ACSC1 / Pack 1 Bypass Valve Fault


TASK 21-61-00-810-868-A
ACSC1 / Pack 1 Bypass Valve Fault


1. Possible Causes
  • CONT-AIR COND SYSTEM 1 [47HH]
  • VALVE-TURBINE BYPASS [10HH]
  • wiring
2. Job Set-up Information
 A. Referenced Information
REFERENCE
DESIGNATION
AMM 21-61-00-710-001
Operational Test of the Pack Temperature-Control System
ASM 216101
AMM 21-61-34-000-002
Removal of the Air-Conditioning System Controller
AMM 21-61-34-400-002
Installation of the Air-Conditioning System Controller
AMM 21-61-53-000-001
Removal of the Turbine Bypass Valve
AMM 21-61-53-400-001
Installation of the Turbine Bypass Valve
3. Fault Confirmation
Subtask 21-61-00-710-157-A ** ON A/C NOT FOR ALL
A. Do the operational test of the pack temperature-control system AMM 21-61-00-710-001.
4. Fault Isolation
Subtask 21-61-00-810-205-A ** ON A/C NOT FOR ALL
A. If the test gives the maintenance message ACSC1(47HH)/P1 BY PASS VALVE(10HH):
   (1) If the fault moves with the ACSC1:
  • swap back the ACSC2 (57HH) and replace the CONT-AIR COND SYSTEM 1 [47HH] (ACSC1 47HH).
   (2) If the fault does not move with the ACSC1:
   (3) If the fault continues:
  • do a check and repair the wiring ASM 216101 from:
  • the VALVE (10HH) to the ACSC1 (47HH) and,
  • the VALVE (10HH) to ground.
Subtask 21-61-00-720-057-A ** ON A/C NOT FOR ALL
B. Put the aircraft back to its initial configuration.