Blower Fan Inoperative because of a Failure of the AEVC


TASK 21-26-00-810-813-A
Blower Fan Inoperative because of a Failure of the AEVC


1. Possible Causes
2. Job Set-up Information
 A. Referenced Information
REFERENCE
DESIGNATION
AMM 21-26-00-710-001
Operational Check of the Avionics Equipment Ventilation-System via MCDU
AMM 21-26-00-710-008
Operational Test to Read the CFDS for CLASS 3 Faults of the AEVC
AMM 21-26-00-710-009
Operational Test to Read the CFDS for LAST LEG REPORT of the AEVC
ASM 212603
AMM 21-26-34-000-001
Removal of the Avionics Equipment Ventilation Computer (AEVC)
AMM 21-26-34-400-001
Installation of the Avionics Equipment Ventilation Computer (AEVC)
AMM 31-50-00-710-001
Ground Scanning of the Central Warning System
3. Fault Confirmation
Subtask 21-26-00-865-056-A
A. Table of the circuit breakers used in this procedure:
PANELDESIGNATIONFINLOCATION
** ON A/C ALL
49VUFWS/FWC1/SPLY3WWF01
121VUEIS/FWC2/SPLY2WWQ07
122VUAIR COND/AVNCS/VENT/MONG3HQY17
Subtask 21-26-00-710-077-A
B. Test
   (1) Do the reset of the AEVC (10HQ).
     (a) Open the circuit breaker AIR COND/AVNCS/VENT/MONG (3HQ).
     (b) Wait for five seconds.
     (c) Close the circuit breaker AIR COND/AVNCS/VENT/MONG (3HQ).
   (2) Do the operational test of the avionics equipment ventilation from the Multipurpose Control and Display Unit (MCDU) AMM 21-26-00-710-001.
   (3) Read the LAST LEG REPORT of the AEVC AMM 21-26-00-710-009.
   (4) Read the CLASS 3 faults of the AEVC AMM 21-26-00-710-008.
4. Fault Isolation
Subtask 21-26-00-810-064-A
A. If the test gives the maintenance message AEVC:
   (1) If the fault continues:
  • Do a check and repair the wiring ASM 212603 between:
    . Pin 2 of the AIR COND/AVNCS/VENT/MONG circuit breaker (3HQ) and pin A/E of the avionics-ventilation blower fan (20HQ)
    . Pin A/D of the avionics-ventilation blower fan (20HQ) and pin X of the avionics-ventilation blower-fan contactor (8HQ)
    . Pin Z of the avionics-ventilation blower-fan contactor (8HQ) and pin AA/8A of the AEVC (10HQ).
Subtask 21-26-00-710-113-A
B. Test
   (1) Reset of the FWC1 and FWC2
NOTE: The circuit breakers must be open for a minimum of five seconds before you close them.
     (a) Open this(these) circuit breaker(s):
       1 2WW
       2 3WW.
     (b) Close this(these) circuit breaker(s):
       1 2WW
       2 3WW.
   (2) Do the ground scanning of the central warning system AMM 31-50-00-710-001.