AFT Cargo-Compartment Trim-Air Pressure Regulating Fault


TASK 21-43-00-810-812-A
AFT Cargo-Compartment Trim-Air Pressure Regulating Fault


1. Possible Causes
  • AFT CARGO PRESS REG VALVE [11HC]
2. Job Set-up Information
 A. Referenced Information
REFERENCE
DESIGNATION
AMM 21-43-00-710-003
Operational Test of the AFT Cargo Compartment Heating System
AMM 21-43-52-000-001
Removal of the Pressure Regulating Valve - Aft Cargo-Compartment Heating
AMM 21-43-52-400-001
Installation of the Pressure Regulating Valve - Aft Cargo-Compartment Heating
3. Fault Confirmation
Subtask 21-43-00-720-050-A
A. Do the operational test of the AFT cargo-compartment Ventilation system AMM 21-43-00-710-003.
NOTE: During this test, monitor the position of the trim-air pressure-regulating valve (11HC) on the ECAM.
4. Fault Isolation
Subtask 21-43-00-810-062-A
A. If the temperature in the AFT cargo compartment is lower than the selected temperature and the AFT cargo-compartment pressure-regulating valve-symbol on ECAM is closed (green):
Subtask 21-43-00-710-073-A
B. Do the test as given in the Para. 3.A.
5. Close-up
Subtask 21-43-00-860-061-A
A. Put the aircraft back to its initial configuration.