Functional Test of the Bleed Transferred Pressure-Transducer with the Bleed Test Set P/N 98L36103002000
TASK 36-11-15-720-001-A-01
Functional Test of the Bleed Transferred Pressure-Transducer with the Bleed Test Set P/N 98L36103002000
Self explanatory
2. Job Set-up Information
A. Fixtures, Tools, Test and Support Equipment
B. Consumable Materials
C. Work Zones and Access Panels
D. Referenced Information
3. Job Set-up
Subtask 36-11-15-861-054-A ** ON A/C NOT FOR ALL Subtask 36-11-15-941-054-A ** ON A/C NOT FOR ALL
Subtask 36-11-15-720-052-A ** ON A/C NOT FOR ALL
Subtask 36-11-15-942-052-C ** ON A/C NOT FOR ALL
[Rev.10 from 2021]
2026.04.01 01:08:19 UTC
Functional Test of the Bleed Transferred Pressure-Transducer with the Bleed Test Set P/N 98L36103002000
WARNING:
BE CAREFUL WHEN YOU USE CONSUMABLE MATERIALS. OBEY THE MATERIAL MANUFACTURER'S INSTRUCTIONS AND YOUR LOCAL REGULATIONS.
1. Reason for the JobSelf explanatory
2. Job Set-up Information
A. Fixtures, Tools, Test and Support Equipment
| REFERENCE | QTY | DESIGNATION |
|---|---|---|
| No specific | AR | ACCESS PLATFORM 5M (16 FT)- ADJUSTABLE |
| No specific | AR | CAP - BLANKING |
| No specific | AR | PLUG - BLANKING |
| No specific | AR | WARNING NOTICE(S) |
| No specific | Torque wrench: range to between 1.7 and 1.5 m.daN (12.54 and 11.06 lbf.ft ) ![]() | |
| 98L36103002000 | 1 | TEST SET - ENGINE BLEED |
| REFERENCE | DESIGNATION |
|---|---|
| (Material No.14QEB1) | Wire-Locking Dia: 0.6 mm CRES Nickel Alloy - |
| ZONE/ACCESS | ZONE DESCRIPTION |
|---|---|
| FOR [7HA1] (XDCR-BLEED TRANSFER PRESS, ENG 1) | |
| 415AL, 415AR | |
| FOR [7HA2] (XDCR-BLEED TRANSFER PRESS, ENG 2) | |
| 425AL, 425AR | |
| REFERENCE | DESIGNATION |
|---|---|
| TASK 24-41-00-861-002-A | Energize the Aircraft Electrical Circuits from the External Power |
| TASK 24-41-00-861-002-A-01 | Energize the Aircraft Electrical Circuits from the APU |
| TASK 24-41-00-861-002-A-02 | Energize the Aircraft Electrical Circuits from Engine 1(2) |
| TASK 24-41-00-862-002-A | De-energize the Aircraft Electrical Circuits Supplied from the External Power |
| TASK 24-41-00-862-002-A-01 | De-energize the Aircraft Electrical Circuits Supplied from the APU |
| TASK 24-41-00-862-002-A-02 | De-energize the Aircraft Electrical Circuits Supplied from the Engine 1(2) |
| TASK 31-60-00-860-001-A | EIS Start Procedure |
| TASK 31-60-00-860-002-A | EIS Stop Procedure |
| TASK 36-11-00-740-001-A | BITE Test of the BMC 1(2) |
Subtask 36-11-15-861-054-A ** ON A/C NOT FOR ALL Subtask 36-11-15-941-054-A ** ON A/C NOT FOR ALL
B. Safety Precautions
(1) Make sure that the engine 1(2) shutdown occurred not less than 5 minutes before you do this procedure.
(2) On the AIR COND panel 30VU:
Subtask 36-11-15-010-058-A ** ON A/C NOT FOR ALL (1) Make sure that the engine 1(2) shutdown occurred not less than 5 minutes before you do this procedure.
(2) On the AIR COND panel 30VU:
- Make sure that the ENG 1(2) BLEED pushbutton switch is released (OFF legend is on).
- Make sure that the APU BLEED pushbutton switch is released (ON legend is off).
- Put a WARNING NOTICE(S) in position to tell persons not to operate the pneumatic system.
- Put a WARNING NOTICE(S) in position to tell the persons not to start the engine 1(2).
- Put a WARNING NOTICE(S) in position to tell persons not to pressurize the pneumatic system.
- Make sure that the ON legend of the ENG/FADEC GND PWR 1(2) pushbutton switch is off.
- Put a WARNING NOTICE(S) in position to tell persons not to energize the FADEC 1(2).
C. Get Access
(1) Put the ACCESS PLATFORM 5M (16 FT)- ADJUSTABLE in position at the pylon access.
(2) Open the access doors:
(a) FOR [7HA1] (XDCR-BLEED TRANSFER PRESS, ENG 1)
415AL 415AR
(b) FOR [7HA2] (XDCR-BLEED TRANSFER PRESS, ENG 2)
425AL 425AR.
Subtask 36-11-15-860-054-C ** ON A/C NOT FOR ALL (1) Put the ACCESS PLATFORM 5M (16 FT)- ADJUSTABLE in position at the pylon access.
(2) Open the access doors:
(a) FOR [7HA1] (XDCR-BLEED TRANSFER PRESS, ENG 1)
415AL 415AR
(b) FOR [7HA2] (XDCR-BLEED TRANSFER PRESS, ENG 2)
425AL 425AR.
D. Aircraft Maintenance Configuration
(1) Disconnect the electrical connector 7HA1-A(7HA2-A) from the bleed transferred pressure-transducer 7HA1(2).
(2) Disconnect the electrical connector 8HA1-A(8HA2-A) from the bleed regulated pressure-transducer 8HA1(2).
(3) Put a CAP - BLANKING on the wiring side of the electrical connector 7HA1-A(7HA2-A).
(4) Use the cable bundle from the 98L36103002000 TEST SET - ENGINE BLEED to connect the electrical connector 8HA1-A(8HA2-A) on the bleed transferred pressure-transducer 7HA1(2).
(5) Disconnection of the sense line
(b) Disconnect the sense line from the bleed transferred pressure-transducer 7HA1(2).
(6) Put the PLUG-BLANKING in each disconnected line end.
(7) Do the EIS start procedure (upper ECAM DU and lower ECAM DU only)
(Ref. AMM TASK 31-60-00-860-001).
4. Procedure(1) Disconnect the electrical connector 7HA1-A(7HA2-A) from the bleed transferred pressure-transducer 7HA1(2).
(2) Disconnect the electrical connector 8HA1-A(8HA2-A) from the bleed regulated pressure-transducer 8HA1(2).
(3) Put a CAP - BLANKING on the wiring side of the electrical connector 7HA1-A(7HA2-A).
(4) Use the cable bundle from the 98L36103002000 TEST SET - ENGINE BLEED to connect the electrical connector 8HA1-A(8HA2-A) on the bleed transferred pressure-transducer 7HA1(2).
(5) Disconnection of the sense line
CAUTION:
USE A SECOND WRENCH TO APPLY COUNTERTORQUE TO THE UNION WHEN YOU DISCONNECT/CONNECT THE PNEUMATIC LINES ON UNIONS.
(a) Remove and discard the lockwire from the sense line. (b) Disconnect the sense line from the bleed transferred pressure-transducer 7HA1(2).
(6) Put the PLUG-BLANKING in each disconnected line end.
(7) Do the EIS start procedure (upper ECAM DU and lower ECAM DU only)
(Ref. AMM TASK 31-60-00-860-001).
Subtask 36-11-15-720-052-A ** ON A/C NOT FOR ALL
A. Functional Test of the Bleed Transferred Pressure-Transducer
(1) Close the shutoff valve, the purge valve and the pressure regulator valve on the 98L36103002000 TEST SET - ENGINE BLEED.
(3) Connection of the test set.
(4) Do a reset of the digital pressure gage.
(5) Make sure that the regulator valve of the test set is closed before pressurize the system.
(6) Do the test that follows:
5. Close-up(1) Close the shutoff valve, the purge valve and the pressure regulator valve on the 98L36103002000 TEST SET - ENGINE BLEED.
WARNING:
MAKE SURE THAT THE PRESSURE SUPPLIED TO BLEED TEST SET 98L36103002000 NEVER EXCEEDS 217 PSI (15 BAR). IF THE PRESSURE SUPPLIED TO THE BLEED TEST SET EXCEEDS THIS VALUE, THERE IS A RISK OF INJURY TO PERSONNEL AND DAMAGE TO EQUIPMENT.
IF THE AIR CYLINDER DOES NOT HAVE A MANOMETER INSTALLED, YOU MUST INSTALL THE PRIMARY REGULATOR VALVE BETWEEN THE AIR BOTTLE AND BLEED TEST SET 98L36103002000. THE PRIMARY REGULATOR VALVE WILL LIMIT THE PRESSURE IN THE BLEED TEST SET TO 217 PSI (15 BAR).
(2) Connect an air cylinder to the 98L36103002000 TEST SET - ENGINE BLEED. (3) Connection of the test set.
CAUTION:
BE CAREFUL WHEN YOU CONNECT/DISCONNECT THE TEST SET TO/FROM THE EQUIPMENT.
THE PRESSURE REGULATING VALVE AND THE PRESSURE GAGE ASSEMBLY OF THE TEST SET ARE HEAVY AND CAN CAUSE DAMAGE TO THE ENGINE.
(a) Connect the 98L36103002000 TEST SET - ENGINE BLEED with the short bend flexible assembly to the union of the bleed transferred pressure-transducer. (4) Do a reset of the digital pressure gage.
(5) Make sure that the regulator valve of the test set is closed before pressurize the system.
(6) Do the test that follows:
| ACTION | RESULT |
|---|---|
1.On the ECAM control panel:
| On the SD:
|
2.Pressurize the test set:
| |
3.On the test set:
| On the test set:
|
| | On the SD:
|
4.On the test set:
| On the test set:
|
Subtask 36-11-15-942-052-C ** ON A/C NOT FOR ALL
A. Put the aircraft back to its initial configuration.
(1) Close the shutoff valve of the air cylinder.
(2) Slowly open the purge valve to depressurize the test set.
(3) Disconnection of the test set.
(5) Remove the PLUG-BLANKING from each disconnected line end.
(6) Connection of the sense line
(b) TORQUE the nut of the sense line to between 1.7 and 1.5 m.daN (12.54 and 11.06 lbf.ft )
.
(c) Safety the sense line with14QEB1 Wire-Locking Dia: 0.6 mm CRES Nickel Alloy - .
(7) Disconnect the cable bundle from the electrical connector 8HA1-A(8HA2-A) and from the bleed transferred pressure-transducer 7HA1(2).
(8) Remove the blanking cap from the electrical connector 7HA1-A(7HA2-A).
(9) Connect the electrical connector 8HA1-A(8HA2-A) to the bleed regulated pressure-transducer 8HA1(2).
(10) Connect the electrical connector 7HA1-A(7HA2-A) to the bleed transferred pressure-transducer 7HA1(2).
(11) Do the EIS stop procedure
(Ref. AMM TASK 31-60-00-860-002).
Subtask 36-11-15-740-051-A ** ON A/C NOT FOR ALL (1) Close the shutoff valve of the air cylinder.
(2) Slowly open the purge valve to depressurize the test set.
(3) Disconnection of the test set.
WARNING:
BEFORE YOU START TO REMOVE THE TOOLING, MAKE SURE THAT THERE IS NO PRESSURIZED GAS LEFT INSIDE THE DUCTS. IT CAN CAUSE AN INJURY TO PERSONNEL AND/OR DAMAGE TO EQUIPMENT.
CAUTION:
BE CAREFUL WHEN YOU CONNECT/DISCONNECT THE TEST SET TO/FROM THE EQUIPMENT.
THE PRESSURE REGULATING VALVE AND THE PRESSURE GAGE ASSEMBLY OF THE TEST SET ARE HEAVY AND CAN CAUSE DAMAGE TO THE ENGINE.
(4) Disconnect the short bend flexible assembly from the union of the bleed transferred pressure-transducer. (5) Remove the PLUG-BLANKING from each disconnected line end.
(6) Connection of the sense line
CAUTION:
USE A SECOND WRENCH TO APPLY COUNTERTORQUE TO THE UNION WHEN YOU DISCONNECT/CONNECT THE PNEUMATIC LINES ON UNIONS.
(a) Connect the sense line to the bleed transferred pressure-transducer 7HA1(2). (b) TORQUE the nut of the sense line to between 1.7 and 1.5 m.daN (12.54 and 11.06 lbf.ft )
. (c) Safety the sense line with
(7) Disconnect the cable bundle from the electrical connector 8HA1-A(8HA2-A) and from the bleed transferred pressure-transducer 7HA1(2).
(8) Remove the blanking cap from the electrical connector 7HA1-A(7HA2-A).
(9) Connect the electrical connector 8HA1-A(8HA2-A) to the bleed regulated pressure-transducer 8HA1(2).
(10) Connect the electrical connector 7HA1-A(7HA2-A) to the bleed transferred pressure-transducer 7HA1(2).
(11) Do the EIS stop procedure
(Ref. AMM TASK 31-60-00-860-002).
B. Do the BITE Test of the BMC 1(2) (Ref. AMM TASK 36-11-00-740-001).
(1) Make sure that the maintenance messages are not shown on the TEST RESULT page:
Subtask 36-11-15-410-057-A ** ON A/C NOT FOR ALL (1) Make sure that the maintenance messages are not shown on the TEST RESULT page:
| --------------------------------------- |
| ! CLASS 3 : 36-11-15 ! |
| ! TRANSF-PRESS XDCR 7HA1(2) ! |
| !-------------------------------------! |
| ! CLASS 2 : 36-11-16 ! |
| ! REG-PRESS XDCR 8HA1(2) ! |
| --------------------------------------- |
C. Close Access
(1) Make sure that the work area is clean and clear of tools and other items.
(2) Close the access doors:
(a) FOR [7HA1] (XDCR-BLEED TRANSFER PRESS, ENG 1)
415AL 415AR
(b) FOR [7HA2] (XDCR-BLEED TRANSFER PRESS, ENG 2)
425AL 425AR.
(3) Remove the access platform(s).
(4) Remove the WARNING NOTICE(S).
Subtask 36-11-15-862-054-A ** ON A/C NOT FOR ALL (1) Make sure that the work area is clean and clear of tools and other items.
(2) Close the access doors:
(a) FOR [7HA1] (XDCR-BLEED TRANSFER PRESS, ENG 1)
415AL 415AR
(b) FOR [7HA2] (XDCR-BLEED TRANSFER PRESS, ENG 2)
425AL 425AR.
(3) Remove the access platform(s).
(4) Remove the WARNING NOTICE(S).
Functional Test of the Bleed Transferred Pressure-Transducer with the Bleed Test Set P/N 98L36103002000