Loss of the Reception of the ELAC 1 Discretes by One FAC or One FMGC


TASK 22-66-00-810-850-A
Loss of the Reception of the ELAC 1 Discretes by One FAC or One FMGC


1. Possible Causes
  • FAC-1 [1CC1]
  • wiring of the ELAC OWN HLTY MON discrete from the FAC 1 (1CC1) to the first terminal block
  • FAC-2 [1CC2]
  • wiring of the ELAC OPP HLTY COM discrete from the FAC 2 (1CC2) to the first terminal block
  • FMGC-1 [1CA1]
  • ELAC-1 [2CE1]
  • wiring of the ELAC OWN AP DISC MON and ELAC OWN AP DISC COM discretes from the FMGC 1 (1CA1) to the ELAC 1 (2CE1)
  • FMGC-2 [1CA2]
  • wiring of the ELAC OPP AP DISC MON and ELAC OPP AP DISC COM discretes from the FMGC 2 (1CA2) to the ELAC 1 (2CE1)
2. Job Set-up Information
 A. Referenced Information
REFERENCE
DESIGNATION
AMM 22-66-34-000-002
Removal of the FAC
AMM 22-66-34-400-002
Installation of the FAC
ASM 226801
AMM 22-83-34-000-001
Removal of the FMGC
AMM 22-83-34-400-001
Installation of the FMGC
ASM 228504
AMM 22-96-00-710-001
Operational Test of the AFS
AMM 27-93-34-000-001
Removal of the ELAC
AMM 27-93-34-400-001
Installation of the ELAC
3. Fault Confirmation
Subtask 22-66-00-865-067-A
A. Make sure that this(these) circuit breaker(s) is(are) closed:
PANELDESIGNATIONFINLOCATION
** ON A/C ALL
49VUFLIGHT CONTROLS/ELAC1/NORM/SPLY15CE1B11
121VUFLIGHT CONTROLS/ELAC2/NORM/SPLY15CE2R20
Subtask 22-66-00-710-148-A
B. Test
   (1) Do the test of the AFS AMM 22-96-00-710-001.
4. Fault Isolation
Subtask 22-66-00-810-106-A
A. If the test gives the maintenance message AFS: ELAC1 (ISSUED BY: FAC1):
   (1) If the fault continues:
  • do a check and repair the wiring of the ELAC OWN HLTY MON discrete from the FAC 1 (1CC1) to the first terminal block ASM 226801.
Subtask 22-66-00-810-107-A
B. If the test gives the maintenance message AFS: ELAC1 (ISSUED BY: FAC2):
   (1) If the fault continues:
  • do a check and repair the wiring of the ELAC OPP HLTY COM discrete from the FAC 2 (1CC2) to the first terminal block ASM 226801.
Subtask 22-66-00-810-108-A
C. If the test gives the maintenance message AFS: ELAC1 (ISSUED BY: FG1):
   (1) If the fault continues:
   (2) If the fault continues:
  • do a check and repair the wiring of the ELAC OWN AP DISC MON and ELAC OWN AP DISC COM discretes from the FMGC 1 (1CA1) to the ELAC 1 (2CE1) ASM 228504.
Subtask 22-66-00-810-109-A
D. If the test gives the maintenance message AFS: ELAC1 (ISSUED BY: FG2):
   (1) If the fault continues:
   (2) If the fault continues:
  • do a check and repair the wiring of the ELAC OPP AP DISC MON and ELAC OPP AP DISC COM discretes from the FMGC 2 (1CA2) to the ELAC 1 (2CE1) ASM 228504.
Subtask 22-66-00-710-149-A
E. Do the test given in Para. 3.
[Rev.8 from Aug 2018] 2026.04.04 04:25:19 UTC