ECS receives no Data from CIDS


TASK 21-63-00-810-858-A
ECS receives no Data from CIDS


1. Possible Causes
  • ZONE CONTROLLER [8HK]
2. Job Set-up Information
 A. Referenced Information
REFERENCE
DESIGNATION
AMM 21-63-00-710-004
Operational Test of the Cockpit and Cabin Temperature Control with CFDS/MCDU
ASM 216301
AMM 21-63-34-000-001
Removal of the Zone Controller
AMM 21-63-34-400-001
Installation of the Zone Controller
AMM 23-73-00-740-003
BITE-Test of the Cabin Intercommunication Data System (CIDS) through the PTP
3. Fault Confirmation
Subtask 21-63-00-710-147-A ** ON A/C NOT FOR ALL
A. Do the operational test of the cockpit and cabin temperature-control system with CFDS/MCDU AMM 21-63-00-710-004.
4. Fault Isolation
Subtask 21-63-00-810-153-A ** ON A/C NOT FOR ALL
A. If the test gives the maintenance message NO DATA FROM CIDS:
   (1) If the test gives a different maintenance message, do the related trouble shooting procedure.
   (2) If the fault continues:
     (a) Do a check and repair if necessary the connector pin at the connector 8HK/BA for the CIDS option.
  • If CIDS option is installed pin BA3 to ground.
  • If CIDS option is not installed pin BA3 is not used and should show OPEN CONTACT.
   (3) If the fault continues:
     (a) Do a check and repair the ARINC 429 wiring as necessary of the signal INPUT CIDS from: ASM 216301
  • the CIDS Director (101RH) connector AA/6A to the Zone Controller (8HK) connector AA/3A.
  • the CIDS Director (101RH) connector AA/6B to the Zone Controller (8HK) connector AA/B3.
   (4) If the fault continues:
Subtask 21-63-00-710-148-A ** ON A/C NOT FOR ALL
B. Do the test given in Para. 3.
5. Close-up
Subtask 21-63-00-860-082-A ** ON A/C NOT FOR ALL
A. Put the aircraft back to its initial configuration.