MCDU - NO TEST Indications
TASK 21-61-00-810-888-A
MCDU - NO TEST Indications
1. Possible Causes
2. Fault Confirmation
Subtask 21-61-00-710-182-A ** ON A/C NOT FOR ALL
Subtask 21-61-00-810-230-A ** ON A/C NOT FOR ALL
[Rev.8 from Aug 2018]
2026.04.04 04:24:58 UTC
MCDU - NO TEST Indications
1. Possible Causes
2. Fault Confirmation
Subtask 21-61-00-710-182-A ** ON A/C NOT FOR ALL
A. Unable to complete temperature control test (MCDU).
3. Fault IsolationSubtask 21-61-00-810-230-A ** ON A/C NOT FOR ALL
A. If the temperature control test shows the MCDU indications NO TEST: PACK 1 NOT OFF and PACK 2 NOT OFF:
(1) Where applicable disconnect or shut down the Engine, APU and/or HP bleed air supplies.
(3) Wait for a minimum of 5 seconds.
(4) Close the circuit breakers 49HH, 50HH, 51HH, 52HH, 53HH, 54HH, 55HH and 56HH.
(5) With the bleed air supply still disconnected or shut down restart the related temperature control test.
(1) Where applicable disconnect or shut down the Engine, APU and/or HP bleed air supplies.
NOTE: Presence of bleed air pressure could lead to test performance failure.
(2) Open the circuit breakers 49HH, 50HH, 51HH, 52HH, 53HH, 54HH, 55HH and 56HH. (3) Wait for a minimum of 5 seconds.
(4) Close the circuit breakers 49HH, 50HH, 51HH, 52HH, 53HH, 54HH, 55HH and 56HH.
(5) With the bleed air supply still disconnected or shut down restart the related temperature control test.