Cockpit Temperature uncontrollable or too low with TAV AMBER XX
TASK 21-63-00-810-855-A
Cockpit Temperature uncontrollable or too low with TAV AMBER XX
1. Possible Causes
A. Referenced Information
3. Fault Confirmation
Subtask 21-63-00-710-145-A ** ON A/C NOT FOR ALL
Subtask 21-63-00-810-152-A ** ON A/C NOT FOR ALL
[Rev.8 from Aug 2018]
2026.04.04 04:25:05 UTC
Cockpit Temperature uncontrollable or too low with TAV AMBER XX
1. Possible Causes
- TRIM VALVE CKPT [11HK]
- wiring
A. Referenced Information
| REFERENCE | DESIGNATION |
|---|---|
| AMM 21-63-00-710-004 | Operational Test of the Cockpit and Cabin Temperature Control with CFDS/MCDU |
| ASM 216302 | |
| ASM 216303 | |
| AMM 21-63-51-000-001 | Removal of the Trim Air Valve |
| AMM 21-63-51-400-001 | Installation of the Trim Air Valve |
Subtask 21-63-00-710-145-A ** ON A/C NOT FOR ALL
A. Confirmation of the Fault
(1) Do the operational test of the cockpit and cabin temperature-control system AMM 21-63-00-710-004.
4. Fault Isolation(1) Do the operational test of the cockpit and cabin temperature-control system AMM 21-63-00-710-004.
Subtask 21-63-00-810-152-A ** ON A/C NOT FOR ALL
A. If on the ECAM COND page the CKPT trim air valve position indication shows amber XX and/or the Cockpit temperature is uncontrollable or too low (in flight):
(a) This wiring check is only applicable for Trim Air Valves previous to P/N 1320A0000-01 or 963B0000-01 or 750B0000-01.
Subtask 21-63-00-810-152-B ** ON A/C NOT FOR ALL - replace the TRIM VALVE CKPT [11HK] AMM 21-63-51-000-001 and AMM 21-63-51-400-001.
(a) This wiring check is only applicable for Trim Air Valves previous to P/N 1320A0000-01 or 963B0000-01 or 750B0000-01.
- do a check and repair the wiring ASM 216302 from:
- the TRIM VALVE CKPT (11HK) to the Zone Controller (8HK) and,
- the TRIM VALVE CKPT (11HK) to ground.
- do a check and repair the wiring ASM 216302 between:
- TRIM VALVE CKPT (11HK) connector A/U and ZC (8HK) connector AB/13A,
- TRIM VALVE CKPT (11HK) connector A/J and ZC (8HK) connector AB/12B,
- TRIM VALVE CKPT (11HK) connector A/K and ZC (8HK) connector AB/13B,
- TRIM VALVE CKPT (11HK) connector A/L and ZC (8HK) connector AB/14B,
- TRIM VALVE CKPT (11HK) connector A/C and ZC (8HK) connector AB/7C,
- TRIM VALVE CKPT (11HK) connector A/E and ZC (8HK) connector AB/7B,
- the TRIM VALVE CKPT (11HK) to ground.
A. If on the ECAM COND page the CKPT trim air valve position indication shows amber XX and/or the Cockpit temperature is uncontrollable or too low (in flight):
Subtask 21-63-00-710-146-A ** ON A/C NOT FOR ALL - replace the TRIM VALVE CKPT [11HK] AMM 21-63-51-000-001 and AMM 21-63-51-400-001.
- do a check and repair the wiring ASM 216303 from:
- the TRIM AIR VALVE CKPT (11HK) to the ACSC1 (47HH) and,
- the TRIM AIR VALVE CKPT (11HK) to ground.
B. Do the test given in Para. 3.