W DOC AIRBUS | TSM A320F

Loss of the Information from the LGCIUs


TASK 21-26-00-810-821-A
Loss of the Information from the LGCIUs


1. Possible Causes
2. Job Set-up Information
 A. Referenced Information
REFERENCE
DESIGNATION
TSM TASK 32-31-00-810-802-A
LGCIU Fault
AMM 21-26-00-710-001
Operational Check of the Avionics Equipment Ventilation-System via MCDU
AMM 21-26-00-710-008
Operational Test to Read the CFDS for CLASS 3 Faults of the AEVC
AMM 21-26-00-710-009
Operational Test to Read the CFDS for LAST LEG REPORT of the AEVC
ASM 212602
AMM 21-26-34-000-001
Removal of the Avionics Equipment Ventilation Computer (AEVC)
AMM 21-26-34-400-001
Installation of the Avionics Equipment Ventilation Computer (AEVC)
AMM 24-42-00-861-001
Energize the Ground Service Network from the External Power
3. Fault Confirmation
Subtask 21-26-00-865-065-A
A. Table of the circuit breakers used in this procedure:
PANELDESIGNATIONFINLOCATION
** ON A/C ALL
122VUAIR COND/AVNCS/VENT/MONG3HQY17
Subtask 21-26-00-710-068-A
B. Test
   (1) Do a reset of the Avionics Equipment Ventilation Computer (AEVC) (10HQ).
     (a) Open the circuit breaker AIR COND/AVNCS/VENT/MONG (3HQ).
     (b) Wait for ten seconds.
     (c) Close the circuit breaker AIR COND/AVNCS/VENT/MONG (3HQ).
   (2) Do the operational test of the avionics equipment ventilation from the Multipurpose Control and Display Unit (MCDU) AMM 21-26-00-710-001.
   (3) Read the LAST LEG REPORT of the AEVC AMM 21-26-00-710-009.
   (4) Read the CLASS 3 faults of the AEVC AMM 21-26-00-710-008.
4. Fault Isolation
Subtask 21-26-00-860-051-A
A. Aircraft Maintenance Configuration
   (1) Release the EXTRACT pushbutton switch (the Override (OVRD) legend comes on).
   (2) Wait for 60 seconds.
   (3) Remove the AEVC AMM 21-26-34-000-001.
   (4) Install BREAKOUT BOX on the position of 10HQ (AEVC).
   (5) Energize the ground service network
AMM 24-42-00-861-001.
   (6) If, after the disconnection of the AEVC, the ground scanning give the maintenance message : VENT AVNCS SYS FAULT
  • Ignore this message
   (7) In case the air conditioning system is not operating, the ground crew call might be activated after 30 seconds.
Subtask 21-26-00-810-059-A
B. If the test gives the maintenance message CHECK LGCIU - AEVC INTFC:
  • Do a check for a ground signal at pin AB/9C and pin AB/10C of the AEVC (10HQ) ASM 212602.
   (1) If there is a ground signal:
   (2) If there is no ground signal:
  • Do a check of the wiring ASM 212602 between:
    . Pin AB/9C of the AEVC (10HQ) and pin AB/1D of the LGCIU-1 (5GA1)
    . Pin AB/10C of the AEVC (10HQ) and pin AB/1D of the LGCIU-2 (5GA2).
     (a) If the wiring is not correct:
  • Repair the related wiring.
     (b) If the wiring is correct:
Subtask 21-26-00-710-069-A
C. Do the operational test given in Para. 3.