No data from AIR COND Controller Fault


TASK 21-58-00-810-820-A
No data from AIR COND Controller Fault


1. Possible Causes
  • CSAS CONTROL UNIT [100HW]
  • wiring
2. Job Set-up Information
 A. Referenced Information
REFERENCE
DESIGNATION
ASM 215301
AMM 21-58-00-710-001
Operational Test of the Conditioned Service Air System without Bleed Air
AMM 21-58-34-000-001
Removal of the CSAS Control Unit
AMM 21-58-34-400-001
Installation of the CSAS Control Unit
AMM 21-63-00-710-004
Operational Test of the Cockpit and Cabin Temperature Control with CFDS/MCDU
ASM 216303
3. Fault Confirmation
Subtask 21-58-00-710-088-A ** ON A/C NOT FOR ALL
A. Do the operational test of the conditioned service air system without bleed air AMM 21-58-00-710-001.
NOTE: Make sure that the circuit breakers 49HH, 50HH, 51HH and 52HH are closed during the test.
Subtask 21-58-00-710-088-C ** ON A/C NOT FOR ALL
A. Do the operational test of the conditioned service air system without bleed air AMM 21-58-00-710-001.
NOTE: Make sure that the circuit breakers 1HK, 2HK, 3HK and 4HK are closed during the test.
4. Fault Isolation
Subtask 21-58-00-810-081-A ** ON A/C NOT FOR ALL
A. If the test gives the maintenance message NO DATA FROM AIR COND CTL:
  • do the operational test of the cockpit and cabin temperature-control system with CFDS/MCDU AMM 21-63-00-710-004.
   (1) If the test gives a different maintenance message, do the related trouble shooting procedure.
   (2) If the fault continues:
   (3) If the fault continues:
  • do a check and repair the wiring of the signal ARINC 429 XTR EXT from the ACSC1 (47HH) to the CSAS CONTROL UNIT (100HW) ASM 216303 and ASM 215301.
Subtask 21-58-00-810-081-C ** ON A/C NOT FOR ALL
A. If the test gives the maintenance message NO DATA FROM AIR COND CTL:
  • do the operational test of the cockpit and cabin temperature-control system with CFDS/MCDU AMM 21-63-00-710-004.
   (1) If the test gives a different maintenance message, do the related trouble shooting procedure.
   (2) If the fault continues:
   (3) If the fault continues:
  • do a check and repair the wiring of the signal ARINC 429 XTR EXT from the ZC (8HK) to the CSAS CONTROL UNIT (100HW) ASM 216303 and ASM 215301.
Subtask 21-58-00-710-089-A ** ON A/C NOT FOR ALL
B. Do the test as given in the Para. 3.A.