System Latched by Analog Circuit of CCU


TASK 21-58-00-810-819-A
System Latched by Analog Circuit of CCU


1. Possible Causes
  • CSAS CONTROL UNIT [100HW]
  • SENSOR-TEMP DUCT,CSAS [115HW]
  • wiring
2. Job Set-up Information
 A. Referenced Information
REFERENCE
DESIGNATION
ASM 215301
AMM 21-58-00-710-001
Operational Test of the Conditioned Service Air System without Bleed Air
AMM 21-58-11-000-001
Removal of the Duct Temperature Sensor
AMM 21-58-11-400-001
Installation of the Duct Temperature Sensor
AMM 21-58-34-000-001
Removal of the CSAS Control Unit
AMM 21-58-34-400-001
Installation of the CSAS Control Unit
3. Fault Confirmation
Subtask 21-58-00-710-086-A ** ON A/C NOT FOR ALL
A. Test
   (1) Do the reset procedure for the CSAS and the IGGS as follows,
  • open the circuit breakers 1HW and 7YA.
  • wait for a minimum of 5 seconds.
  • close the circuit breakers 1HW and 7YA.
   (2) Do the operational test of the conditioned service air system without bleed air AMM 21-58-00-710-001.
4. Fault Isolation
Subtask 21-58-00-810-068-A ** ON A/C NOT FOR ALL
A. If the test gives a different maintenance message, do the related trouble shooting procedure.
Subtask 21-58-00-810-070-A ** ON A/C NOT FOR ALL
B. If the test gives the maintenance message SYS LATCHED BY ANALOG CIRCUIT OF CCU:
   (1) Do the reset procedure for the CSAS and the IGGS as follows,
  • open the circuit breakers 1HW and 7YA.
  • wait for a minimum of 5 seconds.
  • close the circuit breakers 1HW and 7YA.
   (2) If the fault continues:
   (3) If the fault continues:
   (4) If the fault continues:
  • do a check and repair the wiring from:
    the CSAS TEMPERATURE SENSOR (115HW) to the CSAS CONTROL UNIT (100HW) and,
    the CSAS TEMPERATURE SENSOR (115HW) to ground ASM 215301.
Subtask 21-58-00-710-087-A ** ON A/C NOT FOR ALL
C. Do the test as given in the Para. 3.A.