Smoke Detection Function (CIDS-SDF)
| 23-73-10-01 | Smoke Detection Function (CIDS-SDF) |
|---|
Applicable to: -
23-73-10-01-A
| Repair interval | Nbr installed | Nbr required | Placard |
|---|---|---|---|
| C 13.04.2026 | 1 | 0 | No |
May be inoperative provided that:
1)
The cargo compartments are empty or do
not contain flammable or combustible materials, and
2)
The lavatory smoke detection system is considered inoperative.
NOTE:
Failure of a single CIDS-SDF channel is indicated by a MAINTENANCE message on the STATUS SD Page.
| 23-73-10-01 | Smoke Detection Function (CIDS-SDF) |
|---|
Applicable to: -
23-73-10-01-B
| Repair interval | Nbr installed | Nbr required | Placard |
|---|---|---|---|
| C 13.04.2026 | 1 | 0 | No |
May be inoperative provided that the restrictions concerning lavatory
smoke detection system and (If Installed) cargo smoke detection systemare applied.
Refer to item 01 Smoke Detector in the FWD Cargo Compartment (if FWD cargo compartment
smoke detection system installed) and
Refer to item 02 Smoke Detector in the AFT and the BULK Cargo Compartments (if AFT cargo compartment smoke detection system
installed).
NOTE:
Failure of a single CIDS-SDF channel is indicated by a MAINTENANCE message on the STATUS SD Page.