W DOC AIRBUS | AMM A320F

Operational Test of the APU Fire-Extinguishing Loop/Squib


TASK 26-22-00-710-001-A
Operational Test of the APU Fire-Extinguishing Loop/Squib


1. Reason for the Job
Self explanatory
2. Job Set-up Information
 A. Fixtures, Tools, Test and Support Equipment
REFERENCE
QTY
DESIGNATION
No specific
AR
SAFETY CLIP - CIRCUIT BREAKER
 B. Referenced Information
REFERENCE
DESIGNATION
TASK 24-41-00-861-002-A
Energize the Aircraft Electrical Circuits from the External Power
TASK 24-41-00-861-002-A-01
Energize the Aircraft Electrical Circuits from the APU
TASK 24-41-00-861-002-A-02
Energize the Aircraft Electrical Circuits from Engine 1(2)
TASK 24-41-00-862-002-A
De-energize the Aircraft Electrical Circuits Supplied from the External Power
TASK 24-41-00-862-002-A-01
De-energize the Aircraft Electrical Circuits Supplied from the APU
TASK 24-41-00-862-002-A-02
De-energize the Aircraft Electrical Circuits Supplied from the Engine 1(2)
TASK 31-60-00-860-001-A
EIS Start Procedure
TASK 31-60-00-860-002-A
EIS Stop Procedure
TASK 33-14-00-710-001-A
Operational Check of the Light Test System
3. Job Set-up
Subtask 26-22-00-860-050-A
A. Aircraft Maintenance Configuration
   (1) Energize the aircraft electrical circuits
(Ref. AMM TASK 24-41-00-861-002).
   (2) Do the EIS start procedure (upper ECAM DU and lower ECAM DU only)
(Ref. AMM TASK 31-60-00-860-001).
   (3) Do the operational test of the annunciator light test system in the cockpit (Ref. AMM TASK 33-14-00-710-001).
Subtask 26-22-00-865-053-A
B. Make sure that this(these) circuit breaker(s) is(are) closed:
PANELDESIGNATIONFINLOCATION
** ON A/C ALL
121VUAPU/FIRE AND OVHT/DET/LOOP B2WGL44
121VUAPU/FIRE AND OVHT/DET/LOOP A1WGL43
121VUAPU/ECB/SPLY1KDL41
121VUAPU/FIRE/EXTIG/SQUIB/B2WFL39
121VUAPU/FIRE/EXTIG/SQUIB/A1WFL38
121VUAPU/FIRE/LP VALVE/NORM4WFM42
121VUAPU/FIRE/LP VALVE/STBY3WFM41
4. Procedure
Subtask 26-22-00-875-050-A ** ON A/C NOT FOR ALL
A. Open, safety and tag this(these) circuit breaker(s):
PANELDESIGNATIONFINLOCATION
** ON A/C NOT FOR ALL
121VUAPU/AUTO/EXTIG/GND/TEST30WFL40
Subtask 26-22-00-710-052-A ** ON A/C NOT FOR ALL
B. Operational Test of the APU Fire-Extinguishing Loop/Squib
  • Make sure that circuit breaker APU AUTO EXTIG GND TEST 30WF (L40) on panel 121VU is open.
NOTE: You can open circuit breaker APU AUTO EXTIG GND TEST 30WF (L40) to prevent an unwanted automatic fire-extinguisher discharge during the test.
ACTION
RESULT
WARNING: DO NOT PUSH THE APU FIRE/TEST PUSHBUTTON SWITCH FOR MORE THAN 3 SECONDS. IF YOU PUSH IT FOR MORE THAN 3 SECONDS, THERE IS A RISK THAT IT WILL CAUSE THE DISCHARGE OF THE APU FIRE-EXTINGUISHER BOTTLE.
1.On APU FIRE panel 20VU:
  • Push and hold the APU FIRE/TEST pushbutton switch for not more than 3 seconds.
On APU FIRE panel 20VU:
  • The APU FIRE light in the APU FIRE pushbutton switch comes on.
  • The DISCH and SQUIB legends in the AGENT pushbutton switch come on.

On glareshield panels 130VU and 131VU:
  • The MASTER WARN lights flash.
  • You hear a continuous repetitive chime.

On the ECAM upper display unit:
  • The warnings that follow come on:
    APU FIRE
    APU FIRE P/B....PUSH.
2.On APU FIRE panel 20VU:
  • Release the APU FIRE/TEST pushbutton switch.
On APU FIRE panel 20VU:
  • The APU FIRE light in the APU FIRE pushbutton switch goes off.
  • The DISCH and SQUIB legends in the AGENT pushbutton switch go off.

On glareshield panels 130VU and 131VU:
  • The MASTER WARN lights go off.
  • The continuous repetitive chime stops.

On the ECAM upper display unit:
  • The warnings that follow go off:
    APU FIRE
    APU FIRE P/B....PUSH.
Subtask 26-22-00-710-052-B ** ON A/C NOT FOR ALL
B. Operational Test of the APU Fire-Extinguishing Loop/Squib
ACTION
RESULT
WARNING: DO NOT PUSH THE APU FIRE/TEST PUSHBUTTON SWITCH FOR MORE THAN 3 SECONDS. IF YOU PUSH IT FOR MORE THAN 3 SECONDS, THERE IS A RISK THAT IT WILL CAUSE THE DISCHARGE OF THE APU FIRE-EXTINGUISHER BOTTLE.
1.On APU FIRE panel 20VU:
  • Push and hold the APU FIRE/TEST pushbutton switch for not more than 3 seconds.
On APU FIRE panel 20VU:
  • The APU FIRE light in the APU FIRE pushbutton switch comes on.
  • The DISCH and SQUIB legends in the AGENT pushbutton switch come on.

On glareshield panels 130VU and 131VU:
  • The MASTER WARN lights flash.
  • You hear a continuous repetitive chime.

On the ECAM upper display unit:
  • The warnings that follow come on:
    APU FIRE
    APU FIRE P/B....PUSH.
2.On APU FIRE panel 20VU:
  • Release the APU FIRE/TEST pushbutton switch.
On APU FIRE panel 20VU:
  • The APU FIRE light in the APU FIRE pushbutton switch goes off.
  • The DISCH and SQUIB legends in the AGENT pushbutton switch go off.

On glareshield panels 130VU and 131VU:
  • The MASTER WARN lights go off.
  • The continuous repetitive chime stops.

On the ECAM upper display unit:
  • The warnings that follow go off:
    APU FIRE
    APU FIRE P/B....PUSH.
Subtask 26-22-00-875-051-A ** ON A/C NOT FOR ALL
C. Remove the safety clip(s) and the tag(s) and close this(these) circuit breaker(s):
PANELDESIGNATIONFINLOCATION
** ON A/C NOT FOR ALL
121VUAPU/AUTO/EXTIG/GND/TEST30WFL40
5. Close-up
Subtask 26-22-00-860-051-A
A. Put the aircraft back to its initial configuration.
   (1) Do the EIS stop procedure
(Ref. AMM TASK 31-60-00-860-002).
   (2) De-energize the aircraft electrical circuits
(Ref. AMM TASK 24-41-00-862-002).
[Rev.10 from 2021] 2026.03.31 23:45:29 UTC