Warning of the Avionics-Ventilation Comfort Duct-Temperature-Sensor Inoperative


TASK 21-26-00-810-846-A
Warning of the Avionics-Ventilation Comfort Duct-Temperature-Sensor Inoperative


1. Possible Causes
  • SENSOR-DUCT TEMP, AVNCS VENT COMFORT [34HQ]
  • wiring between the AEVC (10HQ) and the comfort duct temperature-sensor (34HQ),
  • AEVC [10HQ]
2. Job Set-up Information
 A. Referenced Information
REFERENCE
DESIGNATION
AMM 21-26-00-710-001
Operational Check of the Avionics Equipment Ventilation-System via MCDU
AMM 21-26-00-710-008
Operational Test to Read the CFDS for CLASS 3 Faults of the AEVC
AMM 21-26-00-710-009
Operational Test to Read the CFDS for LAST LEG REPORT of the AEVC
ASM 212603
AMM 21-26-12-000-802
Removal of the Avionics-Ventilation Comfort Duct-Temperature-Sensor
AMM 21-26-12-400-802
Installation of the Avionics-Ventilation Comfort Duct-Temperature-Sensor
AMM 21-26-34-000-001
Removal of the Avionics Equipment Ventilation Computer (AEVC)
AMM 21-26-34-400-001
Installation of the Avionics Equipment Ventilation Computer (AEVC)
3. Fault Confirmation
Subtask 21-26-00-710-129-A ** ON A/C NOT FOR ALL
A. Test
   (1) Do a reset of the AEVC (10HQ).
     (a) Open circuit breaker AIR COND/AVNCS/VENT/MONG (3HQ).
     (b) Wait for five seconds.
     (c) Close circuit breaker AIR COND/AVNCS/VENT/MONG (3HQ).
   (2) Do the operational test of the avionics equipment ventilation from the Multipurpose Control and Display Unit (MCDU) AMM 21-26-00-710-001.
   (3) Read the LAST LEG REPORT of the AEVC AMM 21-26-00-710-009.
   (4) Read the CLASS 3 faults of the AEVC AMM 21-26-00-710-008.
4. Fault Isolation
Subtask 21-26-00-810-100-A ** ON A/C NOT FOR ALL
A. If the test gives the maintenance message AV COMF SENSOR 34HQ:
   (1) If the fault continues:
  • Do a check of the wiring between the AEVC (10HQ) and the comfort duct temperature-sensor (34HQ), ASM 212603.
    . Pin AB/11B and pin A/C
     (a) If the wiring is not correct:
  • Repair the related wiring.
     (b) If the wiring is correct:
Subtask 21-26-00-710-130-A ** ON A/C NOT FOR ALL
B. Do the operational test given in Para. 3.