W DOC AIRBUS | TSM A320F

ACSC receives no Data from the CFDS


TASK 21-61-00-810-918-A
ACSC receives no Data from the CFDS


1. Possible Causes
  • CONT-AIR COND SYSTEM 2 [57HH]
  • wiring
2. Job Set-up Information
 A. Referenced Information
REFERENCE
DESIGNATION
ASM 216101
AMM 21-61-34-000-002
Removal of the Air-Conditioning System Controller
AMM 21-61-34-400-002
Installation of the Air-Conditioning System Controller
AMM 21-63-00-710-004
Operational Test of the Cockpit and Cabin Temperature Control with CFDS/MCDU
AMM 31-32-00-740-002
BITE Test of the Centralized Fault Display Interface Unit (CFDIU)
ASM 313205
3. Fault Confirmation
Subtask 21-61-00-710-210-A ** ON A/C NOT FOR ALL
A. Do the operational test of the cockpit and cabin temperature-control system with CFDS/MCDU AMM 21-63-00-710-004.
NOTE: Make sure that the circuit breakers 2TW and 8TW are closed during the test.
4. Fault Isolation
Subtask 21-61-00-810-256-A ** ON A/C NOT FOR ALL
A. If the test gives the maintenance message CFDIU(1TW):
   (1) If the test gives a different maintenance message, do the related trouble shooting procedure.
   (2) If the fault continues:
   (3) If the fault continues:
  • do a check and repair the wiring of the signal ARINC 429 OUT (BUS 4) from the CFDIU (1TW) to the ACSC2 (57HH) ASM 216101 and ASM 313205.
Subtask 21-61-00-710-211-A ** ON A/C NOT FOR ALL
B. Do the test given in Para. 3.
5. Close-up
Subtask 21-61-00-860-096-A ** ON A/C NOT FOR ALL
A. Put the aircraft back to its initial configuration.
[Rev.8 from Aug 2018] 2026.04.04 04:24:59 UTC