/SPLY15CE2R20
Subtask 22-66-00-710-150-A
B. Test
   (1) Do the test of the AFS AMM 22-96-00-710-001.
NOTE: When the APU is under MMEL, the AFS: ELAC2 message can possibly come into view before the second engine starts.
If the failure message comes into view, it will go out of view when the two engines run (but the failure message will be recorded in the PFR).
If the APU is under MMEL and if the test of the AFS is correct, no maintenance action is necessary.
4. Fault Isolation
Subtask 22-66-00-810-110-A
A. If the test gives the maintenance message AFS: ELAC2 (ISSUED BY: FAC1):
   (1) If the fault continues:
  • do a check and repair the wiring of the ELAC OPP HLTY COM discrete from the FAC 1 (1CC1) to the first terminal block ASM 226801.
Subtask 22-66-00-810-111-A
B. If the test gives the maintenance message AFS: ELAC2 (ISSUED BY: FAC2):
   (1) If the fault continues:
  • do a check and repair the wiring of the ELAC OWN HLTY MON discrete from the FAC 2 (1CC2) to the first terminal block ASM 226801.
Subtask 22-66-00-810-112-A
C. If the test gives the maintenance message AFS: ELAC2 (ISSUED BY: FG1):
   (1) If the fault continues:
   (2) If the fault continues:
  • do a check and repair the wiring of the ELAC OPP AP DISC MON and ELAC OPP AP DISC COM discretes from the FMGC 1 (1CA1) to the ELAC 2 (2CE2) ASM 228504.
Subtask 22-66-00-810-113-A
D. If the test gives the maintenance message AFS: ELAC2 (ISSUED BY: FG2):
   (1) If the fault continues:
   (2) If the fault continues:
  • do a check and repair the wiring of the ELAC OWN AP DISC MON and ELAC OWN AP DISC COM discretes from the FMGC 2 (1CA2) to the ELAC 2 (2CE2) ASM 228504.
Subtask 22-66-00-710-151-A
E. Do the test given in Para. 3.