Critical Overtemperature Fault
TASK 21-58-00-810-815-A
Critical Overtemperature Fault
1. Possible Causes
2. Job Set-up Information
A. Referenced Information
3. Fault Confirmation
Subtask 21-58-00-710-078-B ** ON A/C NOT FOR ALL
Subtask 21-58-00-810-075-A ** ON A/C NOT FOR ALL
[Rev.8 from Aug 2018]
2026.04.04 04:24:50 UTC
Critical Overtemperature Fault
1. Possible Causes
2. Job Set-up Information
A. Referenced Information
| REFERENCE | DESIGNATION |
|---|---|
| AMM 21-58-00-100-001 | Remove CSAS Heat Exchanger for Cleaning |
| AMM 21-58-00-710-002 | Operational Test of the Conditioned Service Air System with Bleed Air |
| AMM 21-58-11-000-001 | Removal of the Duct Temperature Sensor |
| AMM 21-58-11-400-001 | Installation of the Duct Temperature Sensor |
| AMM 47-41-11-000-001 | Removal of the Temperature Sensor |
| AMM 47-41-11-400-001 | Installation of the Temperature Sensor |
Subtask 21-58-00-710-078-B ** ON A/C NOT FOR ALL
A. Test.
(1) Do the reset procedure for the CSAS and the IGGS as follows,
(3) Do a read out of the post flight report.
4. Fault Isolation(1) Do the reset procedure for the CSAS and the IGGS as follows,
- open the circuit breakers 1HW and 7YA.
- wait for a minimum of 5 seconds.
- close the circuit breakers 1HW and 7YA.
(3) Do a read out of the post flight report.
Subtask 21-58-00-810-075-A ** ON A/C NOT FOR ALL
A. If the test gives a different maintenance message, do the related trouble shooting procedure.
Subtask 21-58-00-810-064-A ** ON A/C NOT FOR ALL B. If the test gives the maintenance message CRITICAL OVTEMP:
1 clean the Heat Exchanger (5103HM) AMM 21-58-00-100-001.
Subtask 21-58-00-810-101-A ** ON A/C NOT FOR ALL - do a check for leakages downstream of the CSAS Heat Exchanger (5103HM) during the test.
- remove the leakage by replacement of the faulty component if necessary.
- do a check of the CSAS Heat Exchanger and the Ram Air Channel for contamination.
1 clean the Heat Exchanger (5103HM) AMM 21-58-00-100-001.
C. If no leakage and no contamination is found and the post flight report gives the maintenance message CRITICAL OVTEMP:
(a) if the trouble shooting data gives the fault code 1041 1101 or 1041 1102: refer to paragraph D.
(b) if the trouble shooting data gives the fault code 1041 1103 or 1041 1104 or 1041 1105: refer to paragraph E.
Subtask 21-58-00-810-102-A ** ON A/C NOT FOR ALL - do a read out of the TROUBLE SHOOTING DATA (TSD) of the fault message:
(a) if the trouble shooting data gives the fault code 1041 1101 or 1041 1102: refer to paragraph D.
(b) if the trouble shooting data gives the fault code 1041 1103 or 1041 1104 or 1041 1105: refer to paragraph E.
D. If the trouble shooting data gives the fault code 1041 1101 or 1041 1102:
Subtask 21-58-00-810-103-A ** ON A/C NOT FOR ALL - replace the SENSOR-TEMP DUCT,CSAS [115HW] AMM 21-58-11-000-001 and AMM 21-58-11-400-001.
E. If the trouble shooting data gives the fault code 1041 1103 or 1041 1104 or 1041 1105:
Subtask 21-58-00-710-079-A ** ON A/C NOT FOR ALL - replace the SENSOR-BLEED AIR TEMP, IGGS [2YA] AMM 47-41-11-000-001 and AMM 47-41-11-400-001.
F. Do the test as given in the Para. 3.