Pressure Test of the Wing-Tank Vent System
TASK 28-12-00-730-801-A
Pressure Test of the Wing-Tank Vent System
Self explanatory
2. Job Set-up Information
A. Fixtures, Tools, Test and Support Equipment
B. Consumable Materials
C. Work Zones and Access Panels
D. Expendable Parts
E. Referenced Information
3. Job Set-up
Subtask 28-12-00-941-063-A
Wing-Tank Vent System - Location and Detail ** ON A/C NOT FOR ALL
Wing-Tank Vent System - Location and Detail ** ON A/C NOT FOR ALL
(1) Use the applicable items from the 98D28004005000 VENT STRINGER LEAK TEST KIT.
(2) Use a SPATULA - NON METALLIC to remove the sealant from:
(a) Remove the nut (7) and the screw (5) from the pipe (4).
(b) Move the bonding lead (6) away from the pipe (4).
(c) Remove the nut (1) and the screw (3) from the pipe (4).
(d) Move the bonding lead (2) away from the pipe (4).
(e) Remove the nuts (13) and the bolts (14) from the fairlead (15).
(f) Remove the fairlead (15) from the bracket (16).
(g) Remove the bolts (17) from the support bracket (18).
(h) Remove the pipe (4) from the connector (8).
(i) Remove and discard the O-ring (9) from the pipe (4).
(j) Install vent inflation-adapter 98D28004007000 to the connector (8).
(k) Put the valve on vent inflation-adapter 98D28004007000 in the closed position.
(4) Install sphincter blank 98D28204004000 to the drain valve (10) at RIB 2 as follows:
(a) Remove the clamp (11) and the check valve (12) 120QM (121QM) (Ref. AMM TASK 28-12-44-000-003).
(b) Install sphincter blank 98D28204004000 to the drain valve (10).
(5) Install test rig air-pressure 98L28004035000 to vent inflation-adapter 98D28004007000 as follows:
(a) Connect fuel test-hose 98D28204003000 to vent inflation-adapter 98D28004007000.
(b) Connect fuel test-hose 98D28204003000 to test rig air-pressure 98L28004035000.
(c) On test rig air-pressure 98L28004035000, make sure that the pressure isolation valve is in the CLOSED position.
(d) Connect the AIR SOURCE 0.3 TO 0.7 BAR (5 TO 10 PSI)- FILTERED, DRY to test rig air-pressure 98L28004035000.
(6) Install vent-stringer duct-blank 98D28004009000 to the vent stringer duct at RIB 22:
(a) Remove the NACA vent intake (Ref. AMM TASK 28-12-47-000-001).
(b) Install vent-stringer duct-blank 98D28004009000 to the vent stringer duct at RIB 22.
(7) Install the float-valve blank 98D28004008000 to the adapter (19) at RIB 15 as follows:
(a) Remove the vent float valve (20) 16QM (17QM) (Ref. AMM TASK 28-12-43-000-002).
(b) Install float valve-blank 98D28004008000 to the adapter (19).
(c) Put the valve on float-valve blank 98D28004008000 in the closed position.
(8) Install sphincter blank 98D28204004000 to the drain valve (23) at RIB 15 as follows:
(a) Remove the clamp (21) and the check valve (22) 52QM (53QM) (Ref. AMM TASK 28-12-44-000-001).
(b) Install sphincter blank 98D28204004000 to the drain valve (23).
Subtask 28-12-00-480-050-C ** ON A/C NOT FOR ALL
(1) Use the applicable items from the 98D28004005000 VENT STRINGER LEAK TEST KIT.
(2) Use a SPATULA - NON METALLIC to remove the sealant from:
(a) Remove the nut (7) and the screw (5) from the pipe (4).
(b) Move the bonding lead (6) away from the pipe (4).
(c) Remove the nut (1) and the screw (3) from the pipe (4).
(d) Move the bonding lead (2) away from the pipe (4).
(e) Remove the nut (13) and the bolts (14) from the fairlead (15).
(f) Remove the fairlead (15) from the bracket (16).
(g) Remove the bolts (17) from the support bracket (18).
(h) Remove the pipe (4) from the connector (8).
(i) Remove and discard the O-ring (9) from the pipe (4).
(j) Install vent inflation-adapter 98D28004007000 to the connector (8).
(k) Put the valve on vent inflation-adapter 98D28004007000 in the closed position.
(4) Install sphincter blank 98D28204004000 to the drain valve (10) at RIB 2 as follows:
(a) Remove the clamp (11) and the check valve (12) 120QM (121QM) (Ref. AMM TASK 28-12-44-000-003).
(b) Install sphincter blank 98D28204004000 to the drain valve (10).
(5) Install test rig air-pressure 98L28004035000 to vent inflation-adapter 98D28004007000:
(a) Connect fuel test-hose 98D28204003000 to vent inflation-adapter 98D28004007000.
(b) Connect fuel test-hose 98D28204003000 to test rig air-pressure 98L28004035000.
(c) On test rig air-pressure 98L28004035000, make sure that the pressure isolation valve is in the CLOSED position.
(d) Connect the AIR SOURCE 0.3 TO 0.7 BAR (5 TO 10 PSI)- FILTERED, DRY to test rig air-pressure 98L28004035000.
(6) Install vent-stringer duct-blank 98D28004009000 to the vent stringer duct at RIB 22 as follows:
(a) Remove the NACA vent intake (Ref. AMM TASK 28-12-47-000-001).
(b) Install vent-stringer duct-blank 98D28004009000 to the vent stringer duct at RIB 22.
4. Procedure
Subtask 28-12-00-730-050-A ** ON A/C NOT FOR ALL
Subtask 28-12-00-080-050-B ** ON A/C NOT FOR ALL
[Rev.10 from 2021]
2026.04.02 07:01:21 UTC
Pressure Test of the Wing-Tank Vent System
WARNING:
BE CAREFUL WHEN YOU USE CONSUMABLE MATERIALS. OBEY THE MATERIAL MANUFACTURER'S INSTRUCTIONS AND YOUR LOCAL REGULATIONS.
WARNING:
PUT THE SAFETY DEVICES AND THE WARNING NOTICES IN POSITION BEFORE YOU START A TASK ON OR NEAR:
- THE FLIGHT CONTROLS
- THE FLIGHT CONTROL SURFACES
- THE LANDING GEAR AND THE RELATED DOORS
- COMPONENTS THAT MOVE.
WARNING:
MAKE SURE THAT YOU HAVE THE CORRECT FIRE FIGHTING EQUIPMENT AVAILABLE.
1. Reason for the JobSelf explanatory
2. Job Set-up Information
A. Fixtures, Tools, Test and Support Equipment
| REFERENCE | QTY | DESIGNATION |
|---|---|---|
| No specific | 1 | ACCESS PLATFORM 5M (16 FT)- ADJUSTABLE |
| No specific | 1 | AIR SOURCE 0.3 TO 0.7 BAR (5 TO 10 PSI)- FILTERED, DRY |
| No specific | AR | SAFETY BARRIER(S) |
| No specific | 1 | SPATULA - NON METALLIC |
| No specific | AR | WARNING NOTICE(S) |
| No specific | AR | WATER - SOAPY SOLUTION |
| No specific | Torque wrench: range to between 0.13 and 0.11 m.daN (11.50 and 9.73 lbf.in ) ![]() | |
| No specific | Torque wrench: range to between 0.16 and 0.14 m.daN (14.16 and 12.39 lbf.in ) ![]() | |
| 98D28004005000 | 1 | VENT STRINGER LEAK TEST KIT |
| 98D57004014000 | 2 | HOOK-COVER (RIB2-SURGE DOORS) |
| REFERENCE | DESIGNATION |
|---|---|
| (Material No.03FAB1) | Mineral Oil base Grease-- Vaseline or Petrolatum - |
| (Material No.06AAB1) | Polysulfide Sealant-General Purpose Fillet - |
| (Material No.14CBB1) | Testing Medium-Leak Detection Bubbles - |
| ZONE/ACCESS | ZONE DESCRIPTION |
|---|---|
| 540 | FUEL TANK |
| 550 | VENT SURGE TANK |
| 640 | FUEL TANK |
| 650 | VENT SURGE TANK |
| 540AB, 540BZ, 640AB, 640BZ | |
| 540JB, 640JB |
| FIG.ITEM | DESIGNATION | IPC-CSN |
|---|---|---|
| 9 | ORING | AIPC 28-12-05-30-180 |
| 9 | O-RING | AIPC 28-12-85-22-180 |
| REFERENCE | DESIGNATION |
|---|---|
| TASK 12-11-28-650-003-A | Pressure Refuel with Automatic Control |
| TASK 12-11-28-650-004-A | Pressure Refuel with Manual Control |
| TASK 20-21-11-911-001-A | Tightening Torques for Standard Threaded Fasteners |
| TASK 20-28-00-869-002-A | Table of the Maximum Permitted Resistance-Values |
| TASK 20-28-00-912-802-A | Electrical Bonding - General Maintenance Procedure |
| TASK 28-10-00-910-001-A | Safety Procedures When You Do Work in a Fuel Tank |
| TASK 28-10-00-910-002-A | Access to the Fuel Tanks and the Work Areas |
| TASK 28-12-43-000-002-A | Removal of the Vent Float-Valve |
| TASK 28-12-43-400-002-A | Installation of the Vent Float-Valve |
| TASK 28-12-44-000-001-A | Removal of the Check Valve |
| TASK 28-12-44-000-003-A | Removal of the Check Valve |
| TASK 28-12-44-400-001-A | Installation of the Check Valve |
| TASK 28-12-44-400-003-A | Installation of the Check Valve |
| TASK 28-12-47-000-001-A | Removal of the NACA Vent Intake |
| TASK 28-12-47-400-001-A | Installation of the NACA Vent Intake |
| TASK 28-25-00-650-001-A | Pressure Defuel |
| TASK 28-25-00-650-003-A | To Drain Remaining Fuel from the Wing Tanks and the Center Tank |
| TASK 28-25-00-650-003-A-01 | To Drain Remaining Fuel from the Wing Tanks and the Center Tank |
| TASK 57-27-11-000-001-A | Removal of the Access Panel |
| TASK 57-27-11-000-002-A | Removal of the Access Panel |
| TASK 57-27-11-400-001-A | Installation of the Access Panel |
| TASK 57-27-11-400-002-A | Installation of the Access Panel |
| TASK 57-27-12-000-002-A | Removal of the Rib 2 Access Panel 540AZ(640AZ) or 540BZ(640BZ) |
| TASK 57-27-12-400-002-A | Installation of the Rib 2 Access Panel 540AZ (640AZ) or 540BZ (640BZ) |
Subtask 28-12-00-941-063-A
A. Safety Precautions
(2) As necessary, use the applicable SAFETY BARRIERS, specified by the operator's instructions and your local regulations.
(3) In the cockpit (zone 210), put the WARNING NOTICE(S) in position:
Subtask 28-12-00-860-067-A WARNING:
BEFORE YOU DO WORK IN OR NEAR A FUEL TANK, MAKE SURE THAT YOU OBEY ALL THE SAFETY PROCEDURES. THIS WILL PREVENT INJURY TO PERSONS AND/OR DAMAGE TO THE AIRCRAFT.
(1) You must obey the safety procedures when you do work in a fuel tank (Ref. AMM TASK 28-10-00-910-001). (2) As necessary, use the applicable SAFETY BARRIERS, specified by the operator's instructions and your local regulations.
(3) In the cockpit (zone 210), put the WARNING NOTICE(S) in position:
- On the overhead panel, on fuel control-panel 40VU, to tell persons not to operate the fuel system.
- On the flight controls, to tell persons not to operate the flight controls.
B. Aircraft Maintenance Configuration
(1) Defuel the applicable fuel tanks (Ref. AMM TASK 28-25-00-650-001).
(2) Drain the remaining fuel from the applicable fuel tanks (Ref. AMM TASK 28-25-00-650-003).
Subtask 28-12-00-010-065-A ** ON A/C NOT FOR ALL (1) Defuel the applicable fuel tanks (Ref. AMM TASK 28-25-00-650-001).
(2) Drain the remaining fuel from the applicable fuel tanks (Ref. AMM TASK 28-25-00-650-003).
C. Get Access
(1) Put the ACCESS PLATFORM 5M (16 FT)- ADJUSTABLE in position below the applicable underwing tank access-panel(s):
(a) For the left wing:
(b) For the right wing:
(2) Remove the applicable underwing tank access-panel(s) (Ref. AMM TASK 28-10-00-910-002), (Ref. AMM TASK 57-27-11-000-001) and (Ref. AMM TASK 57-27-11-000-002).
(a) For the left wing:
(b) For the right wing:
(3) Open the applicable aft fuel-surge door(s) (Ref. AMM TASK 28-10-00-910-002):
(a) For the left wing:
(b) For the right wing:
(4) Install the 98D57004014000 HOOK-COVER (RIB2-SURGE DOORS) to hold the fuel-surge door(s) open.
Subtask 28-12-00-010-065-B ** ON A/C NOT FOR ALL (1) Put the ACCESS PLATFORM 5M (16 FT)- ADJUSTABLE in position below the applicable underwing tank access-panel(s):
(a) For the left wing:
(b) For the right wing:
(2) Remove the applicable underwing tank access-panel(s) (Ref. AMM TASK 28-10-00-910-002), (Ref. AMM TASK 57-27-11-000-001) and (Ref. AMM TASK 57-27-11-000-002).
(a) For the left wing:
(b) For the right wing:
(3) Open the applicable aft fuel-surge door(s) (Ref. AMM TASK 28-10-00-910-002):
(a) For the left wing:
(b) For the right wing:
(4) Install the 98D57004014000 HOOK-COVER (RIB2-SURGE DOORS) to hold the fuel-surge door(s) open.
C. Get Access
(1) Put the ACCESS PLATFORM 5M (16 FT)- ADJUSTABLE in position below the applicable underwing tank access-panel(s):
(a) For the left wing:
(b) For the right wing:
(2) Remove the applicable underwing tank access-panel(s) (Ref. AMM TASK 28-10-00-910-002) and (Ref. AMM TASK 57-27-11-000-001):
(a) For the left wing:
(b) For the right wing:
(3) Open the applicable aft fuel-surge door(s) (Ref. AMM TASK 28-10-00-910-002):
(a) For the left wing:
(b) For the right wing:
(4) Install the 98D57004014000 HOOK-COVER (RIB2-SURGE DOORS) to hold the fuel-surge door(s) open.
Subtask 28-12-00-010-065-C ** ON A/C NOT FOR ALL (1) Put the ACCESS PLATFORM 5M (16 FT)- ADJUSTABLE in position below the applicable underwing tank access-panel(s):
(a) For the left wing:
(b) For the right wing:
(2) Remove the applicable underwing tank access-panel(s) (Ref. AMM TASK 28-10-00-910-002) and (Ref. AMM TASK 57-27-11-000-001):
(a) For the left wing:
(b) For the right wing:
(3) Open the applicable aft fuel-surge door(s) (Ref. AMM TASK 28-10-00-910-002):
(a) For the left wing:
(b) For the right wing:
(4) Install the 98D57004014000 HOOK-COVER (RIB2-SURGE DOORS) to hold the fuel-surge door(s) open.
C. Get Access
(1) Put the ACCESS PLATFORM 5M (16 FT)- ADJUSTABLE in position below the applicable underwing tank access panels:
(a) For the left wing:
(b) For the right wing:
(2) Remove the applicable underwing tank access panels (Ref. AMM TASK 28-10-00-910-002):
(a) For the left wing:
(a) For the left wing:
Subtask 28-12-00-010-065-D ** ON A/C NOT FOR ALL (1) Put the ACCESS PLATFORM 5M (16 FT)- ADJUSTABLE in position below the applicable underwing tank access panels:
(a) For the left wing:
(b) For the right wing:
(2) Remove the applicable underwing tank access panels (Ref. AMM TASK 28-10-00-910-002):
(a) For the left wing:
- Remove 540AB and 540JB (Ref. AMM TASK 57-27-11-000-001) and (Ref. AMM TASK 57-27-11-000-002).
- Remove 640AB and 640JB (Ref. AMM TASK 57-27-11-000-001) and (Ref. AMM TASK 57-27-11-000-002).
(a) For the left wing:
- Remove 540BZ (Ref. AMM TASK 57-27-12-000-002).
- Remove 640BZ (Ref. AMM TASK 57-27-12-000-002).
C. Get Access
(1) Put the ACCESS PLATFORM 5M (16 FT)- ADJUSTABLE in position below the applicable underwing tank access panels:
(a) For the left wing:
(b) For the right wing:
(2) Remove the applicable underwing tank access panels (Ref. AMM TASK 28-10-00-910-002):
(a) For the left wing:
(a) For the left wing:
Subtask 28-12-00-480-050-B ** ON A/C NOT FOR ALL (1) Put the ACCESS PLATFORM 5M (16 FT)- ADJUSTABLE in position below the applicable underwing tank access panels:
(a) For the left wing:
(b) For the right wing:
(2) Remove the applicable underwing tank access panels (Ref. AMM TASK 28-10-00-910-002):
(a) For the left wing:
- Remove 540AB (Ref. AMM TASK 57-27-11-000-001).
- Remove 640AB (Ref. AMM TASK 57-27-11-000-001).
(a) For the left wing:
- Remove 540BZ (Ref. AMM TASK 57-27-12-000-002).
- Remove 640BZ (Ref. AMM TASK 57-27-12-000-002).
CAUTION:
DO NOT USE THE FUEL PIPES AND THE EQUIPMENT AS HANDHOLDS WHEN YOU DO WORK IN A FUEL TANK. THIS WILL PREVENT DAMAGE TO THEM.
CAUTION:
YOU MUST ALWAYS PUT CAPS ON DISCONNECTED FUEL VENT PIPES. IF YOU DO NOT DO THIS, CONTAMINATION OF THE FUEL VENT PIPES CAN OCCUR.
CAUTION:
WHEN YOU DO WORK ON OR NEAR FUEL VENT PIPES, BE CAREFUL NOT TO CAUSE DAMAGE TO THEM.
D. Installation of the Adapters and Blanks to the LH (RH) Wing-Tank Vent System
Wing-Tank Vent System - Location and Detail ** ON A/C NOT FOR ALL
Wing-Tank Vent System - Location and Detail ** ON A/C NOT FOR ALL (2) Use a SPATULA - NON METALLIC to remove the sealant from:
- The nuts (1), (7) and (13)
- The bolts (14) and (17)
- The screws (3) and (5).
(a) Remove the nut (7) and the screw (5) from the pipe (4).
(b) Move the bonding lead (6) away from the pipe (4).
(c) Remove the nut (1) and the screw (3) from the pipe (4).
(d) Move the bonding lead (2) away from the pipe (4).
(e) Remove the nuts (13) and the bolts (14) from the fairlead (15).
(f) Remove the fairlead (15) from the bracket (16).
(g) Remove the bolts (17) from the support bracket (18).
(h) Remove the pipe (4) from the connector (8).
(i) Remove and discard the O-ring (9) from the pipe (4).
(j) Install vent inflation-adapter 98D28004007000 to the connector (8).
(k) Put the valve on vent inflation-adapter 98D28004007000 in the closed position.
(4) Install sphincter blank 98D28204004000 to the drain valve (10) at RIB 2 as follows:
(a) Remove the clamp (11) and the check valve (12) 120QM (121QM) (Ref. AMM TASK 28-12-44-000-003).
(b) Install sphincter blank 98D28204004000 to the drain valve (10).
(5) Install test rig air-pressure 98L28004035000 to vent inflation-adapter 98D28004007000 as follows:
(a) Connect fuel test-hose 98D28204003000 to vent inflation-adapter 98D28004007000.
(b) Connect fuel test-hose 98D28204003000 to test rig air-pressure 98L28004035000.
(c) On test rig air-pressure 98L28004035000, make sure that the pressure isolation valve is in the CLOSED position.
(d) Connect the AIR SOURCE 0.3 TO 0.7 BAR (5 TO 10 PSI)- FILTERED, DRY to test rig air-pressure 98L28004035000.
(6) Install vent-stringer duct-blank 98D28004009000 to the vent stringer duct at RIB 22:
(a) Remove the NACA vent intake (Ref. AMM TASK 28-12-47-000-001).
(b) Install vent-stringer duct-blank 98D28004009000 to the vent stringer duct at RIB 22.
(7) Install the float-valve blank 98D28004008000 to the adapter (19) at RIB 15 as follows:
(a) Remove the vent float valve (20) 16QM (17QM) (Ref. AMM TASK 28-12-43-000-002).
(b) Install float valve-blank 98D28004008000 to the adapter (19).
(c) Put the valve on float-valve blank 98D28004008000 in the closed position.
(8) Install sphincter blank 98D28204004000 to the drain valve (23) at RIB 15 as follows:
(a) Remove the clamp (21) and the check valve (22) 52QM (53QM) (Ref. AMM TASK 28-12-44-000-001).
(b) Install sphincter blank 98D28204004000 to the drain valve (23).
CAUTION:
DO NOT USE THE FUEL PIPES AND THE EQUIPMENT AS HANDHOLDS WHEN YOU DO WORK IN A FUEL TANK. THIS WILL PREVENT DAMAGE TO THEM.
CAUTION:
YOU MUST ALWAYS PUT CAPS ON DISCONNECTED FUEL VENT PIPES. IF YOU DO NOT DO THIS, CONTAMINATION OF THE FUEL VENT PIPES CAN OCCUR.
CAUTION:
WHEN YOU DO WORK ON OR NEAR FUEL VENT PIPES, BE CAREFUL NOT TO CAUSE DAMAGE TO THEM.
D. Installation of the Adapters and Blanks to the LH (RH) Wing-Tank Vent System (1) Use the applicable items from the 98D28004005000 VENT STRINGER LEAK TEST KIT.
(2) Use a SPATULA - NON METALLIC to remove the sealant from:
- The nuts (1), (7) and (13)
- The bolts (14) and (17)
- The screws (3) and (5).
(a) Remove the nut (7) and the screw (5) from the pipe (4).
(b) Move the bonding lead (6) away from the pipe (4).
(c) Remove the nut (1) and the screw (3) from the pipe (4).
(d) Move the bonding lead (2) away from the pipe (4).
(e) Remove the nut (13) and the bolts (14) from the fairlead (15).
(f) Remove the fairlead (15) from the bracket (16).
(g) Remove the bolts (17) from the support bracket (18).
(h) Remove the pipe (4) from the connector (8).
(i) Remove and discard the O-ring (9) from the pipe (4).
(j) Install vent inflation-adapter 98D28004007000 to the connector (8).
(k) Put the valve on vent inflation-adapter 98D28004007000 in the closed position.
(4) Install sphincter blank 98D28204004000 to the drain valve (10) at RIB 2 as follows:
(a) Remove the clamp (11) and the check valve (12) 120QM (121QM) (Ref. AMM TASK 28-12-44-000-003).
(b) Install sphincter blank 98D28204004000 to the drain valve (10).
(5) Install test rig air-pressure 98L28004035000 to vent inflation-adapter 98D28004007000:
(a) Connect fuel test-hose 98D28204003000 to vent inflation-adapter 98D28004007000.
(b) Connect fuel test-hose 98D28204003000 to test rig air-pressure 98L28004035000.
(c) On test rig air-pressure 98L28004035000, make sure that the pressure isolation valve is in the CLOSED position.
(d) Connect the AIR SOURCE 0.3 TO 0.7 BAR (5 TO 10 PSI)- FILTERED, DRY to test rig air-pressure 98L28004035000.
(6) Install vent-stringer duct-blank 98D28004009000 to the vent stringer duct at RIB 22 as follows:
(a) Remove the NACA vent intake (Ref. AMM TASK 28-12-47-000-001).
(b) Install vent-stringer duct-blank 98D28004009000 to the vent stringer duct at RIB 22.
Subtask 28-12-00-730-050-A ** ON A/C NOT FOR ALL
A. Pressure Test of the Wing-Tank Vent System
(b) Slowly open the pressure isolation valve on test rig air-pressure 98L28004035000.
(c) Increase the air pressure until the pressure gage on the vent inflation adapter shows 0.69 bar (10 psi).
(d) Make sure that there is a free flow of air from float-valve blank 98D28004008000 at RIB 15:
1 If there is no free flow of air, stop the test and release the air pressure at a rate of not more than 0.07 bar (1 psi)/sec.
2 Make sure that there is no blockage in the system.
(e) Slowly close the pressure isolation valve on test rig air-pressure 98L28004035000 until the pressure gage at the vent inflation adapter at RIB 2 shows 0 bar (0 psi).
(f) Close the valve on float-valve blank 98D28004008000 at RIB 15.
(g) Remove vent-stringer duct-blank 98D28004009000 from the vent stringer duct at RIB 22.
(h) Slowly open the pressure isolation valve on test rig air-pressure 98L28004035000.
(i) Increase the air pressure until the pressure gage on the vent inflation adapter shows 0.69 bar (10 psi).
(j) Make sure that there is a free flow of air from the vent stringer duct at RIB 22:
1 If there is no free flow of air, stop the test and release the air pressure at a rate of not more than 0.07 bar (1 psi)/sec.
2 Make sure that there is no blockage in the system.
(2) When the free flow air-test is completed satisfactorily:
(a) Slowly close the pressure isolation valve on test rig air-pressure 98L28004035000 until:
(3) Do the air pressure test as follows:
(a) Slowly open the pressure isolation valve on test rig air-pressure 98L28004035000.
(b) Increase the air pressure until the pressure gage on the vent inflation adapter shows 0.69 bar (10 psi).
(c) Let the air pressure become stable at 0.69 bar (10 psi) at vent inflation-adapter 98D28004007000.
(d) Close the valve on vent inflation-adapter 98D28004007000.
(e) Slowly close the pressure isolation valve on test rig air-pressure 98L28004035000.
(f) Keep the wing-tank vent pipes pressure at 0.69 bar (10 psi) for a minimum of 15 minutes.
(g) If there is no pressure drop after 15 minutes, then the test is satisfactory:
1 Do step (i).
(h) If there is a pressure drop after 15 minutes, then the test is unsatisfactory.
(i) Use a WATER - SOAPY SOLUTION or Testing Medium-Leak Detection Bubbles - (Material No.14CBB1) to find the leaks:
1 Do an approved repair and do the test again.
(j) When the test is completed satisfactorily, do the steps that follow:
1 Remove the AIR SOURCE 0.3 TO 0.7 BAR (5 TO 10 PSI)- FILTERED, DRY from test rig air-pressure 98L28004035000.
2 On test rig air-pressure 98L28004035000, set the pressure isolation valve to OPEN position:
4 Slowly open the valve on vent inflation-adapter 98D28004007000:
Subtask 28-12-00-730-050-B ** ON A/C NOT FOR ALL NOTE: Airbus recommends you to keep the test air pressure less than or equal to 0.69 bar (10 psi).
(1) Do the free flow air-test as follows: WARNING:
WHEN YOU USE COMPRESSED AIR:
(a) Open the valve on vent inflation-adapter 98D28004007000 at RIB 2 and float-valve blank 98D28004008000 at RIB 15. - USE THE CORRECT PROTECTION (FACE SHIELD OR GOGGLES)
- DO NOT POINT THE AIRFLOW AT YOURSELF OR OTHER PERSONS.
(b) Slowly open the pressure isolation valve on test rig air-pressure 98L28004035000.
(c) Increase the air pressure until the pressure gage on the vent inflation adapter shows 0.69 bar (10 psi).
(d) Make sure that there is a free flow of air from float-valve blank 98D28004008000 at RIB 15:
1 If there is no free flow of air, stop the test and release the air pressure at a rate of not more than 0.07 bar (1 psi)/sec.
2 Make sure that there is no blockage in the system.
(e) Slowly close the pressure isolation valve on test rig air-pressure 98L28004035000 until the pressure gage at the vent inflation adapter at RIB 2 shows 0 bar (0 psi).
(f) Close the valve on float-valve blank 98D28004008000 at RIB 15.
(g) Remove vent-stringer duct-blank 98D28004009000 from the vent stringer duct at RIB 22.
(h) Slowly open the pressure isolation valve on test rig air-pressure 98L28004035000.
(i) Increase the air pressure until the pressure gage on the vent inflation adapter shows 0.69 bar (10 psi).
(j) Make sure that there is a free flow of air from the vent stringer duct at RIB 22:
1 If there is no free flow of air, stop the test and release the air pressure at a rate of not more than 0.07 bar (1 psi)/sec.
2 Make sure that there is no blockage in the system.
(2) When the free flow air-test is completed satisfactorily:
(a) Slowly close the pressure isolation valve on test rig air-pressure 98L28004035000 until:
- The pressure gage on the vent inflation adapter at RIB 2 shows 0 bar (0 psi).
(3) Do the air pressure test as follows:
(a) Slowly open the pressure isolation valve on test rig air-pressure 98L28004035000.
(b) Increase the air pressure until the pressure gage on the vent inflation adapter shows 0.69 bar (10 psi).
(c) Let the air pressure become stable at 0.69 bar (10 psi) at vent inflation-adapter 98D28004007000.
(d) Close the valve on vent inflation-adapter 98D28004007000.
(e) Slowly close the pressure isolation valve on test rig air-pressure 98L28004035000.
(f) Keep the wing-tank vent pipes pressure at 0.69 bar (10 psi) for a minimum of 15 minutes.
(g) If there is no pressure drop after 15 minutes, then the test is satisfactory:
1 Do step (i).
(h) If there is a pressure drop after 15 minutes, then the test is unsatisfactory.
(i) Use a WATER - SOAPY SOLUTION or Testing Medium-Leak Detection Bubbles - (Material No.14CBB1) to find the leaks:
1 Do an approved repair and do the test again.
(j) When the test is completed satisfactorily, do the steps that follow:
1 Remove the AIR SOURCE 0.3 TO 0.7 BAR (5 TO 10 PSI)- FILTERED, DRY from test rig air-pressure 98L28004035000.
2 On test rig air-pressure 98L28004035000, set the pressure isolation valve to OPEN position:
NOTE: The valve is set to the OPEN position to release the air pressure from test rig air-pressure 98L28004035000.
3 Remove the fuel test-hose 98D28204003000 from test rig air-pressure 98L28004035000 and vent inflation-adapter 98D28004007000. 4 Slowly open the valve on vent inflation-adapter 98D28004007000:
- To release the air pressure at a rate of not more than 0.07 bar (1 psi)/second until the pressure gage shows 0 bar (0 psi).
A. Pressure Test of the Wing-Tank Vent System
(b) Remove vent-stringer duct-blank 98D28004009000 from the vent stringer duct at RIB 22.
(c) Slowly open the pressure isolation valve on test rig air-pressure 98L28004035000.
(d) Increase the air pressure until the pressure gage on the vent inflation adapter shows 0.69 bar (10 psi).
(e) Make sure that there is a free flow of air from the vent stringer duct at RIB 22:
1 If there is no free flow of air, stop the test and release the air pressure at a rate of not more than 0.07 bar (1 psi)/sec.
2 Make sure that there is no blockage in the system.
(2) When the free flow air-test is completed satisfactorily:
(a) Slowly close the pressure isolation valve on test rig air-pressure 98L28004035000 until:
(3) Do the air pressure test as follows:
(a) Slowly open the pressure isolation valve on test rig air-pressure 98L28004035000.
(b) Increase the air pressure until the pressure gage on the vent inflation adapter shows 0.69 bar (10 psi).
(c) Let the air pressure become stable at 0.69 bar (10 psi) at vent inflation-adapter 98D28004007000.
(d) Close the valve on vent inflation-adapter 98D28004007000.
(e) Slowly close the pressure isolation valve on test rig air-pressure 98L28004035000.
(f) Keep the wing-tank vent pipes pressure at 0.69 bar (10 psi) for a minimum of 15 minutes.
(g) If there is no pressure drop after 15 minutes, then the test is satisfactory:
1 Do step (i).
(h) If there is a pressure drop after 15 minutes, then the test is unsatisfactory.
(i) Use WATER - SOAPY SOLUTION or Testing Medium-Leak Detection Bubbles - (Material No.14CBB1) to find the leaks:
1 Do an approved repair and do the test again.
(j) When the test is completed satisfactorily, do the steps that follow:
1 Remove the AIR SOURCE 0.3 TO 0.7 BAR (5 TO 10 PSI)- FILTERED, DRY from test rig air-pressure 98L28004035000.
2 On test rig air-pressure 98L28004035000, set the pressure isolation valve to OPEN position:
4 Slowly open the valve on vent inflation-adapter 98D28004007000:
5. Close-upNOTE: Airbus recommends you to keep the test air pressure less than or equal to 0.69 bar (10 psi).
(1) Do the free flow air-test as follows: WARNING:
WHEN YOU USE COMPRESSED AIR:
(a) Open the valve on vent inflation-adapter 98D28004007000. - USE THE CORRECT PROTECTION (FACE SHIELD OR GOGGLES)
- DO NOT POINT THE AIRFLOW AT YOURSELF OR OTHER PERSONS.
(b) Remove vent-stringer duct-blank 98D28004009000 from the vent stringer duct at RIB 22.
(c) Slowly open the pressure isolation valve on test rig air-pressure 98L28004035000.
(d) Increase the air pressure until the pressure gage on the vent inflation adapter shows 0.69 bar (10 psi).
(e) Make sure that there is a free flow of air from the vent stringer duct at RIB 22:
1 If there is no free flow of air, stop the test and release the air pressure at a rate of not more than 0.07 bar (1 psi)/sec.
2 Make sure that there is no blockage in the system.
(2) When the free flow air-test is completed satisfactorily:
(a) Slowly close the pressure isolation valve on test rig air-pressure 98L28004035000 until:
- The pressure gage on the vent inflation adapter at RIB 2 shows 0 bar (0.00 psi).
(3) Do the air pressure test as follows:
(a) Slowly open the pressure isolation valve on test rig air-pressure 98L28004035000.
(b) Increase the air pressure until the pressure gage on the vent inflation adapter shows 0.69 bar (10 psi).
(c) Let the air pressure become stable at 0.69 bar (10 psi) at vent inflation-adapter 98D28004007000.
(d) Close the valve on vent inflation-adapter 98D28004007000.
(e) Slowly close the pressure isolation valve on test rig air-pressure 98L28004035000.
(f) Keep the wing-tank vent pipes pressure at 0.69 bar (10 psi) for a minimum of 15 minutes.
(g) If there is no pressure drop after 15 minutes, then the test is satisfactory:
1 Do step (i).
(h) If there is a pressure drop after 15 minutes, then the test is unsatisfactory.
(i) Use WATER - SOAPY SOLUTION or Testing Medium-Leak Detection Bubbles - (Material No.14CBB1) to find the leaks:
1 Do an approved repair and do the test again.
(j) When the test is completed satisfactorily, do the steps that follow:
1 Remove the AIR SOURCE 0.3 TO 0.7 BAR (5 TO 10 PSI)- FILTERED, DRY from test rig air-pressure 98L28004035000.
2 On test rig air-pressure 98L28004035000, set the pressure isolation valve to OPEN position:
- To release the pressure from the test rig air-pressure 98L28004035000.
NOTE: The valve is set to the OPEN position to release the air pressure from the test rig air-pressure 98L28004035000.
3 Remove fuel test-hose 98D28204003000 from test rig air-pressure 98L28004035000 and from vent inflation-adapter 98D28004007000. 4 Slowly open the valve on vent inflation-adapter 98D28004007000:
- To release the air pressure at a rate of not more than 0.07 bar (1 psi)/second until the pressure gage shows 0 bar (0 psi).
Subtask 28-12-00-080-050-B ** ON A/C NOT FOR ALL
A. Removal of the Adapters and Blanks from the LH (RH) Wing-Tank Vent System
Wing-Tank Vent System - Location and Detail ** ON A/C NOT FOR ALL
Wing-Tank Vent System - Location and Detail ** ON A/C NOT FOR ALL
(a) Do a visual inspection of the component interface and/or the adjacent area.
(b) Lubricate the new AIPC 28-12-85-22-180 O-RING (9) or AIPC 28-12-05-30-180 ORING (9) with Mineral Oil base Grease-- Vaseline or Petrolatum - (Material No.03FAB1) .
(2) Removal of the vent-stringer duct-blank 98D28004009000 and installation of the NACA vent intake at RIB 22:
(a) Remove the vent-stringer duct-blank 98D28004009000 from the vent stringer duct at RIB 22.
(b) Install the NACA vent intake (Ref. AMM TASK 28-12-47-400-001).
(3) Removal of the sphincter blank 98D28204004000 and installation of the check valve (22) 52QM (53QM) at RIB 15:
(a) Remove the sphincter blank 98D28204004000 from the drain valve (23).
(b) Install the check valve (22) 52QM (53QM) and the clamp (21) (Ref. AMM TASK 28-12-44-400-001).
(4) Removal of the float valve blank 98D28004008000 and installation of the float valve (20) at RIB 15:
(a) Remove the float valve blank 98D28004008000 from the adapter (19).
(b) Install the vent float valve (20) 16QM(17QM) (Ref. AMM TASK 28-12-43-400-002).
(5) Removal of the sphincter blank 98D28204004000 and installation of the check valve (12) 120QM (121QM) at RIB 2:
(a) Remove the sphincter blank 98D28204004000 from the drain valve (10).
(b) Install the check valve (12) 120QM (121QM) and the clamp (11) (Ref. AMM TASK 28-12-44-400-003).
(6) Removal of the vent inflation adapter 98D28004007000 and installation of the pipe (4) at RIB 2:
(a) Remove the vent inflation adapter 98D28004007000 from the connector (8).
(b) Install the O-ring (9) on the pipe (4).
(c) Install the pipe (4) to the connector (8).
(d) Install the pipe (4) and the fairlead (15) to the bracket (16) with the bolts (14) and the nuts (13).
(e) TORQUE the nuts (13) to between 0.13 and 0.11 m.daN (11.50 and 9.73 lbf.in )
.
(f) Install the pipe (4) to the support bracket (18) with the bolts (17).
(g) Tighten the bolts (17) (Ref. AMM TASK 20-21-11-911-001).
(h) Attach the bonding lead (2) to the pipe (4) with the screw (3) and the nut (1) (Ref. AMM TASK 20-28-00-912-802).
(i) TORQUE the nut (1) to between 0.16 and 0.14 m.daN (14.16 and 12.39 lbf.in )
.
(j) Attach the bonding lead (6) to the pipe (4) with the screw (5) and the nut (7) (Ref. AMM TASK 20-28-00-912-802).
(k) TORQUE the nut (7) to between 0.16 and 0.14 m.daN (14.16 and 12.39 lbf.in )
.
Subtask 28-12-00-080-050-C ** ON A/C NOT FOR ALL
Wing-Tank Vent System - Location and Detail ** ON A/C NOT FOR ALL
Wing-Tank Vent System - Location and Detail ** ON A/C NOT FOR ALL CAUTION:
MAKE SURE THAT ALL THE BLEED/INFLATION ADAPTERS AND BLANKS ARE REMOVED FROM THE FUEL PIPE SYSTEM. IF THE BLANKS ARE NOT REMOVED, DAMAGE WILL OCCUR TO THE AIRCRAFT.
(1) Preparation of components for installation: (a) Do a visual inspection of the component interface and/or the adjacent area.
(b) Lubricate the new AIPC 28-12-85-22-180 O-RING (9) or AIPC 28-12-05-30-180 ORING (9) with Mineral Oil base Grease-- Vaseline or Petrolatum - (Material No.03FAB1) .
(2) Removal of the vent-stringer duct-blank 98D28004009000 and installation of the NACA vent intake at RIB 22:
(a) Remove the vent-stringer duct-blank 98D28004009000 from the vent stringer duct at RIB 22.
(b) Install the NACA vent intake (Ref. AMM TASK 28-12-47-400-001).
(3) Removal of the sphincter blank 98D28204004000 and installation of the check valve (22) 52QM (53QM) at RIB 15:
(a) Remove the sphincter blank 98D28204004000 from the drain valve (23).
(b) Install the check valve (22) 52QM (53QM) and the clamp (21) (Ref. AMM TASK 28-12-44-400-001).
(4) Removal of the float valve blank 98D28004008000 and installation of the float valve (20) at RIB 15:
(a) Remove the float valve blank 98D28004008000 from the adapter (19).
(b) Install the vent float valve (20) 16QM(17QM) (Ref. AMM TASK 28-12-43-400-002).
(5) Removal of the sphincter blank 98D28204004000 and installation of the check valve (12) 120QM (121QM) at RIB 2:
(a) Remove the sphincter blank 98D28204004000 from the drain valve (10).
(b) Install the check valve (12) 120QM (121QM) and the clamp (11) (Ref. AMM TASK 28-12-44-400-003).
(6) Removal of the vent inflation adapter 98D28004007000 and installation of the pipe (4) at RIB 2:
(a) Remove the vent inflation adapter 98D28004007000 from the connector (8).
(b) Install the O-ring (9) on the pipe (4).
(c) Install the pipe (4) to the connector (8).
(d) Install the pipe (4) and the fairlead (15) to the bracket (16) with the bolts (14) and the nuts (13).
(e) TORQUE the nuts (13) to between 0.13 and 0.11 m.daN (11.50 and 9.73 lbf.in )
. (f) Install the pipe (4) to the support bracket (18) with the bolts (17).
(g) Tighten the bolts (17) (Ref. AMM TASK 20-21-11-911-001).
(h) Attach the bonding lead (2) to the pipe (4) with the screw (3) and the nut (1) (Ref. AMM TASK 20-28-00-912-802).
(i) TORQUE the nut (1) to between 0.16 and 0.14 m.daN (14.16 and 12.39 lbf.in )
. (j) Attach the bonding lead (6) to the pipe (4) with the screw (5) and the nut (7) (Ref. AMM TASK 20-28-00-912-802).
(k) TORQUE the nut (7) to between 0.16 and 0.14 m.daN (14.16 and 12.39 lbf.in )
. A. Removal of the Adapters and Blanks from the LH (RH) Wing-Tank Vent System
(a) Do a visual inspection of the component interface and/or the adjacent area.
(b) Lubricate the new AIPC 28-12-85-22-180 O-RING (9) or AIPC 28-12-05-30-180 ORING (9) with Mineral Oil base Grease-- Vaseline or Petrolatum - (Material No.03FAB1) .
(2) Removal of the vent stringer duct blank 98D28004009000 and installation of the NACA vent intake at RIB 22:
(a) Remove the vent stringer duct blank 98D28004009000 from the vent stringer duct at RIB 22.
(b) Install the NACA vent intake (Ref. AMM TASK 28-12-47-400-001).
(3) Removal of the sphincter blank 98D28204004000 and installation of the check valve (12) 120QM (121QM) at RIB 2:
(a) Remove the sphincter blank 98D28204004000 from the drain valve (10).
(b) Install the check valve (12) 120QM (121QM) and the clamp (11) (Ref. AMM TASK 28-12-44-400-003).
(4) Removal of the vent inflation adapter 98D28004007000 and installation of the pipe (4) at RIB 2:
(a) Remove the vent inflation adapter 98D28004007000 from the connector (8).
(b) Install the O-ring (9) on the pipe (4).
(c) Install the pipe (4) to the connector (8).
(d) Install the pipe (4) and the fairlead (15) to the bracket (16) with the bolts (14) and the nuts (13).
(e) TORQUE the nuts (13) to between 0.13 and 0.11 m.daN (11.50 and 9.73 lbf.in )
.
(f) Install the pipe (4) to the support bracket (18) with the bolts (17).
(g) Tighten the bolts (17) (Ref. AMM TASK 20-21-11-911-001).
(h) Attach the bonding lead (2) to the pipe (4) with the screw (3) and the nut (1) (Ref. AMM TASK 20-28-00-912-802).
(i) TORQUE the nut (1) to between 0.16 and 0.14 m.daN (14.16 and 12.39 lbf.in )
.
(j) Attach the bonding lead (6) to the pipe (4) with the screw (5) and the nut (7) (Ref. AMM TASK 20-28-00-912-802).
(k) TORQUE the nut (7) to between 0.16 and 0.14 m.daN (14.16 and 12.39 lbf.in )
.
Subtask 28-12-00-760-050-B CAUTION:
MAKE SURE THAT ALL THE BLEED/INFLATION ADAPTERS AND BLANKS ARE REMOVED FROM THE FUEL PIPE SYSTEM. IF THE BLANKS ARE NOT REMOVED, DAMAGE WILL OCCUR TO THE AIRCRAFT.
(1) Preparation of components for installation: (a) Do a visual inspection of the component interface and/or the adjacent area.
(b) Lubricate the new AIPC 28-12-85-22-180 O-RING (9) or AIPC 28-12-05-30-180 ORING (9) with Mineral Oil base Grease-- Vaseline or Petrolatum - (Material No.03FAB1) .
(2) Removal of the vent stringer duct blank 98D28004009000 and installation of the NACA vent intake at RIB 22:
(a) Remove the vent stringer duct blank 98D28004009000 from the vent stringer duct at RIB 22.
(b) Install the NACA vent intake (Ref. AMM TASK 28-12-47-400-001).
(3) Removal of the sphincter blank 98D28204004000 and installation of the check valve (12) 120QM (121QM) at RIB 2:
(a) Remove the sphincter blank 98D28204004000 from the drain valve (10).
(b) Install the check valve (12) 120QM (121QM) and the clamp (11) (Ref. AMM TASK 28-12-44-400-003).
(4) Removal of the vent inflation adapter 98D28004007000 and installation of the pipe (4) at RIB 2:
(a) Remove the vent inflation adapter 98D28004007000 from the connector (8).
(b) Install the O-ring (9) on the pipe (4).
(c) Install the pipe (4) to the connector (8).
(d) Install the pipe (4) and the fairlead (15) to the bracket (16) with the bolts (14) and the nuts (13).
(e) TORQUE the nuts (13) to between 0.13 and 0.11 m.daN (11.50 and 9.73 lbf.in )
. (f) Install the pipe (4) to the support bracket (18) with the bolts (17).
(g) Tighten the bolts (17) (Ref. AMM TASK 20-21-11-911-001).
(h) Attach the bonding lead (2) to the pipe (4) with the screw (3) and the nut (1) (Ref. AMM TASK 20-28-00-912-802).
(i) TORQUE the nut (1) to between 0.16 and 0.14 m.daN (14.16 and 12.39 lbf.in )
. (j) Attach the bonding lead (6) to the pipe (4) with the screw (5) and the nut (7) (Ref. AMM TASK 20-28-00-912-802).
(k) TORQUE the nut (7) to between 0.16 and 0.14 m.daN (14.16 and 12.39 lbf.in )
. B. Electrical Bonding Test
(1) Do the electrical bonding test on the wing-tank vent pipe system (Ref. AMM TASK 20-28-00-912-802) and (Ref. AMM TASK 20-28-00-869-002).
(2) Use a SPATULA - NON METALLIC to apply a layer of the Polysulfide Sealant-General Purpose Fillet - (Material No.06AAB1) to:
Subtask 28-12-00-410-063-A ** ON A/C NOT FOR ALL (1) Do the electrical bonding test on the wing-tank vent pipe system (Ref. AMM TASK 20-28-00-912-802) and (Ref. AMM TASK 20-28-00-869-002).
(2) Use a SPATULA - NON METALLIC to apply a layer of the Polysulfide Sealant-General Purpose Fillet - (Material No.06AAB1) to:
- The nuts (1), (7) and (13)
- The bolts (14) and (17)
- The screws (3) and (5).
C. Close Access
(1) Make sure that the work area is clean and clear of tools and other items.
(2) To close the applicable aft fuel-surge door(s):
(a) Remove the 98D57004014000 HOOK-COVER (RIB2-SURGE DOORS) and close the aft fuel-surge door(s):
1 For the left wing:
2 For the right wing:
(3) Install the applicable underwing tank access-panel(s) (Ref. AMM TASK 57-27-11-400-001) and (Ref. AMM TASK 57-27-11-400-002):
(a) For the left wing:
(b) For the right wing:
Subtask 28-12-00-410-063-B ** ON A/C NOT FOR ALL (1) Make sure that the work area is clean and clear of tools and other items.
(2) To close the applicable aft fuel-surge door(s):
(a) Remove the 98D57004014000 HOOK-COVER (RIB2-SURGE DOORS) and close the aft fuel-surge door(s):
1 For the left wing:
2 For the right wing:
(3) Install the applicable underwing tank access-panel(s) (Ref. AMM TASK 57-27-11-400-001) and (Ref. AMM TASK 57-27-11-400-002):
(a) For the left wing:
(b) For the right wing:
C. Close Access
(1) Make sure that the work area is clean and clear of tools and other items.
(2) To close the applicable aft fuel-surge door(s):
(a) Remove the 98D57004014000 HOOK-COVER (RIB2-SURGE DOORS) and close the aft fuel-surge door(s):
1 For the left wing:
2 For the right wing:
(3) Install the applicable underwing tank access-panel(s) (Ref. AMM TASK 57-27-11-400-001):
(a) For the left wing:
(b) For the right wing:
Subtask 28-12-00-410-063-C ** ON A/C NOT FOR ALL (1) Make sure that the work area is clean and clear of tools and other items.
(2) To close the applicable aft fuel-surge door(s):
(a) Remove the 98D57004014000 HOOK-COVER (RIB2-SURGE DOORS) and close the aft fuel-surge door(s):
1 For the left wing:
2 For the right wing:
(3) Install the applicable underwing tank access-panel(s) (Ref. AMM TASK 57-27-11-400-001):
(a) For the left wing:
(b) For the right wing:
C. Close Access
(1) Make sure that the work area is clean and clear of tools and other items.
(2) Install the applicable RIB2 access panels:
(a) For the left wing:
(a) For the left wing:
Subtask 28-12-00-410-063-D ** ON A/C NOT FOR ALL (1) Make sure that the work area is clean and clear of tools and other items.
(2) Install the applicable RIB2 access panels:
(a) For the left wing:
- Install 540BZ (Ref. AMM TASK 57-27-12-400-002).
- Install 640BZ (Ref. AMM TASK 57-27-12-400-002).
(a) For the left wing:
- Install 540AB and 540JB (Ref. AMM TASK 57-27-11-400-001) and (Ref. AMM TASK 57-27-11-400-002).
- Install 640AB and 640JB (Ref. AMM TASK 57-27-11-400-001) and (Ref. AMM TASK 57-27-11-400-002).
C. Close Access
(1) Make sure that the work area is clean and clear of tools and other items.
(2) Install the applicable RIB2 access panels:
(a) For the left wing:
(a) For the left wing:
Subtask 28-12-00-650-060-A (1) Make sure that the work area is clean and clear of tools and other items.
(2) Install the applicable RIB2 access panels:
(a) For the left wing:
- Install 540BZ (Ref. AMM TASK 57-27-12-400-002).
- Install 640BZ (Ref. AMM TASK 57-27-12-400-002).
(a) For the left wing:
- Install 540AB (Ref. AMM TASK 57-27-11-400-001).
- Install 640AB (Ref. AMM TASK 57-27-11-400-001).
D. Refuel
(1) Refuel the applicable wing tanks (Ref. AMM TASK 12-11-28-650-003) or (Ref. AMM TASK 12-11-28-650-004).
Subtask 28-12-00-942-066-A (1) Refuel the applicable wing tanks (Ref. AMM TASK 12-11-28-650-003) or (Ref. AMM TASK 12-11-28-650-004).
E. Removal of Equipment
(1) Remove the ground support and maintenance equipment, the special and standard tools and all other items.
(2) Remove the access platform(s).
(3) Remove the WARNING NOTICE(S).
(4) Remove the SAFETY BARRIERS.
(1) Remove the ground support and maintenance equipment, the special and standard tools and all other items.
(2) Remove the access platform(s).
(3) Remove the WARNING NOTICE(S).
(4) Remove the SAFETY BARRIERS.