W DOC AIRBUS | TSM A320F

ZC receives no Data from the CFDS


TASK 21-63-00-810-829-A
ZC receives no Data from the CFDS


1. Possible Causes
  • ZONE CONTROLLER [8HK]
  • wiring
2. Job Set-up Information
 A. Referenced Information
REFERENCE
DESIGNATION
AMM 21-63-00-710-004
Operational Test of the Cockpit and Cabin Temperature Control with CFDS/MCDU
ASM 216302
AMM 21-63-34-000-001
Removal of the Zone Controller
AMM 21-63-34-400-001
Installation of the Zone Controller
AMM 31-32-00-740-002
BITE Test of the Centralized Fault Display Interface Unit (CFDIU)
ASM 313205
3. Fault Confirmation
Subtask 21-63-00-710-107-A ** ON A/C NOT FOR ALL
A. Do the operational test of the cockpit and cabin temperature-control system with CFDS/MCDU AMM 21-63-00-710-004.
NOTE: Make sure that the circuit breakers 2TW and 8TW are closed during the test.
NOTE: If a fault is detected, the ZC gives a fault code for shop maintenance in addition to the related CFDS message(s). For detailed information see the applicable Page Block 301.
4. Fault Isolation
Subtask 21-63-00-810-112-A ** ON A/C NOT FOR ALL
A. If the test gives the maintenance message NO DATA FROM CFDS:
   (1) If the test gives a different maintenance message, do the related trouble shooting procedure.
   (2) If the fault continues:
   (3) If the fault continues:
  • do a check and repair the wiring of the signal ARINC 429 OUT (BUS 4) from the CFDIU (1TW) to the ZC (8HK) ASM 216302 and ASM 313205.
Subtask 21-63-00-710-108-A ** ON A/C NOT FOR ALL
B. Do the test given in Para. 3.
5. Close-up
Subtask 21-63-00-860-078-A ** ON A/C NOT FOR ALL
A. Put the aircraft back to its initial configuration.
[Rev.8 from Aug 2018] 2026.04.04 04:25:03 UTC