Visual Inspection of the Engine Fire Detection System


TASK 26-12-00-200-802-A
Visual Inspection of the Engine Fire Detection System


WARNING: BE CAREFUL WHEN YOU DO WORK ON THE ENGINE AFTER SHUTDOWN. THE ENGINE CAN STAY HOT FOR A LONG TIME. IF YOU DO NOT OBEY THIS INSTRUCTION, INJURY CAN OCCUR.
WARNING: ALWAYS USE APPLICABLE GLOVES TO TOUCH HOT PARTS. HOT PARTS CAN CAUSE INJURY TO PERSONS.
ZONE: 400
1. Reason for the Job
Use this inspection procedure to examine the engine fire and overheat detection system for correct installation and for damage.
2. Job Set-up Information
 A. Fixtures, Tools, Test and Support Equipment
REFERENCE
QTY
DESIGNATION
No specific
1
ACCESS PLATFORM 2M (6 FT) - ADJUSTABLE
No specific
1
BRUSH - NON METALLIC
No specific
AR
SAFETY CLIP - CIRCUIT BREAKER
No specific
1
WATER - DEIONIZED
98D26203003001
1
CAMBERING TOOL
 B. Work Zones and Access Panels
ZONE/ACCESS
ZONE DESCRIPTION
400
POWER PLANT, NACELLES AND PYLONS
FOR [4020KM1] (POWER PLANT-DEMOUNTABLE, ENG 1)
437AL, 438AR, 451AL, 452AR
FOR [4020KM2] (POWER PLANT-DEMOUNTABLE, ENG 2)
447AL, 448AR, 461AL, 462AR
 C. Referenced Information
REFERENCE
DESIGNATION
TASK 24-42-00-861-001-A
Energize the Ground Service Network from the External Power
TASK 24-42-00-862-001-A
De-energize the Ground Service Network Supplied from the External Power
TASK 26-12-16-400-803-A
Installation of the Pylon Fire Detector
TASK 26-12-17-400-802-A
Installation of the Forward Fire/Overheat Detector
TASK 26-12-17-400-803-A
Installation of the Aft Fire/Overheat Detector
TASK 71-00-00-860-833-A
Procedure to Prevent Engine Motoring
TASK 71-13-00-010-802-A
Opening of the Fan Cowl Doors
TASK 71-13-00-410-802-A
Closing of the Fan Cowl Doors
TASK 78-30-00-040-805-A
Deactivation of the Thrust Reverser System for Ground Maintenance
TASK 78-30-00-440-805-A
Reactivation of the Thrust Reverser System after Ground Maintenance
TASK 78-36-00-010-802-A
Opening of the Thrust Reverser Cowl-Doors
TASK 78-36-00-410-802-A
Closing of the Thrust Reverser Cowl-Doors
F Pylon Fire Detectors ** ON A/C NOT FOR ALL
F Pylon Fire Detectors ** ON A/C NOT FOR ALL
3. Job Set-up
Subtask 26-12-00-861-058-A ** ON A/C NOT FOR ALL
A. Energize the ground service network
(Ref. AMM TASK 24-42-00-861-001).
Subtask 26-12-00-941-054-A ** ON A/C NOT FOR ALL
B. Safety Precautions
   (1) Do the procedure to prevent engine motoring
(Ref. AMM TASK 71-00-00-860-833).
Subtask 26-12-00-865-057-A ** ON A/C NOT FOR ALL
C. Open, safety and tag this(these) circuit breaker(s):
PANELDESIGNATIONFINLOCATION
** ON A/C NOT FOR ALL
FOR FIN: 4020KM1 (POWER PLANTDEMOUNTABLE, ENG 1)
49VUENGINE/1/FIRE DET/LOOP A7WD1A06
121VUENGINE/ENG1/FIRE DET/LOOP B8WD1Q38
FOR FIN: 4020KM2 (POWER PLANTDEMOUNTABLE, ENG 2)
49VUENGINE/2/FIRE DET/LOOP B8WD2A07
121VUENGINE/ENG2/FIRE DET/LOOP A7WD2Q39
Subtask 26-12-00-010-058-A ** ON A/C NOT FOR ALL
D. Get Access
   (1) Open the fan cowl doors (Ref. AMM TASK 71-13-00-010-802):
     (a) FOR [4020KM1] (POWER PLANT-DEMOUNTABLE, ENG 1)
437AL 438AR
     (b) FOR [4020KM2] (POWER PLANT-DEMOUNTABLE, ENG 2)
447AL 448AR
   (2) Put an ACCESS PLATFORM 2M (6 FT) - ADJUSTABLE in position.
Subtask 26-12-00-040-055-A ** ON A/C NOT FOR ALL
E. Deactivation of the Thrust Reverser for Maintenance
WARNING: YOU MUST DEACTIVATE THE THRUST REVERSER BEFORE YOU DO WORK ON OR AROUND IT. IF YOU DO NOT, THE THRUST REVERSER CAN OPERATE ACCIDENTALLY AND CAUSE AN INJURY AND/OR DAMAGE.
   (1) Do the deactivation of the thrust reverser system for ground maintenance (Ref. AMM TASK 78-30-00-040-805).
Subtask 26-12-00-010-059-A ** ON A/C NOT FOR ALL
F. Get Access
   (1) Open the thrust reverser cowl-doors (Ref. AMM TASK 78-36-00-010-802):
     (a) FOR [4020KM1] (POWER PLANT-DEMOUNTABLE, ENG 1)
451AL 452AR
     (b) FOR [4020KM2] (POWER PLANT-DEMOUNTABLE, ENG 2)
461AL 462AR
4. Procedure
Subtask 26-12-00-210-063-A ** ON A/C NOT FOR ALL
A. Visual Inspection of the Pylon Fire Detectors
F Pylon Fire Detectors ** ON A/C NOT FOR ALL
CAUTION: DO NOT USE ELECTRICAL OR PNEUMATIC TOOLS TO LOOSEN OR TIGHTEN THE QUARTER-TURN FASTENER ON THE FIRE DETECTOR CLAMP. ONLY USE A MANUAL SCREWDRIVER. ELECTRICAL OR PNEUMATIC TOOLS WILL CAUSE THE FASTENER TO TURN TOO MUCH AND POSSIBLY TO BREAK.
CAUTION: DO NOT BEND THE MANIFOLD OF THE SENSING ELEMENT. IF YOU BEND IT, YOU CAN CAUSE DAMAGE TO THE WELDING.
   (1) Make sure that the minimum permitted bend radius through the manifold tube and the braze is 150 mm (6 in.) (Detail C).
   (2) Make sure that the bend radius of the sensing elements (1) is 9.5 mm (0.37 in.) minimum (Detail C). Use the 98D26203003001 CAMBERING TOOL to make sure that the pylon fire-detector loop is bent correctly.
   (3) Make sure that the minimum distance between the sensing elements (1) and their supports is 2.54 mm (0.10 in.) (Details D and E).
   (4) Make sure that all the clamps (3) and (6) are correctly closed and the sensing elements (1) are correctly installed. If not, (Ref. AMM TASK 26-12-16-400-803) to close the clamp(s) (3) and (6) with the quarter-turn fastener(s) (2) and (5) and/or install the sensing element(s) (1).
   (5) Make sure that there is no damage or chafing on the fire detectors, the rail assemblies (4) and the related brackets.
   (6) Make sure that there is no damage or chafing on the detection harness insulations to prevent short-circuit.
   (7) For MEGGITT pylon fire-detectors, go to Para. 4.D. to do the cleaning.
Subtask 26-12-00-210-063-B ** ON A/C NOT FOR ALL
A. Visual Inspection of the Pylon Fire Detectors
F Pylon Fire Detectors ** ON A/C NOT FOR ALL
CAUTION: DO NOT USE ELECTRICAL OR PNEUMATIC TOOLS TO LOOSEN OR TIGHTEN THE QUARTER-TURN FASTENER ON THE FIRE DETECTOR CLAMP. ONLY USE A MANUAL SCREWDRIVER. ELECTRICAL OR PNEUMATIC TOOLS WILL CAUSE THE FASTENER TO TURN TOO MUCH AND POSSIBLY TO BREAK.
CAUTION: DO NOT BEND THE MANIFOLD OF THE SENSING ELEMENT. IF YOU BEND IT, YOU CAN CAUSE DAMAGE TO THE WELDING.
   (1) Make sure that the minimum permitted bend radius through the manifold tube and the braze is 150 mm (5.9 in.).
   (2) Make sure that the bend radius of the sensing elements (4) is 9.5 mm (0.37 in.) minimum. Use the 98D26203003001 CAMBERING TOOL to make sure that the pylon fire-detector loop is bent correctly.
   (3) Make sure that the minimum distance between the sensing elements (4) and their supports is 2.54 mm (0.10 in.).
   (4) Make sure that all the clamps (3) and (6) are correctly closed and the sensing elements (4) are correctly installed. If not, (Ref. AMM TASK 26-12-16-400-803) to close the clamp(s) (3) and (6) with the quarter-turn fastener(s) (2) and (5) and/or install the sensing element(s) (4).
   (5) Make sure that there is no damage or chafing on the fire detectors, the rail assemblies (1) and the related brackets.
   (6) Make sure that there is no damage or chafing on the detection harness insulations to prevent short-circuit.
   (7) For MEGGITT pylon fire-detectors, go to Para. 4.D. to do the cleaning.
Subtask 26-12-00-210-064-A ** ON A/C NOT FOR ALL
B. Visual Inspection of the Aft Fire/Overheat Detector
F Aft Fire/Overheat Detector ** ON A/C NOT FOR ALL
   (1) Make sure that the sensing elements (7) follow the contour of the fire detection support rail correctly and that the minimum bend radius is 9.52 mm (0.37 in.).
   (2) Make sure that all the clamp covers (8) and the bolts (9) are installed and closed correctly. If not, (Ref. AMM TASK 26-12-17-400-803) to close the clamp cover(s) (8) with the bolt(s) (9).
   (3) Make sure that there is no damage or chafing on the fire detectors, the rail assemblies and the related brackets.
   (4) Make sure that there is no damage or chafing on the detection harness insulations to prevent short-circuit.
   (5) For MEGGITT aft fire/overheat detectors , go to Para. 4.D. to do the cleaning.
Subtask 26-12-00-210-065-A ** ON A/C NOT FOR ALL
C. Visual Inspection of the Forward Fire/Overheat Detector
F Forward Fire/Overheat Detector ** ON A/C NOT FOR ALL
   (1) Make sure that the sensing elements (10) follow the contour of the fire detection support rail correctly and that the minimum bend radius is 9.52 mm (0.37 in.).
   (2) Make sure that the sensing elements (10) are adjusted on the fire detection support rail so that there is a 0.40 in. (10.16 mm) clearance with the case drain line.
   (3) Make sure that all the dual-element grommets (12) and the single-element grommets (14) are in the correct condition and that the clamp covers (11) and the bolts (13) are installed and closed correctly. If not, (Ref. AMM TASK 26-12-17-400-802) to close the clamp cover(s) (11) with the bolt(s) (13).
   (4) Make sure that there is no damage or chafing on the fire detectors, the rail assemblies and the related brackets.
   (5) Make sure that there is no damage or chafing on the detection harness insulations to prevent short-circuit.
   (6) For MEGGITT forward fire/overheat detectors, go to Para. 4.D. to do the cleaning.
Subtask 26-12-00-100-051-A ** ON A/C NOT FOR ALL
D. Cleaning of the MEGGITT Fire Detectors
   (1) Use a BRUSH - NON METALLIC and WATER - DEIONIZED to clean the ceramic insulation header and studs of the fire detectors.
   (2) Dry the fire detectors fully.
5. Close-up
Subtask 26-12-00-410-060-A ** ON A/C NOT FOR ALL
A. Close Access
   (1) Make sure that the work area is clean and clear of tools and other items.
   (2) Close the thrust reverser cowl-doors (Ref. AMM TASK 78-36-00-410-802):
     (a) FOR [4020KM1] (POWER PLANT-DEMOUNTABLE, ENG 1)
451AL 452AR
     (b) FOR [4020KM2] (POWER PLANT-DEMOUNTABLE, ENG 2)
461AL 462AR
Subtask 26-12-00-440-055-A ** ON A/C NOT FOR ALL
B. Do the reactivation of the thrust reverser system after ground maintenance (Ref. AMM TASK 78-30-00-440-805).
Subtask 26-12-00-410-061-A ** ON A/C NOT FOR ALL
C. Close Access
   (1) Close the fan cowl doors (Ref. AMM TASK 71-13-00-410-802):
     (a) FOR [4020KM1] (POWER PLANT-DEMOUNTABLE, ENG 1)
437AL 438AR
     (b) FOR [4020KM2] (POWER PLANT-DEMOUNTABLE, ENG 2)
447AL 448AR
   (2) Remove the access platform(s).
   (3) Remove the WARNING NOTICE(S).
Subtask 26-12-00-865-058-A ** ON A/C NOT FOR ALL
D. Remove the safety clip(s) and the tag(s) and close this(these) circuit breaker(s):
PANELDESIGNATIONFINLOCATION
** ON A/C NOT FOR ALL
FOR FIN: 4020KM1 (POWER PLANTDEMOUNTABLE, ENG 1)
49VUENGINE/1/FIRE DET/LOOP A7WD1A06
121VUENGINE/ENG1/FIRE DET/LOOP B8WD1Q38
FOR FIN: 4020KM2 (POWER PLANTDEMOUNTABLE, ENG 2)
49VUENGINE/2/FIRE DET/LOOP B8WD2A07
121VUENGINE/ENG2/FIRE DET/LOOP A7WD2Q39
Subtask 26-12-00-862-056-A ** ON A/C NOT FOR ALL
E. De-energize the ground service network
(Ref. AMM TASK 24-42-00-862-001).