W DOC AIRBUS | AMM A320F

Visual Inspection of the Engine Fire Detection System


TASK 26-12-00-200-001-A
Visual Inspection of the Engine Fire Detection System


WARNING: BE CAREFUL WHEN YOU DO WORK ON THE ENGINE PARTS AFTER THE ENGINE SHUTDOWN. USE APPLICABLE THERMAL GLOVES. THE ENGINE PARTS CAN STAY HOT FOR ONE HOUR AFTER SHUTDOWN AND CAN BURN YOU.
1. Reason for the Job
To make sure that the fire detection loops are correctly installed and do not touch their support and/or engine components.
2. Job Set-up Information
 A. Fixtures, Tools, Test and Support Equipment
REFERENCE
QTY
DESIGNATION
No specific
1
ACCESS PLATFORM 1M(3 FT)
No specific
1
BRUSH - NON METALLIC
No specific
AR
SAFETY CLIP - CIRCUIT BREAKER
No specific
AR
WARNING NOTICE(S)
No specific
1
WATER - DEIONIZED
 B. Work Zones and Access Panels
ZONE/ACCESS
ZONE DESCRIPTION
FOR [1000EM1] (ENGINE-1)
437AL, 438AR, 451AL, 452AR
FOR [1000EM2] (ENGINE-2)
447AL, 448AR, 461AL, 462AR
 C. Referenced Information
REFERENCE
DESIGNATION
TASK 26-12-15-000-041-A
Removal of the Fan Fire Detectors
TASK 26-12-16-000-001-A
Removal of the Pylon Fire Detectors
TASK 26-12-17-000-040-A
Removal of the Core Fire Detectors
TASK 71-13-00-010-040-A
Opening of the Fan Cowl Doors
TASK 71-13-00-410-040-A
Closing of the Fan Cowl Doors
TASK 78-30-00-081-041-A
Make the Thrust Reverser Serviceable after Maintenance
TASK 78-30-00-481-041-A
Make the Thrust Reverser Unserviceable for Maintenance
TASK 78-36-00-010-040-A
Opening of the Thrust Reverser Doors
TASK 78-36-00-410-040-A
Closing of the Thrust Reverser Doors
3. Job Set-up
Subtask 26-12-00-941-050-A ** ON A/C NOT FOR ALL
A. Safety Precautions
   (1) On the center pedestal, on the ENG panel 115VU:
     (a) Make sure that the ENG/MODE/CRANK/NORM/IGN/START selector switch is in the NORM position.
     (b) Put a WARNING NOTICE(S) to tell persons not to start the engine.
   (2) Make sure that the engine 1(2) shutdown occurred not less than 5 minutes before you do this procedure.
   (3) On the overhead maintenance panel 50VU:
     (a) Make sure that the ON legend of the ENG/FADEC GND PWR/1(2) pushbutton switch is off.
     (b) Put a WARNING NOTICE(S) to tell persons not to energize the FADEC 1(2).
Subtask 26-12-00-865-063-A ** ON A/C NOT FOR ALL
B. Open, safety and tag this(these) circuit breaker(s):
PANELDESIGNATIONFINLOCATION
** ON A/C NOT FOR ALL
FOR FIN: 1000EM1 (ENGINE1)
49VUENGINE/1/FIRE DET/LOOP A7WD1A06
121VUENGINE/ENG1/FIRE DET/LOOP B8WD1Q38
FOR FIN: 1000EM2 (ENGINE2)
49VUENGINE/2/FIRE DET/LOOP B8WD2A07
121VUENGINE/ENG2/FIRE DET/LOOP A7WD2Q39
Subtask 26-12-00-010-050-A ** ON A/C NOT FOR ALL
C. Get Access
   (1) Open the fan cowl doors: (Ref. AMM TASK 71-13-00-010-040)
     (a) FOR [1000EM1] (ENGINE-1)
437AL 438AR
     (b) FOR [1000EM2] (ENGINE-2)
447AL 448AR
   (2) Put the ACCESS PLATFORM 1M(3 FT) in position.
Subtask 26-12-00-040-050-A ** ON A/C NOT FOR ALL
D. Make the thrust reverser unserviceable (Ref. AMM TASK 78-30-00-481-041).
Subtask 26-12-00-010-051-A ** ON A/C NOT FOR ALL
E. Open the thrust reverser doors: (Ref. AMM TASK 78-36-00-010-040)
   (1) FOR [1000EM1] (ENGINE-1)
451AL 452AR
   (2) FOR [1000EM2] (ENGINE-2)
461AL 462AR
4. Procedure
Subtask 26-12-00-210-050-A ** ON A/C NOT FOR ALL
A. Visual Inspection of the Pylon Fire-Detection Loops
F Pylon Fire Detectors ** ON A/C NOT FOR ALL
   (1) Make sure that the straight length of the sensing element from the responder head welding is a minimum of 20 mm (0.7874 in.) (see Detail A).
   (2) Make sure that the length of the element between the responder head and the first clamp is 100 +10 mm or -10 mm (3.9370 +0.3937 in. or -0.3937 in.) (see Detail A).
   (3) Make sure that the radius of the sensing element is a minimum of 9 mm (0.3543 in.).
   (4) Make sure that the minimum distance between the sensing element and its support is 6 mm (0.2362 in.) (see Detail B).
   (5) Make sure that the maximum distance between the ends of the two sensing elements and the last clamp is 25.4 mm (1.0000 in.) (see Detail C).
   (6) Make sure that all the bushes are in good condition. If they are not, replace them (Ref. AMM TASK 26-12-16-000-001) (see Details B and C).
   (7) Make sure that there is no damage or signs of chafing on the fire detectors, the rail assemblies and the related brackets.
NOTE: Dents, nicks or small pitting are permitted and it is not necessary to replace the sensor because of them.
   (8) To prevent short circuits, make sure that there is no damage or chafing on the detection harness insulations.
   (9) For MEGGITT pylon fire-detectors, go to Para. 4.D. to do the cleaning.
Subtask 26-12-00-210-051-A ** ON A/C NOT FOR ALL
B. Visual Inspection of the Fan Fire-Detection Loops
F Fan Fire Detectors ** ON A/C NOT FOR ALL
   (1) Make sure that the straight length of the sensing element from the responder head welding is a minimum of 20 mm (0.7874 in.).
   (2) Make sure that the sensing element does not touch its support (see Detail B).
   (3) Make sure that all the grommets are in good condition. If they are not, replace them (Ref. AMM TASK 26-12-15-000-041) (see Detail B).
   (4) Make sure that there is no damage or signs of chafing on the fire detectors, the rail assemblies and the related brackets.
NOTE: Dents, nicks or small pitting are permitted and it is not necessary to replace the sensor because of them.
   (5) To prevent short circuits, make sure that there is no damage or signs of chafing on the detection harness insulations.
   (6) Make sure that the distances between the clamps are equal. Thus, if there is engine vibration, there will not be chafing and the sensing elements will not touch the support and/or the engine components.
   (7) For MEGGITT fan fire-detectors, go to Para. 4.D. to do the cleaning.
Subtask 26-12-00-210-052-A ** ON A/C NOT FOR ALL
C. Visual Inspection of the Core Fire-Detection Loops
F Core Fire Detectors ** ON A/C NOT FOR ALL
F Core Fire Detectors ** ON A/C NOT FOR ALL
   (1) Make sure that the straight length of the sensing element from the responder head welding is minimum of 20 mm (0.7874 in.).
   (2) Make sure that the maximum distance between the ends of the two sensing elements and the last clamp is 25.4 mm (1.0000 in.).
   (3) Make sure that the minimum distance between the sensing element and its support is 6 mm (0.2362 in.).
   (4) Make sure that all the bushes are in good condition. If they are not, replace them (Ref. AMM TASK 26-12-17-000-040).
   (5) Make sure that there is no damage or signs of chafing on the fire detectors, the rail assemblies and the related brackets.
NOTE: Dents, nicks or small pitting are permitted and it is not necessary to replace the sensor because of them.
   (6) To prevent short circuits, make sure that there is no damage or signs of chafing on the detection harness insulations.
   (7) Make sure that the distances between the clamps are equal. Thus, if there is engine vibration, there will not be chafing and the sensing elements will not touch the support and/or engine components.
   (8) For MEGGITT core fire-detectors, go to Para. 4.D. to do the cleaning.
Subtask 26-12-00-100-055-A ** ON A/C NOT FOR ALL
D. Cleaning of the MEGGITT Fire Detectors
   (1) Use a BRUSH - NON METALLIC and WATER - DEIONIZED to clean the ceramic insulation header and studs of the fire detectors.
   (2) Dry the fire detectors fully.
5. Close-up
Subtask 26-12-00-410-050-A ** ON A/C NOT FOR ALL
A. Close Access
   (1) Make sure that the work area is clean and clear of tools and other items.
   (2) Close the thrust reverser doors: (Ref. AMM TASK 78-36-00-410-040)
     (a) FOR [1000EM1] (ENGINE-1)
451AL 452AR
     (b) FOR [1000EM2] (ENGINE-2)
461AL 462AR
Subtask 26-12-00-440-050-A ** ON A/C NOT FOR ALL
B. Make the thrust reverser serviceable (Ref. AMM TASK 78-30-00-081-041)
Subtask 26-12-00-410-051-A ** ON A/C NOT FOR ALL
C. Close Access
   (1) Close the fan cowl doors (Ref. AMM TASK 71-13-00-410-040):
     (a) FOR [1000EM1] (ENGINE-1)
437AL 438AR
     (b) FOR [1000EM2] (ENGINE-2)
447AL 448AR
   (2) Remove the access platform(s).
   (3) Remove the WARNING NOTICE(S).
Subtask 26-12-00-865-064-A ** ON A/C NOT FOR ALL
D. Remove the safety clip(s) and the tag(s) and close this(these) circuit breaker(s):
PANELDESIGNATIONFINLOCATION
** ON A/C NOT FOR ALL
FOR FIN: 1000EM1 (ENGINE1)
49VUENGINE/1/FIRE DET/LOOP A7WD1A06
121VUENGINE/ENG1/FIRE DET/LOOP B8WD1Q38
FOR FIN: 1000EM2 (ENGINE2)
49VUENGINE/2/FIRE DET/LOOP B8WD2A07
121VUENGINE/ENG2/FIRE DET/LOOP A7WD2Q39
[Rev.10 from 2021] 2026.03.31 23:42:20 UTC