Failure of the FMGC 1


TASK 22-11-00-810-801-A
Failure of the FMGC 1


1. Possible Causes
  • FMGC-1 [1CA1]
  • wiring of the 28VDC and 28VDC GND signals
  • short to ground between the circuit breaker (10CA1) and the A/THR 1 relays (5CA1), (17CA1) and (18CA1)
  • C/B-AUTO FLT/FMGC/1 [10CA1]
2. Job Set-up Information
 A. Referenced Information
REFERENCE
DESIGNATION
ASM 223101
AMM 22-83-34-000-001
Removal of the FMGC
AMM 22-83-34-400-001
Installation of the FMGC
ASM 228401
AMM 22-96-00-710-001
Operational Test of the AFS
3. Fault Confirmation
Subtask 22-11-00-865-068-A
A. Make sure that this(these) circuit breaker(s) is(are) closed:
PANELDESIGNATIONFINLOCATION
** ON A/C ALL
49VUAUTO FLT/FMGC/110CA1B02
Subtask 22-11-00-710-050-A
B. Test
   (1) Do the operational test of the AFS AMM 22-96-00-710-001 and read the result for the FMGC 1.
     (a) If the circuit breaker (10CA1) is open, refer to Para. 4.B.
4. Fault Isolation
Subtask 22-11-00-810-050-A
A. If the circuit breaker (10CA1) is closed and if the test gives the maintenance message AFS : FMGC1:
   (1) If the check is correct:
Subtask 22-11-00-810-076-A
B. If the circuit breaker (10CA1) is open:
  • close this circuit breaker.
   (1) If the circuit breaker (10CA1) trips:
     (a) If the fault continues:
  • do a check for a short to ground between the circuit breaker (10CA1) and the FMGC 1 (1CA1) ASM 228401
  • do a check for a short to ground between the circuit breaker (10CA1) and the A/THR 1 relays (5CA1), (17CA1) and (18CA1) ASM 223101.
       1 If there is a short to ground:
  • repair the above wirings.
       2 If there is no short to ground:
  • replace the C/B-AUTO FLT/FMGC/1 [10CA1] .
Subtask 22-11-00-710-051-A
C. Do the test given in Para. 3.