Loss of the Power Supply 26VAC of the Yaw Damper Side 1
TASK 22-63-00-810-807-A
Loss of the Power Supply 26VAC of the Yaw Damper Side 1
1. Possible Causes
A. Referenced Information
3. Fault Confirmation
Subtask 22-63-00-710-064-A 4. Fault Isolation
Subtask 22-63-00-810-058-A
[Rev.8 from Aug 2018]
2026.04.04 04:25:14 UTC
Loss of the Power Supply 26VAC of the Yaw Damper Side 1
1. Possible Causes
- SERVO ACTR-YAW DAMPER, 1 [3CC1]
wiring of the 26VAC signal at yaw-damper servo-actuator (3CC1) wiring of the ground signal at yaw-damper servo-actuator (3CC1)
A. Referenced Information
| REFERENCE | DESIGNATION |
|---|---|
| ASM 226701 | |
| AMM 22-91-00-710-001 | Ground Scanning of the AFS |
| AMM 27-26-51-000-001 | Removal of the Yaw Damper Servo Actuator |
| AMM 27-26-51-400-001 | Installation of the Yaw Damper Servo Actuator |
Subtask 22-63-00-710-064-A 4. Fault Isolation
Subtask 22-63-00-810-058-A
A. If the test gives the maintenance message AFS : 431 XPA BUS BAR:
Subtask 22-63-00-710-065-A - replace the SERVO ACTR-YAW DAMPER, 1 [3CC1] , AMM 27-26-51-000-001 and AMM 27-26-51-400-001.
- do a check of the
wiring of the 26VAC signal at yaw-damper servo-actuator (3CC1) from pin A/A to the first terminal block ASM 226701.
- repair the above wiring.
- do a check and repair the
wiring of the ground signal at yaw-damper servo-actuator (3CC1) pin A/L ASM 226701.
B. Do the test given in Para. 3.