Aft Trim Air Pressure Regulating Valve (TAPRV) Control Circuit Fault


TASK 21-43-00-810-820-A
Aft Trim Air Pressure Regulating Valve (TAPRV) Control Circuit Fault


1. Possible Causes
  • RELAY-TAPRV CLOSE (17HC)
  • PUSHBUTTON SWITCH-CARGO HEAT/HOT AIR (16HC)
  • wiring
2. Job Set-up Information
 A. Referenced Information
REFERENCE
DESIGNATION
ASM 214302
AMM 21-61-00-710-001
Operational Test of the Pack Temperature-Control System
3. Fault Confirmation
Subtask 21-43-00-710-086-A ** ON A/C NOT FOR ALL
A. Do the operational test of the pack temperature-control system AMM 21-61-00-710-001.
NOTE: The ZC (8HK) also monitors the cargo compartment heating system.
Subtask 21-43-00-710-086-D ** ON A/C NOT FOR ALL
A. Do the operational test of the pack temperature-control system AMM 21-61-00-710-001.
4. Fault Isolation
Subtask 21-43-00-810-078-A
A. If the test gives the maintenance message AFT TAPRV SHUT OFF RELAY:
  • do a check for the RELAY-TAPRV CLOSE (17HC) and replace it if necessary ASM 214302.
   (1) If the fault continues:
  • do a check for the PUSHBUTTON SWITCH-CARGO HEAT/HOT AIR (16HC) and replace it if necessary ASM 214302.
   (2) If the fault continues:
  • do a check and repair the wiring between:
    the ACHC (10HC) AA/6A and CB (31HN) ASM 214302.
Subtask 21-43-00-710-087-A
B. Do the test given in Para. 3.
5. Close-up
Subtask 21-43-00-860-067-A
A. Put the aircraft back to its initial configuration.
[Rev.8 from Aug 2018] 2026.04.04 04:24:46 UTC