Pack 1 Anti Ice Valve Fault
TASK 21-61-00-810-818-A
Pack 1 Anti Ice Valve Fault
1. Possible Causes
2. Job Set-up Information
A. Referenced Information
3. Fault Confirmation
Subtask 21-61-00-710-084-A ** ON A/C NOT FOR ALL
Subtask 21-61-00-810-104-A ** ON A/C NOT FOR ALL
Subtask 21-61-00-860-067-A ** ON A/C NOT FOR ALL
[Rev.8 from Aug 2018]
2026.04.04 04:24:53 UTC
Pack 1 Anti Ice Valve Fault
1. Possible Causes
2. Job Set-up Information
A. Referenced Information
| REFERENCE | DESIGNATION |
|---|---|
| AMM 21-61-00-710-001 | Operational Test of the Pack Temperature-Control System |
| ASM 216104 | |
| AMM 21-61-34-000-001 | Removal of the Pack Controller |
| AMM 21-61-34-000-002 | Removal of the Air-Conditioning System Controller |
| AMM 21-61-34-400-001 | Installation of the Pack Controller |
| AMM 21-61-34-400-002 | Installation of the Air-Conditioning System Controller |
| AMM 21-61-41-000-001 | Removal of the Anti-Ice Valve |
| AMM 21-61-41-000-003 | Removal of the Solenoid Valve |
| AMM 21-61-41-400-001 | Installation of the Anti-Ice Valve |
| AMM 21-61-41-400-003 | Installation of the Solenoid Valve |
Subtask 21-61-00-710-084-A ** ON A/C NOT FOR ALL
A. Do the operational test of the pack temperature-control system AMM 21-61-00-710-001.
4. Fault IsolationNOTE: If a fault is detected, the PC gives a fault code for shop maintenance in addition to the related CFDS message(s) (refer to TSM chapter 21-63-00, page block 301).
Subtask 21-61-00-810-104-A ** ON A/C NOT FOR ALL
A. If the test gives the maintenance message P1 CONT OR ANTI ICE VALVE:
Subtask 21-61-00-810-104-B ** ON A/C NOT FOR ALL - swap the PC 1 (7HH) and the PC 2 (27HH) AMM 21-61-34-000-001 and AMM 21-61-34-400-001.
- swap back the PC 1 (7HH) and the PC 2 (27HH) AMM 21-61-34-000-001 and AMM 21-61-34-400-001.
- replace the P1 CONTROLLER [7HH] AMM 21-61-34-000-001 and AMM 21-61-34-400-001.
- swap back the PC 1 (7HH) and the PC 2 (27HH) AMM 21-61-34-000-001 and AMM 21-61-34-400-001.
- replace the VALVE-ANTI ICE [17HH] AMM 21-61-41-000-001 and AMM 21-61-41-400-001.
- do a check and repair the wiring ASM 216104 from:
- the VALVE (17HH)A pin A and the PC 1 (7HH)AB pin 8A and,
- the VALVE (17HH)A pins B and C to ground.
A. If the test gives the maintenance message P1 ANTI ICE VALVE(17HH):
Subtask 21-61-00-810-104-D ** ON A/C NOT FOR ALL - swap the ACSC1 (47HH) and the ACSC2 (57HH) AMM 21-61-34-000-002 and AMM 21-61-34-400-002.
- swap back the ACSC1 (47HH) and the ACSC2 (57HH).
- replace the
[47HH] AMM 21-61-34-000-002 and AMM 21-61-34-400-002.
- swap back the ACSC1 (47HH) and the ACSC2 (57HH) AMM 21-61-34-000-002 and AMM 21-61-34-400-002.
- replace the VALVE-ANTI ICE [17HH] AMM 21-61-41-000-001 and AMM 21-61-41-400-001.
- do a check and repair the wiring ASM 216104 from:
- the VALVE (17HH) to the ACSC1 (47HH) and,
- the VALVE (17HH) to ground.
A. If the test gives the maintenance message P1 CONT OR ANTI ICE VALVE:
Subtask 21-61-00-710-085-A ** ON A/C NOT FOR ALL - swap the PC 1 (7HH) and the PC 2 (27HH) AMM 21-61-34-000-001 and AMM 21-61-34-400-001.
- swap back the PC 1 (7HH) and the PC 2 (27HH) AMM 21-61-34-000-001 and AMM 21-61-34-400-001.
- replace the P1 CONTROLLER [7HH] AMM 21-61-34-000-001 and AMM 21-61-34-400-001.
- swap back the PC 1 (7HH) and the PC 2 (27HH) AMM 21-61-34-000-001 and AMM 21-61-34-400-001.
- replace the VALVE-ANTI ICE [17HH] AMM 21-61-41-000-001 and AMM 21-61-41-400-001.
- do a check and repair the wiring ASM 216104 from:
- the VALVE (17HH)A pin A and the PC 1 (7HH)AB pin 8A and,
- the VALVE (17HH)A pins B and C to ground.
- replace the
SOLENOID VALVE (25HH) AMM 21-61-41-000-003 and AMM 21-61-41-400-003.
- do a check and repair the wiring ASM 216104 from:
- the SOLENOID VALVE (25HH)A pin A and the PC 1 (7HH)AB pin 8A and,
- the SOLENOID VALVE (25HH)A pins B and C to ground.
B. Do the test as given in the Para. 3.A.
5. Close-upSubtask 21-61-00-860-067-A ** ON A/C NOT FOR ALL
A. Put the aircraft back to its initial configuration.