Loss of the AP2 OPP Discretes
TASK 22-11-00-810-813-A
Loss of the AP2 OPP Discretes
1. Possible Causes
A. Referenced Information
3. Fault Confirmation
Subtask 22-11-00-710-062-A
Subtask 22-11-00-810-062-A
[Rev.8 from Aug 2018]
2026.04.04 04:25:07 UTC
Loss of the AP2 OPP Discretes
1. Possible Causes
- FMGC-2 [1CA2]
- FMGC-1 [1CA1]
- FWC-1 [1WW1]
- ELAC-1 [2CE1]
- FAC-1 [1CC1]
wiring of the AP OWN ENGD MON OPP discrete (from the FMGC 2 (1CA2) pin AD/14D to the first terminal block) wiring of the AP OWN ENGD COM OPP discrete (from the FMGC 2 (1CA2) pin AA/14B to the first terminal block)
A. Referenced Information
| REFERENCE | DESIGNATION |
|---|---|
| TSM TASK 31-32-00-810-932-A | Failure of the Discrete Links |
| AMM 22-66-34-000-002 | Removal of the FAC |
| AMM 22-66-34-400-002 | Installation of the FAC |
| AMM 22-83-34-000-001 | Removal of the FMGC |
| AMM 22-83-34-400-001 | Installation of the FMGC |
| ASM 228503 | |
| AMM 22-96-00-710-001 | Operational Test of the AFS |
| AMM 27-93-34-000-001 | Removal of the ELAC |
| AMM 27-93-34-400-001 | Installation of the ELAC |
| AMM 31-53-34-000-001 | Removal of the Flight Warning Computer (FWC) |
| AMM 31-53-34-400-001 | Installation of the Flight Warning Computer (FWC) |
Subtask 22-11-00-710-062-A
A. Test
(1) Do the operational test of the AFS AMM 22-96-00-710-001 and read the results for the FMGC 2 and the FAC 1.
(2) On the FCU, push the AP2 pushbutton switch.
(3) Do the operational test of the AFS AMM 22-96-00-710-001 again and read the results for the FMGC 2 and the FAC 1.
4. Fault Isolation(1) Do the operational test of the AFS AMM 22-96-00-710-001 and read the results for the FMGC 2 and the FAC 1.
(2) On the FCU, push the AP2 pushbutton switch.
(3) Do the operational test of the AFS AMM 22-96-00-710-001 again and read the results for the FMGC 2 and the FAC 1.
Subtask 22-11-00-810-062-A
A. If one of the tests gives the maintenance messages:
AFS: FMGC2/AP ENGD FDBK and
AFS: FAC1/AP2 ENGD WIRING
Subtask 22-11-00-710-063-A AFS: FMGC2/AP ENGD FDBK and
AFS: FAC1/AP2 ENGD WIRING
- Replace the FMGC-2 [1CA2] AMM 22-83-34-000-001 and AMM 22-83-34-400-001.
- Do the troubleshooting procedure (Ref. TSM TASK 31-32-00-810-932):
. Related to the AP OWN ENGD MON OPP discrete
. Related to the AP OWN ENGD COM OPP discrete ASM 228503.
If you do not find fault during the troubleshooting procedure (Ref. TSM TASK 31-32-00-810-932), go to Para. (e).
- Replace the FMGC-1 [1CA1] AMM 22-83-34-000-001 and AMM 22-83-34-400-001.
- Replace the FWC-1 [1WW1] AMM 31-53-34-000-001 and AMM 31-53-34-400-001.
- Replace the ELAC-1 [2CE1] AMM 27-93-34-000-001 and AMM 27-93-34-400-001.
- Replace the FAC-1 [1CC1] AMM 22-66-34-000-002 and AMM 22-66-34-400-002.
- Do a check and repair the
wiring of the AP OWN ENGD MON OPP discrete (from the FMGC 2 (1CA2) pin AD/14D to the first terminal block) - Do a check and repair the
wiring of the AP OWN ENGD COM OPP discrete (from the FMGC 2 (1CA2) pin AA/14B to the first terminal block) ASM 228503.
B. Do the test given in Para. 3.